Commission Regulation (EU) 2017/1485 of 2 August 2017 establishing a guideline on electricity transmission system operation (Text with EEA relevance)

 Help about what version

Pa Fersiwn

 Help about advanced features

Nodweddion Uwch

 Help about UK-EU Regulation

Legislation originating from the EU

When the UK left the EU, legislation.gov.uk published EU legislation that had been published by the EU up to IP completion day (31 December 2020 11.00 p.m.). On legislation.gov.uk, these items of legislation are kept up-to-date with any amendments made by the UK since then.

Close

Mae hon yn eitem o ddeddfwriaeth sy’n deillio o’r UE

Mae unrhyw newidiadau sydd wedi cael eu gwneud yn barod gan y tîm yn ymddangos yn y cynnwys a chyfeirir atynt gydag anodiadau.Ar ôl y diwrnod ymadael bydd tair fersiwn o’r ddeddfwriaeth yma i’w gwirio at ddibenion gwahanol. Y fersiwn legislation.gov.uk yw’r fersiwn sy’n weithredol yn y Deyrnas Unedig. Y Fersiwn UE sydd ar EUR-lex ar hyn o bryd yw’r fersiwn sy’n weithredol yn yr UE h.y. efallai y bydd arnoch angen y fersiwn hon os byddwch yn gweithredu busnes yn yr UE. EUR-Lex Y fersiwn yn yr archif ar y we yw’r fersiwn swyddogol o’r ddeddfwriaeth fel yr oedd ar y diwrnod ymadael cyn cael ei chyhoeddi ar legislation.gov.uk ac unrhyw newidiadau ac effeithiau a weithredwyd yn y Deyrnas Unedig wedyn. Mae’r archif ar y we hefyd yn cynnwys cyfraith achos a ffurfiau mewn ieithoedd eraill o EUR-Lex. The EU Exit Web Archive legislation_originated_from_EU_p3

Changes to legislation:

Commission Regulation (EU) 2017/1485, PART I is up to date with all changes known to be in force on or before 25 August 2024. There are changes that may be brought into force at a future date. Changes that have been made appear in the content and are referenced with annotations. Help about Changes to Legislation

Close

Changes to Legislation

Revised legislation carried on this site may not be fully up to date. Changes and effects are recorded by our editorial team in lists which can be found in the ‘Changes to Legislation’ area. Where those effects have yet to be applied to the text of the legislation by the editorial team they are also listed alongside the legislation in the affected provisions. Use the ‘more’ link to open the changes and effects relevant to the provision you are viewing.

View outstanding changes

Newidiadau ac effeithiau heb eu gweithredu eto ar yr eitem ddeddfwriaeth gyfan a’r darpariaethau cysylltiedig.

PART IU.K.GENERAL PROVISIONS

Article 1U.K.Subject matter

For the purpose of safeguarding operational security, frequency quality and the efficient use of the interconnected system and resources, this Regulation lays down detailed guidelines on:

(a)

requirements and principles concerning operational security;

(b)

rules and responsibilities for the coordination and data exchange between TSOs, between TSOs and DSOs, and between TSOs or DSOs and SGUs, in operational planning and in close to real-time operation;

(c)

rules for training and certification of system operator employees;

(d)

requirements on outage coordination;

(e)

requirements for scheduling between the TSOs' control areas; and

(f)

rules aiming at the establishment of a F1... framework for load-frequency control and reserves.

Article 2U.K.Scope

1.The rules and requirements set out in this Regulation shall apply to the following SGUs [F2within the jurisdiction of Great Britain]:

(a)existing and new power generating modules that are, or would be, classified as type B, C and D in accordance with the criteria set out in Article 5 of Commission Regulation (EU) 2016/631(1);

(b)existing and new transmission-connected demand facilities;

(c)existing and new transmission-connected closed distribution systems;

(d)existing and new demand facilities, closed distribution systems and third parties if they provide demand response directly to the TSO F3...;

(e)providers of redispatching of power generating modules or demand facilities by means of aggregation and providers of active power reserve in accordance with Title 8 of Part IV of this Regulation; and

(f)existing and new high voltage direct current (‘HVDC’) systems in accordance with the criteria in Article 3(1) of Commission Regulation (EU) 2016/1447(2).

