xmlns:atom="http://www.w3.org/2005/Atom" xmlns:atom="http://www.w3.org/2005/Atom"
The efficiency of the 12 V motor generator shall be determined in accordance with ISO 8854:2012, with the exception of the elements specified in this point.
Evidence shall be provided to the type approval authority that the speed ranges of the efficient 12 V motor generator are consistent with those set out in Table 1. The measurements shall be conducted at different operating points, as set out in Table 1. The efficient 12 V motor generator current intensity shall be defined as half of the rated current for all operating points. For each speed the voltage and the output current of the alternator shall be kept constant at 14,3 V.
Operating points
Operating pointi | Holding time[s] | Rotational frequencyni[min– 1] | Frequencyhi |
---|---|---|---|
1 | 1 200 | 1 800 | 0,25 |
2 | 1 200 | 3 000 | 0,40 |
3 | 600 | 6 000 | 0,25 |
4 | 300 | 10 000 | 0,10 |
The efficiency at each operating point shall be calculated in accordance with the following Formula 1:
All efficiency measurements are to be performed consecutively at least five (5) times. The average of the measurements at each operating point ( ) shall be calculated.
The efficiency of the motor generator (ηMG) shall be calculated in accordance with the following Formula 2:
The motor generator leads to saved mechanical power under real-world conditions (ΔPmRW) and type approval conditions (ΔPmTA) as set out in Formula 3.
Where the saved mechanical power under real-world conditions (ΔPmRW) shall be calculated in accordance with Formula 4 and the saved mechanical power under type-approval conditions (ΔPmTA) in accordance with the following Formula 5:
where
:
Power requirement under ‘real-world’ conditions [W], which is 750W
:
Power requirement under type-approval conditions [W], which is 350W
:
Efficiency of the baseline alternator [%], which is 67 %