ANNEX II Ecodesign requirements

1.REQUIREMENTS FOR SEASONAL SPACE HEATING ENERGY EFFICIENCY

(a)

From 26 September 2015 the seasonal space heating energy efficiency and useful efficiencies of heaters shall not fall below the following values:

  • Fuel boiler space heaters with rated heat output ≤ 70 kW and fuel boiler combination heaters with rated heat output ≤ 70 kW, with the exception of type B1 boilers with rated heat output ≤ 10 kW and type B1 combination boilers with rated heat output ≤ 30 kW:

    The seasonal space heating energy efficiency shall not fall below 86 %.

  • Type B1 boilers with rated heat output ≤ 10 kW and type B1 combination boilers with rated heat output ≤ 30 kW:

    The seasonal space heating energy efficiency shall not fall below 75 %.

  • Fuel boiler space heaters with rated heat output > 70 kW and ≤ 400 kW and fuel boiler combination heaters with rated heat output > 70 kW and ≤ 400 kW:

    The useful efficiency at 100 % of the rated heat output shall not fall below 86 %, and the useful efficiency at 30 % of the rated heat output shall not fall below 94 %.

  • Electric boiler space heaters and electric boiler combination heaters:

    The seasonal space heating energy efficiency shall not fall below 30 %.

  • Cogeneration space heaters:

    The seasonal space heating energy efficiency shall not fall below 86 %.

  • Heat pump space heaters and heat pump combination heaters, with the exception of low-temperature heat pumps:

    The seasonal space heating energy efficiency shall not fall below 100 %.

  • Low-temperature heat pumps:

    The seasonal space heating energy efficiency shall not fall below 115 %.

(b)

From 26 September 2017 the seasonal space heating energy efficiency of electric boiler space heaters, electric boiler combination heaters, cogeneration space heaters, heat pump space heaters and heat pump combination heaters shall not fall below the following values:

  • Electric boiler space heaters and electric boiler combination heaters:

    The seasonal space heating energy efficiency shall not fall below 36 %.

  • Cogeneration space heaters:

    The seasonal space heating energy efficiency shall not fall below 100 %.

  • Heat pump space heaters and heat pump combination heaters, with the exception of low-temperature heat pumps:

    The seasonal space heating energy efficiency shall not fall below 110 %.

  • Low-temperature heat pumps:

    The seasonal space heating energy efficiency shall not fall below 125 %.

2.REQUIREMENTS FOR WATER HEATING ENERGY EFFICIENCY

(a)From 26 September 2015 the water heating energy efficiency of combination heaters shall not fall below the following values:

Declared load profile 3XS XXS XS S M L XL XXL 3XL 4XL
Water heating energy efficiency22 %23 %26 %26 %30 %30 %30 %32 %32 %32 %

(b)From 26 September 2017 the water heating energy efficiency of combination heaters shall not fall below the following values:

Declared load profile 3XS XXS XS S M L XL XXL 3XL 4XL
Water heating energy efficiency32 %32 %32 %32 %36 %37 %38 %60 %64 %64 %

3.REQUIREMENTS FOR SOUND POWER LEVEL

From 26 September 2015 the sound power level of heat pump space heaters and heat pump combination heaters shall not exceed the following values:

Rated heat output ≤ 6 kWRated heat output > 6 kW and ≤ 12 kWRated heat output > 12 kW and ≤ 30 kWRated heat output > 30 kW and ≤ 70 kW
Sound power level (LWA ), indoorsSound power level (LWA ), outdoorsSound power level (LWA ), indoorsSound power level (LWA ), outdoorsSound power level (LWA ), indoorsSound power level (LWA ), outdoorsSound power level (LWA ), indoorsSound power level (LWA ), outdoors
60 dB65 dB65 dB70 dB70 dB78 dB80 dB88 dB

4.REQUIREMENTS FOR EMISSIONS OF NITROGEN OXIDES

(a)From 26 September 2018 emissions of nitrogen oxides, expressed in nitrogen dioxide, of heaters shall not exceed the following values:

5.REQUIREMENTS FOR PRODUCT INFORMATION

From 26 September 2015 the following product information on heaters shall be provided:

(a)

the instruction manuals for installers and end-users, and free access websites of manufacturers, their authorised representatives and importers shall contain the following elements:

  • for boiler space heaters, boiler combination heaters and cogeneration space heaters, the technical parameters set out in Table 1, measured and calculated in accordance with Annex III;

  • for heat pump space heaters and heat pump combination heaters, the technical parameters set out in Table 2, measured and calculated in accordance with Annex III;

  • any specific precautions that shall be taken when the heater is assembled, installed or maintained;

  • for type B1 boilers and type B1 combination boilers, their characteristics and the following standard text: ‘This natural draught boiler is intended to be connected only to a flue shared between multiple dwellings in existing buildings that evacuates the residues of combustion to the outside of the room containing the boiler. It draws the combustion air directly from the room and incorporates a draught diverter. Due to lower efficiency, any other use of this boiler shall be avoided and would result in higher energy consumption and higher operating costs.’;

  • for heat generators designed for heaters, and heater housings to be equipped with such heat generators, their characteristics, the requirements for assembly, to ensure compliance with the ecodesign requirements for heaters and, where appropriate, the list of combinations recommended by the manufacturer;

  • information relevant for disassembly, recycling and/or disposal at end-of-life;

(b)

the technical documentation for the purposes of conformity assessment pursuant to Article 4 shall contain the following elements:

  • the elements specified in point (a);

  • for heat pump space heaters and heat pump combination heaters where the information relating to a specific model comprising a combination of indoor and outdoor units has been obtained by calculation on the basis of design and/or extrapolation from other combinations, the details of such calculations and/or extrapolations, and of any tests undertaken to verify the accuracy of the calculations, including details of the mathematical model for calculating the performance of such combinations and details of the measurements taken to verify this model;

(c)

the following information shall be durably marked on the heater:

  • if applicable, ‘type B1 boiler’ or ‘type B1 combination boiler’;

  • for cogeneration space heaters, the electrical capacity.