2.[F4Except for Article 13,] this Regulation shall apply to all transmission systems, distribution systems and interconnections [F5within the jurisdiction of Great Britain], except transmission systems and distribution systems or parts of the transmission systems and distribution systems located in islands [F6which are not part of the GB synchronous area].

3.[F7Except for Article 13, this Regulation applies to all TSOs that are certified by the regulatory authority, to the extent they are operating within the jurisdiction of Great Britain.] Where a TSO does not have a function relevant to one or more obligations under this Regulation, [F8the regulatory authority may] provide that the responsibility of a TSO to comply with one or some or all obligations under this Regulation is assigned to one or more specific TSOs.

F94.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.Where the requirements under this Regulation are to be established by a relevant system operator that is not a TSO, [F10the regulatory authority] may provide that instead the TSO be responsible for establishing the relevant requirements.

Textual Amendments

Article 3U.K.Definitions

1.[F11Except where stated in this Article,] for the purposes of this Regulation, the definitions in Article 2 of [F12Regulation (EU) 2019/943 of the European Parliament and of the Council of 5 June 2019 on the internal market for electricity (recast)], Article 2 of Commission Regulation (EU) 2015/1222(3), Article 2 of Commission Regulation (EU) 2016/631, Article 2 of Commission Regulation (EU) 2016/1388, Article 2 of Commission Regulation (EU) 2016/1447 [F13and] F14... Article 2 of Commission Regulation (EU) No 543/2013(4) on submission and publication of data in electricity markets F15... shall apply [F16, subject to paragraphs 1A and 1B].

[F171A.The following definitions do not apply for the purposes of this Regulation—

(a)the definition of “individual grid model” in Article 2 of Commission Regulation (EU) 2015/1222;

(b)the definitions of “equipment certificate” and “synchronous area” in Article 2 of Commission Regulation (EU) 2016/631;

(c)the definition of “closed distribution system” in Article 2 of Commission Regulation (EU) 2016/1388;

X1(d)the definition of “regulatory authority” in Article 2 of Regulation (EU) 2019/943;

(e)the definitions of “ancillary service” and “renewable energy” in Article 2 of Regulation (EU) 2019/943;

and instead the definitions of those terms in points (160), (162), (164), (166), (170) and (171) of paragraph 3 apply.

1B.The definition of “transmission system operator” or “TSO” in Article 2 of Regulation (EU) 2019/943 applies for the purposes of this Regulation except where specified otherwise.

1C.In this Regulation—

(a)any reference to Commission Regulation (EU) 2015/1222 is a reference to that Regulation as it applied in EU law immediately before IP completion day.]

2.In addition, the following definitions shall apply:

(1)

‘operational security’ means the transmission system's capability to retain a normal state or to return to a normal state as soon as possible, and which is characterised by operational security limits;

(2)

‘constraint’ means a situation in which there is a need to prepare and activate a remedial action in order to respect operational security limits;

(3)

‘N-situation’ means the situation where no transmission system element is unavailable due to occurrence of a contingency;

(4)

‘contingency list’ means the list of contingencies to be simulated in order to test the compliance with the operational security limits;

(5)

‘normal state’ means a situation in which the system is within operational security limits in the N-situation and after the occurrence of any contingency from the contingency list, taking into account the effect of the available remedial actions;

(6)

‘frequency containment reserves’ or ‘FCR’ means the active power reserves available to contain system frequency after the occurrence of an imbalance;

(7)

‘frequency restoration reserves’ or ‘FRR’ means the active power reserves available to restore system frequency to the nominal frequency and, for a synchronous area consisting of more than one LFC area, to restore power balance to the scheduled value;

(8)

‘replacement reserves’ or ‘RR’ means the active power reserves available to restore or support the required level of FRR to be prepared for additional system imbalances, including generation reserves;

