Commission Regulation (EU) 2016/1388Dangos y teitl llawn

Commission Regulation (EU) 2016/1388 of 17 August 2016 establishing a Network Code on Demand Connection (Text with EEA relevance)

ANNEX I Frequency ranges and time periods referred to in Article 12(1)

Synchronous areaFrequency rangeTime period for operation
Continental Europe47,5 Hz-48,5 HzTo be specified by each TSO, but not less than 30 minutes
48,5 Hz-49,0 HzTo be specified by each TSO, but not less than the period for 47,5 Hz-48,5 Hz
49,0 Hz-51,0 HzUnlimited
51,0 Hz-51,5 Hz30 minutes
Nordic47,5 Hz-48,5 Hz30 minutes
48,5 Hz-49,0 HzTo be specified by each TSO, but not less than 30 minutes
49,0 Hz-51,0 HzUnlimited
51,0 Hz-51,5 Hz30 minutes
Great Britain47,0 Hz-47,5 Hz20 seconds
47,5 Hz-48,5 Hz90 minutes
48,5 Hz-49,0 HzTo be specified by each TSO, but not less than 90 minutes
49,0 Hz-51,0 HzUnlimited
51,0 Hz-51,5 Hz90 minutes
51,5 Hz-52,0 Hz15 minutes
Ireland and Northern Ireland47,5 Hz-48,5 Hz90 minutes
48,5 Hz-49,0 HzTo be specified by each TSO, but not less than 90 minutes
49,0 Hz-51,0 HzUnlimited
51,0 Hz-51,5 Hz90 minutes
Baltic47,5 Hz-48,5 HzTo be specified by each TSO, but not less than 30 minutes
48,5 Hz-49,0 HzTo be specified by each TSO, but not less than the period for 47,5 Hz-48,5 Hz
49,0 Hz-51,0 HzUnlimited
51,0 Hz-51,5 HzTo be specified by each TSO, but not less than 30 minutes

The table shows the minimum time periods for which a transmission-connected demand facility, a transmission-connected distribution facility or a distribution system has to be capable of operating on different frequencies, deviating from a nominal value, without disconnecting from the network.