Table 1

Information requirements for boiler space heaters, boiler combination heaters and cogeneration space heaters

a

High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.

b

Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C return temperature (at heater inlet).

Model(s): [information identifying the model(s) to which the information relates]
Condensing boiler: [yes/no]
Low-temperatureb boiler: [yes/no]
B1 boiler: [yes/no]
Cogeneration space heater: [yes/no]If yes, equipped with a supplementary heater: [yes/no]
Combination heater: [yes/no]
Item Symbol Value Unit Item Symbol Value Unit
Rated heat output PratedxkW Seasonal space heating energy efficiency ηs x%
For boiler space heaters and boiler combination heaters: Useful heat outputFor boiler space heaters and boiler combination heaters: Useful efficiency
At rated heat output and high-temperature regimea P4 x,xkWAt rated heat output and high-temperature regimea η4 x,x%
At 30 % of rated heat output and low-temperature regimeb P1 x,xkWAt 30 % of rated heat output and low-temperature regimeb η1 x,x%
For cogeneration space heaters: Useful heat outputFor cogeneration space heaters: Useful efficiency
At rated heat output of cogeneration space heater with supplementary heater disabled PCHP100 + Sup0 x,xkWAt rated heat output of cogeneration space heater with supplementary heater disabled ηCHP100 + Sup0 x,x%
At rated heat output of cogeneration space heater with supplementary heater enabled PCHP100 + Sup100 x,xkWAt rated heat output of cogeneration space heater with supplementary heater enabled ηCHP100 + Sup100 x,x%
For cogeneration space heaters: Electrical efficiencySupplementary heater
At rated heat output of cogeneration space heater with supplementary heater disabled ηel,CHP100 + Sup0 x,x%Rated heat output Psupx,xkW
At rated heat output of cogeneration space heater with supplementary heater enabled ηel,CHP100 + Sup100 x,x%Type of energy input
Auxiliary electricity consumptionOther items
At full load elmaxx,xxxkWStandby heat loss Pstby x,xxxkW
At part load elminx,xxxkWIgnition burner power consumption Pign x,xxxkW
In standby mode PSB x,xxxkWEmissions of nitrogen oxides NOx xmg/kWh
For combination heaters:
Declared load profile Water heating energy efficiency ηwh x%
Daily electricity consumption Qelec x,xxxkWhDaily fuel consumption Qfuel x,xxxkWh
Contact detailsName and address of the manufacturer or its authorised representative.

Table 2

Information requirements for heat pump space heaters and heat pump combination heaters

a

For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

b

If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

Model(s): [information identifying the model(s) to which the information relates]
Air-to-water heat pump: [yes/no]
Water-to-water heat pump: [yes/no]
Brine-to-water heat pump: [yes/no]
Low-temperature heat pump: [yes/no]
Equipped with a supplementary heater: [yes/no]
Heat pump combination heater: [yes/no]
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pumps, parameters shall be declared for low-temperature application.
Parameters shall be declared for average climate conditions.
Item Symbol Value Unit Item Symbol Value Unit
Rated heat output a PratedxkW Seasonal space heating energy efficiency ηs x%
Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj
Tj = – 7 °C Pdhx,xkW Tj = – 7 °C COPd or PERdx,xx or x,x– or %
Tj = + 2 °C Pdhx,xkW Tj = + 2 °C COPd or PERdx,xx or x,x– or %
Tj = + 7 °C Pdhx,xkW Tj = + 7 °C COPd or PERdx,xx or x,x– or %
Tj = + 12 °C Pdhx,xkW Tj = + 12 °C COPd or PERdx,xx or x,x– or %
Tj = bivalent temperature Pdhx,xkW Tj = bivalent temperature COPd or PERdx,xx or x,x– or %
Tj = operation limit temperature Pdhx,xkW Tj = operation limit temperature COPd or PERdx,xx or x,x– or %
For air-to-water heat pumps: Tj = – 15 °C (if TOL < – 20 °C) Pdhx,xkWFor air-to-water heat pumps: Tj = – 15 °C (if TOL < – 20 °C) COPd or PERdx,xx or x,x– or %
Bivalent temperature Tbiv x°CFor air-to-water heat pumps: Operation limit temperature TOLx°C
Cycling interval capacity for heating Pcychx,xkWCycling interval efficiency COPcyc or PERcycx,xx or x,x– or %
Degradation co-efficientb Cdhx,xHeating water operating limit temperature WTOLx°C
Power consumption in modes other than active modeSupplementary heater
Off mode POFF x,xxxkWRated heat outputa Psupx,xkW
Thermostat-off mode PTO x,xxxkW
Standby mode PSB x,xxxkWType of energy input
Crankcase heater mode PCK x,xxxkW
Other items
Capacity controlfixed/variableFor air-to-water heat pumps: Rated air flow rate, outdoorsxm3/h
Sound power level, indoors/outdoors LWA x/xdBFor water-/brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchangerxm3/h
Emissions of nitrogen oxides NOx xmg/kWh
For heat pump combination heater:
Declared load profilex Water heating energy efficiency ηwh x%
Daily electricity consumption Qelec x,xxxkWhDaily fuel consumption Qfuel x,xxxkWh
Contact detailsName and address of the manufacturer or its authorised representative.