(9)

‘reserve provider’ means a legal entity with a legal or contractual obligation to supply FCR, FRR or RR from at least one reserve providing unit or reserve providing group;

(10)

‘reserve providing unit’ means a single or an aggregation of power generating modules and/or demand units connected to a common connection point fulfilling the requirements to provide FCR, FRR or RR;

(11)

‘reserve providing group’ means an aggregation of power generating modules, demand units and/or reserve providing units connected to more than one connection point fulfilling the requirements to provide FCR, FRR or RR;

(12)

‘load-frequency control area’ or ‘LFC area’ means a part of a synchronous area or an entire synchronous area, physically demarcated by points of measurement at interconnectors to other LFC areas, operated by one or more TSOs fulfilling the obligations of load-frequency control;

(13)

‘time to restore frequency’ means the maximum expected time after the occurrence of an instantaneous power imbalance smaller than or equal to the reference incident in which the system frequency returns to the frequency restoration range for synchronous areas with only one LFC area and in the case of synchronous areas with more than one LFC area, the maximum expected time after the occurrence of an instantaneous power imbalance of an LFC area within which the imbalance is compensated;

(14)

‘(N-1) criterion’ means the rule according to which the elements remaining in operation within a TSO's control area after occurrence of a contingency are capable of accommodating the new operational situation without violating operational security limits;

(15)

‘(N-1) situation’ means the situation in the transmission system in which one contingency from the contingency list occurred;

(16)

‘active power reserve’ means the balancing reserves available for maintaining the frequency;

(17)

‘alert state’ means the system state in which the system is within operational security limits, but a contingency from the contingency list has been detected and in case of its occurrence the available remedial actions are not sufficient to keep the normal state;

(18)

‘load-frequency control block’ or ‘LFC block’ means a part of a synchronous area or an entire synchronous area, physically demarcated by points of measurement at interconnectors to other LFC blocks, consisting of one or more LFC areas, operated by one or more TSOs fulfilling the obligations of load-frequency control;

(19)

‘area control error’ or ‘ACE’ means the sum of the power control error (‘ΔP’), that is the real-time difference between the measured actual real time power interchange value (‘P’) and the control program (‘P0’) of a specific LFC area or LFC block and the frequency control error (‘K*Δf’), that is the product of the K-factor and the frequency deviation of that specific LFC area or LFC block, where the area control error equals ΔP+K*Δf;

(20)

‘control program’ means a sequence of set-point values for the netted power interchange of a LFC area or LFC block over alternating current (‘AC’) interconnectors;

(21)

‘voltage control’ means the manual or automatic control actions at the generation node, at the end nodes of the AC lines or HVDC systems, on transformers, or other means, designed to maintain the set voltage level or the set value of reactive power;

(22)

‘blackout state’ means the system state in which the operation of part or all of the transmission system is terminated;

(23)

F18...

(24)

F18...

(25)

F18...

(26)

F18...

(27)

‘contingency analysis’ means a computer based simulation of contingencies from the contingency list;

(28)

‘critical fault clearing time’ means the maximum fault duration for which the transmission system retains stability of operation;

(29)

‘fault’ means all types of short-circuits (single-, double- and triple-phase, with and without earth contact), a broken conductor, interrupted circuit, or an intermittent connection, resulting in the permanent non-availability of the affected transmission system element;

(30)

‘transmission system element’ means any component of the transmission system;

(31)

‘disturbance’ means an unplanned event that may cause the transmission system to divert from the normal state;

(32)

‘dynamic stability’ is a common term including the rotor angle stability, frequency stability and voltage stability;

(33)

‘dynamic stability assessment’ means the operational security assessment in terms of dynamic stability;

(34)

‘frequency stability’ means the ability of the transmission system to maintain frequency stable in the N-situation and after being subjected to a disturbance;

(35)

‘voltage stability’ means the ability of a transmission system to maintain acceptable voltages at all nodes in the transmission system in the N-situation and after being subjected to a disturbance;

(36)

