The Pollution Prevention and Control (Scotland) Regulations 2012

PART BS

Unless described in Part A of this section—

(a)Burning any fuel in a boiler or furnace with a rated thermal input of more than 20 megawatts and less than 50 megawatts,

(b)Burning any fuel in a gas turbine or compression ignition engine with a rated thermal input of more than 20 megawatts and less than 50 megawatts.

[F1(c)Burning any fuel in a combination of appliances with a total rated thermal input of more than 20 megawatts and less than 50 megawatts in an installation to which Schedule 1A applies.]

[F2(d)Burning any fuel in a medium combustion plant with a rated thermal input equal to or greater than 1 megawatt and less than or equal to 20 megawatts.]

Interpretation of Section 1.1S

For the purposes of section 1.1—

“rated thermal input” is the rate at which fuel can be burned at the maximum continuous rating of the appliance multiplied by the net calorific value of the fuel and expressed as megawatts thermal.

[F3Interpretation of Part BS

For the purposes of paragraph (c) of Part B—

(a)“appliance” means a boiler, furnace, gas turbine or compression ignition engine, and

(b)fuel is burned in a combination of appliances where two or more appliances are operated on the same site.]

Textual Amendments