Voltage ranges referred to in Article 27:
Voltage ranges at the connection point between 110 kV and 300 kV
Synchronous area | Voltage range |
---|---|
Continental Europe | 0,90 pu-1,118 pu |
Nordic | 0,90 pu-1,05 pu |
Great Britain | 0,90 pu-1,10 pu |
Ireland and Northern Ireland | 0,90 pu-1,118 pu |
Baltic | 0,90 pu-1,118 pu |
Voltage ranges at the connection point between 300 kV and 400 kV
Synchronous area | Voltage range |
---|---|
Continental Europe | 0,90 pu-1,05 pu |
Nordic | 0,90 pu-1,05 pu |
Great Britain | 0,90 pu-1,05 pu |
Ireland and Northern Ireland | 0,90 pu-1,05 pu |
Baltic | 0,90 pu-1,097 pu |