‘system state’ means the operational state of the transmission system in relation to the operational security limits which can be normal state, alert state, emergency state, blackout state and restoration state;

(37)

‘emergency state’ means the system state in which one or more operational security limits are violated;

(38)

‘restoration state’ means the system state in which the objective of all activities in the transmission system is to re-establish the system operation and maintain operational security after the blackout state or the emergency state;

(39)

‘exceptional contingency’ means the simultaneous occurrence of multiple contingencies with a common cause;

(40)

‘frequency deviation’ means the difference between the actual and the nominal frequency of the synchronous area which can be negative or positive;

(41)

‘system frequency’ means the electric frequency of the system that can be measured in all parts of the synchronous area under the assumption of a coherent value for the system in the timeframe of seconds, with only minor differences between different measurement locations;

(42)

‘frequency restoration process’ or ‘FRP’ means a process that aims at restoring frequency to the nominal frequency and, for synchronous areas consisting of more than one LFC area, a process that aims at restoring the power balance to the scheduled value;

(43)

‘frequency restoration control error’ or ‘FRCE’ means the control error for the FRP which is equal to the ACE of a LFC area or equal to the frequency deviation where the LFC area geographically corresponds to the synchronous area;

(44)

‘schedule’ means a reference set of values representing the generation, consumption or exchange of electricity for a given time period;

(45)

‘K-factor of an LFC area or LFC block’ means a value expressed in megawatts per hertz (‘MW/Hz’), which is as close as practical to, or greater than the sum of the auto-control of generation, self-regulation of load and of the contribution of frequency containment reserve relative to the maximum steady-state frequency deviation;

(46)

‘local state’ means the qualification of an alert, emergency or blackout state when there is no risk of extension of the consequences outside of the control area including interconnectors connected to this control area;

(47)

‘maximum steady-state frequency deviation’ means the maximum expected frequency deviation after the occurrence of an imbalance equal to or less than the reference incident at which the system frequency is designed to be stabilised;

(48)

‘observability area’ means a TSO's own transmission system and the relevant parts of distribution systems and neighbouring TSOs' transmission systems, on which the TSO implements real-time monitoring and modelling to maintain operational security in its control area including interconnectors;

(49)

‘neighbouring TSOs’ means the TSOs directly connected via at least one AC or DC interconnector [F19and includes a TSO operating outside the jurisdiction of Great Britain and for this purpose “TSO” has the meaning given in Article 2 of Directive 2009/72/EC];

(50)

‘operational security analysis’ means the entire scope of the computer based, manual and automatic activities performed in order to assess the operational security of the transmission system and to evaluate the remedial actions needed to maintain operational security;

(51)

‘operational security indicators’ means indicators used by TSOs to monitor the operational security in terms of system states as well as faults and disturbances influencing operational security;

(52)

‘operational security ranking’ means the ranking used by TSOs to monitor the operational security on the basis of the operational security indicators;

(53)

‘operational tests’ means the tests carried out by a TSO or DSO for maintenance, development of system operation practices and training and to acquire information on transmission system behaviour under abnormal system conditions and the tests carried out by significant grid users for similar purposes on their facilities;

(54)

‘ordinary contingency’ means the occurrence of a contingency of a single branch or injection;

(55)

‘out-of-range contingency’ means the simultaneous occurrence of multiple contingencies without a common cause, or a loss of power generating modules with a total loss of generation capacity exceeding the reference incident;

(56)

‘ramping rate’ means the rate of change of active power by a power generating module, demand facility or HVDC system;

(57)

‘reactive power reserve’ means the reactive power which is available for maintaining voltage;

(58)

‘reference incident’ means the maximum positive or negative power deviation occurring instantaneously between generation and demand in a synchronous area, considered in the FCR dimensioning;

(59)

‘rotor angle stability’ means the ability of synchronous machines to remain in synchronism under N-situation and after being subject to a disturbance;

(60)

‘security plan’ means the plan containing a risk assessment of critical TSO's assets to major physical- and cyber-threat scenarios with an assessment of the potential impacts;

