Article 16U.K.General requirements for type D power-generating modules
1.In addition to fulfilling the requirements listed in Article 13, except for Article 13(2)(b), (6) and (7), Article 14, except for Article 14(2), and Article 15, except for Article 15(3), type D power-generating modules shall fulfil the requirements set out in this Article.
2.Type D power-generating modules shall fulfil the following requirements relating to voltage stability:
(a)with regard to voltage ranges:
(i)
without prejudice to point (a) of Article 14(3) and point (a) of paragraph 3 below, a power-generating module shall be capable of staying connected to the network and operating within the ranges of the network voltage at the connection point, expressed by the voltage at the connection point related to the reference 1 pu voltage, and for the time periods specified in Tables 6.1 and 6.2;
(ii)
the relevant TSO may specify shorter periods of time during which power-generating modules shall be capable of remaining connected to the network in the event of simultaneous overvoltage and underfrequency or simultaneous undervoltage and overfrequency;
(iv)
for the 400 kV grid voltage level (or alternatively commonly referred to as 380 kV level), the reference 1 pu value is 400 kV; for other grid voltage levels, the reference 1 pu voltage may differ for each system operator in the same synchronous area;
Table 6.1
Synchronous area | Voltage range | Time period for operation |
---|
. . . | . . . | . . . |
. . . | . . . |
. . . | . . . |
. . . | . . . | . . . |
. . . | . . . |
Great Britain | [0.90] pu-[1.10] pu | Unlimited |
. . . | . . . | . . . |
. . . | . . . | . . . |
. . . | . . . |
. . . | . . . |
The table shows the minimum time periods during which a power-generating module must be capable of operating for voltages deviating from the reference 1 pu value at the connection point without disconnecting from the network, where the voltage base for pu values is from 110 kV to 300 kV.
Table 6.2
Synchronous area | Voltage range | Time period for operation |
---|
. . . | . . . | . . . |
. . . | . . . |
. . . | . . . |
. . . | . . . | . . . |
. . . | . . . |
Great Britain | [0.90] pu-[1.05] pu | Unlimited |
[1.05] pu-[1.10] pu | 15 minutes |
. . . | . . . | . . . |
. . . | . . . | . . . |
. . . | . . . |
. . . | . . . |
The table shows the minimum time periods during which a power-generating module must be capable of operating for voltages deviating from the reference 1 pu value at the connection point without disconnecting from the network where the voltage base for pu values is from 300 kV to 400 kV.
(b)wider voltage ranges or longer minimum time periods for operation may be agreed between the relevant system operator and the power-generating facility owner in coordination with the relevant TSO. If wider voltage ranges or longer minimum times for operation are economically and technically feasible, the power-generating facility owner shall not unreasonably withhold an agreement;
(c)without prejudice to point (a), the relevant system operator in coordination with the relevant TSO shall have the right to specify voltages at the connection point at which a power-generating module is capable of automatic disconnection. The terms and settings for automatic disconnection shall be agreed between the relevant system operator and the power-generating facility owner.
3.Type D power-generating modules shall fulfil the following requirements in relation to robustness:
(a)with regard to fault-ride-through capability:
(i)
power-generating modules shall be capable of staying connected to the network and continuing to operate stably after the power system has been disturbed by secured faults. That capability shall be in accordance with a voltage-against-time profile at the connection point for fault conditions specified by the relevant TSO.
The voltage-against-time-profile shall express a lower limit of the actual course of the phase-to-phase voltages on the network voltage level at the connection point during a symmetrical fault, as a function of time before, during and after the fault.
That lower limit shall be specified by the relevant TSO, using the parameters set out in Figure 3 and within the ranges set out in Tables 7.1 and 7.2 for type D power-generating modules connected at or above the 110 kV level.
That lower limit shall also be specified by the relevant TSO, using parameters set out in Figure 3 and within the ranges set out in Tables 3.1 and 3.2 for type D power-generating modules connected below the 110 kV level;
(ii)
each TSO shall specify the pre-fault and post-fault conditions for the fault-ride-through capability referred to in point (iv) of Article 14(3)(a). The specified pre-fault and post-fault conditions for the fault-ride-through capability shall be made publicly available;
Table 7.1
Parameters for Figure 3 for fault-ride-through capability of synchronous power-generating modules
Voltage parameters (pu) | Time parameters (seconds) |
---|
Uret: | 0 | tclear: | [0.14]-[0.15] (or [0.14]-[0.25] if system protection and secure operation so require) |
Uclear: | [0.25] | trec1: | tclear-[0.45] |
Urec1: | [0.5]-[0.7] | trec2: | trec1-[0.7] |
Urec2: | [0.85]-[0.9] | trec3: | trec2-[1.5] |
Table 7.2
Parameters for Figure 3 for fault-ride-through capability of power park modules
Voltage parameters (pu) | Time parameters (seconds) |
---|
Uret: | 0 | tclear: | [0.14]-[0.15] (or [0.14]-[0.25] if system protection and secure operation so require) |
Uclear: | Uret | trec1: | tclear |
Urec1: | Uclear | trec2: | trec1 |
Urec2: | [0.85] | trec3: | [1.5]-[3.0] |
(b)at the request of a power-generating facility owner, the relevant system operator shall provide the pre-fault and post-fault conditions to be considered for fault-ride-through capability as an outcome of the calculations at the connection point as specified in point (iv) of Article 14(3)(a) regarding:
(i)
pre-fault minimum short circuit capacity at each connection point expressed in MVA;
(ii)
pre-fault operating point of the power-generating module expressed as active power output and reactive power output at the connection point and voltage at the connection point; and
(iii)
post-fault minimum short circuit capacity at each connection point expressed in MVA;
(c)fault-ride-through capabilities in case of asymmetrical faults shall be specified by each TSO.
4.Type D power-generating modules shall fulfil the following general system management requirements:
(a)with regard to synchronisation, when starting a power-generating module, synchronisation shall be performed by the power-generating facility owner only after authorisation by the relevant system operator;
(b)the power-generating module shall be equipped with the necessary synchronisation facilities;
(c)synchronisation of power-generating modules shall be possible at frequencies within the ranges set out in Table 2;
(d)the relevant system operator and the power-generating facility owner shall agree on the settings of synchronisation devices to be concluded prior to operation of the power-generating module. This agreement shall cover:
(v)
deviation of voltage and frequency.