(61)

‘stability limits’ means the permitted boundaries for the operation of the transmission system in terms of respecting the limits of voltage stability, rotor angle stability and frequency stability;

(62)

‘wide area state’ means the qualification of an alert state, emergency state or blackout state when there is a risk of propagation to the interconnected transmission systems;

(63)

‘system defence plan’ means the technical and organisational measures to be undertaken to prevent the propagation or deterioration of a disturbance in the transmission system, in order to avoid a wide area state disturbance and blackout state;

(64)

‘topology’ means the data concerning the connectivity of the different transmission system or distribution system elements in a substation and includes the electrical configuration and the position of circuit breakers and isolators;

(65)

‘transitory admissible overloads’ means the temporary overloads of transmission system elements which are allowed for a limited period and which do not cause physical damage to the transmission system elements as long as the defined duration and thresholds are respected;

(66)

‘virtual tie-line’ means an additional input of the controllers of the involved LFC areas that has the same effect as a measuring value of a physical interconnector and allows exchange of electric energy between the respective areas;

(67)

F20...

(68)

‘adequacy’ means the ability of in-feeds into an area to meet the load in that area;

(69)

F21...

(70)

‘availability plan’ means the combination of all planned availability statuses of a relevant asset for a given time period;

(71)

‘availability status’ means the capability of a power generating module, grid element or demand facility to provide a service for a given time period, regardless of whether or not it is in operation;

(72)

‘close to real-time’ means the time lapse of not more than 15 minutes between the last intraday gate closure and real-time;

(73)

‘consumption schedule’ means a schedule representing the consumption of a demand facility or of a group of demand facilities;

(74)

F22...

(75)

‘external commercial trade schedule’ means a schedule representing the commercial exchange of electricity between market participants in different scheduling areas;

(76)

‘external TSO schedule’ means a schedule representing the exchange of electricity between TSOs in different scheduling areas;

(77)

‘forced outage’ means the unplanned removal from service of a relevant asset for any urgent reason that is not under the operational control of the operator of the concerned relevant asset;

(78)

‘generation schedule’ means a schedule representing the electricity generation of a power generating module or of a group of power generating modules;

(79)

‘internal commercial trade schedule’ means a schedule representing the commercial exchange of electricity within a scheduling area between different market participants;

(80)

‘internal relevant asset’ means a relevant asset which is part of a TSO's control area or a relevant asset located in a distribution system, including a closed distribution system, which is connected directly or indirectly to that TSO's control area;

(81)

‘netted area AC position’ means the netted aggregation of all AC external schedules of an area;

(82)

‘outage coordination region’ means a combination of control areas for which TSOs define procedures to monitor and where necessary coordinate the availability status of relevant assets in all time-frames;

(83)

‘relevant demand facility’ means a demand facility which participates in the outage coordination and the availability status of which influences cross-border operational security;

(84)

‘relevant asset’ means any relevant demand facility, relevant power generating module, or relevant grid element partaking in the outage coordination;

(85)

‘relevant grid element’ means any component of a transmission system, including interconnectors, or of a distribution system, including a closed distribution system, such as a single line, a single circuit, a single transformer, a single phase-shifting transformer, or a voltage compensation installation, which participates in the outage coordination and the availability status of which influences cross-border operational security;

(86)

‘outage planning incompatibility’ means the state in which a combination of the availability status of one or more relevant grid elements, relevant power generating modules, and/or relevant demand facilities and the best estimate of the forecasted electricity grid situation leads to violation of operational security limits taking into account remedial actions without costs which are at the TSO's disposal;

(87)

‘outage planning agent’ means an entity with the task of planning the availability status of a relevant power generating module, a relevant demand facility or a relevant grid element;

(88)

‘relevant power generating module’ means a power generating module which participates in the outage coordination and the availability status of which influences cross-border operational security;

(89)

F23...

(90)

‘scheduling agent’ means the entity or entities with the task of providing schedules from market participants to TSOs, or where applicable third parties;

(91)

‘scheduling area’ means an area within which the TSOs' obligations regarding scheduling apply due to operational or organisational needs;

(92)

‘week-ahead’ means the week prior to the calendar week of operation;

(93)

‘year-ahead’ means the year prior to the calendar year of operation;

(94)

‘affected TSO’ means a TSO for which information on the exchange of reserves and/or sharing of reserves F24... is needed for the analysis and maintenance of operational security;

(95)

‘reserve capacity’ means the amount of FCR, FRR or RR that needs to be available to the TSO;

(96)

‘exchange of reserves’ means the possibility of a TSO to access reserve capacity connected to another LFC area, LFC block, or synchronous area to fulfil its reserve requirements resulting from its own reserve dimensioning process of either FCR, FRR or RR and where that reserve capacity is exclusively for that TSO, and is not taken into account by any other TSO to fulfil its reserve requirements resulting from their respective reserve dimensioning processes;

(97)

‘sharing of reserves’ means a mechanism in which more than one TSO takes the same reserve capacity, being FCR, FRR or RR, into account to fulfil their respective reserve requirements resulting from their reserve dimensioning processes;

(98)

‘alert state trigger time’ means the time before alert state becomes active;

(99)

‘automatic FRR’ means FRR that can be activated by an automatic control device;

(100)

‘automatic FRR activation delay’ means the period of time between the setting of a new setpoint value by the frequency restoration controller and the start of physical automatic FRR delivery;

(101)

‘automatic FRR full activation time’ means the time period between the setting of a new setpoint value by the frequency restoration controller and the corresponding activation or deactivation of automatic FRR;

(102)

‘average FRCE data’ means the set of data consisting of the average value of the recorded instantaneous FRCE of a LFC area or a LFC block within a given measured period time;

(103)

‘control capability providing TSO’ means the TSO that shall trigger the activation of its reserve capacity for a control capability receiving TSO under the conditions of an agreement for sharing reserves;

(104)

‘control capability receiving TSO’ means the TSO calculating reserve capacity by taking into account reserve capacity which is accessible through a control capability providing TSO under the conditions of an agreement for sharing reserves;

(105)

‘criteria application process’ means the process of calculating the target parameters for the synchronous area, the LFC block and the LFC area based on the data obtained in the data collection and delivery process;

(106)

‘data collection and delivery process’ means the process of collection of the set of data necessary in order to perform the frequency quality evaluation criteria;

(107)

F25...

(108)

F26...

(109)

‘dimensioning incident’ means the highest expected instantaneously occurring active power imbalance within a LFC block in both positive and negative direction;

(110)

‘electrical time deviation’ means the time discrepancy between synchronous time and coordinated universal time (‘UTC’);

(111)

‘FCR full activation frequency deviation’ means the rated value of frequency deviation at which the FCR in a synchronous area is fully activated;

(112)

‘FCR full activation time’ means the time period between the occurrence of the reference incident and the corresponding full activation of the FCR;

(113)

‘FCR obligation’ means the part of all of the FCR that falls under the responsibility of a TSO;

(114)

‘frequency containment process’ or ‘FCP’ means a process that aims at stabilising the system frequency by compensating imbalances by means of appropriate reserves;

(115)

F27...

(116)

‘frequency quality defining parameter’ means the main system frequency variables that define the principles of frequency quality;

(117)

‘frequency quality target parameter’ means the main system frequency target on which the behaviour of FCR, FRR and RR activation processes is evaluated in normal state;

(118)

‘frequency quality evaluation criteria’ means a set of calculations using system frequency measurements that allows the evaluation of the quality of the system frequency against the frequency quality target parameters;

(119)

‘frequency quality evaluation data’ means the set of data that allows the calculation of the frequency quality evaluation criteria;

(120)

‘frequency recovery range’ means the system frequency range to which the system frequency is expected to return in the GB [F28synchronous area], after the occurrence of an imbalance equal to or smaller than the reference incident, within the time to recover frequency;

(121)

‘time to recover frequency’ means [F29GB synchronous area], the maximum expected time after the occurrence of an imbalance smaller than or equal to the reference incident in which the system frequency returns to the maximum steady state frequency deviation;

(122)

‘frequency restoration range’ means the system frequency range to which the system frequency is expected to return in the GB, [F30synchronous area] after the occurrence of an imbalance equal to or smaller than the reference incident within the time to restore frequency;

(123)

‘FRCE target parameters’ means the main target LFC block variables on the basis of which the dimensioning criteria for FRR and RR of the LFC block are determined and evaluated and which are used to reflect the LFC block behaviour in normal operation;

(124)

F31...

(125)

‘frequency setpoint’ means the frequency target value used in the FRP, defined as the sum of the nominal system frequency and an offset value needed to reduce an electrical time deviation;

(126)

‘FRR availability requirements’ means a set of requirements defined by the TSOs of a LFC block regarding the availability of FRR;

(127)

‘FRR dimensioning rules’ means the specifications of the FRR dimensioning process of a LFC block;

(128)

F32...

(129)

F33...

(130)

‘initial FCR obligation’ means the amount of FCR allocated to a TSO on the basis of a sharing key;

(131)

‘instantaneous frequency data’ means a set of data measurements of the overall system frequency for the synchronous area with a measurement period equal to or shorter than one second used for system frequency quality evaluation purposes;

(132)

‘instantaneous frequency deviation’ means a set of data measurements of the overall system frequency deviations for the synchronous area with a measurement period equal to or shorter than one second used for system frequency quality evaluation purposes;

(133)

‘instantaneous FRCE data’ means a set of data of the FRCE of a LFC block with a measurement period equal to or shorter than 10 seconds used for system frequency quality evaluation purposes;

(134)

‘level 1 FRCE range’ means the first range used for system frequency quality evaluation purposes on LFC block level within which the FRCE should be kept for a specified percentage of the time;

(135)

‘level 2 FRCE range’ means the second range used for system frequency quality evaluation purposes on LFC block level within which the FRCE should be kept for a specified percentage of the time;

(136)

‘LFC block operational agreement’ means a multi-party agreement between all TSOs of a LFC block if the LFC block is operated by more than one TSO and means a LFC block operational methodology to be adopted unilaterally by the relevant TSO if the LFC block is operated by only one TSO;

(137)

F34...

(138)

F35...

(139)

‘LFC block monitor’ means a TSO responsible for collecting the frequency quality evaluation criteria data and applying the frequency quality evaluation criteria for the LFC block;

(140)

‘load-frequency control structure’ means the basic structure considering all relevant aspects of load-frequency control in particular concerning respective responsibilities and obligations as well as types and purposes of active power reserves;

(141)

‘process responsibility structure’ means the structure to determine responsibilities and obligations with respect to active power reserves based on the control structure of the synchronous area;

(142)

‘process activation structure’ means the structure to categorise the processes concerning the different types of active power reserves in terms of purpose and activation;

(143)

‘manual FRR full activation time’ means the time period between the setpoint change and the corresponding activation or deactivation of manual FRR;

(144)

‘maximum instantaneous frequency deviation’ means the maximum expected absolute value of an instantaneous frequency deviation after the occurrence of an imbalance equal to or smaller than the reference incident, beyond which emergency measures are activated;

(145)

‘monitoring area’ means a part of the synchronous area or the entire synchronous area, physically demarcated by points of measurement at interconnectors to other monitoring areas, operated by one or more TSOs fulfilling the obligations of a monitoring area;

(146)

‘prequalification’ means the process to verify the compliance of a reserve providing unit or a reserve providing group with the requirements set by the TSO;

(147)

‘ramping period’ means a period of time defined by a fixed starting point and a length of time during which the input and/or output of active power will be increased or decreased;

(148)

‘reserve instructing TSO’ means the TSO responsible for the instruction of the reserve providing unit or the reserve providing group to activate FRR and/or RR;

(149)

‘reserve connecting DSO’ means the DSO responsible for the distribution network to which a reserve providing unit or reserve providing group, providing reserves to a TSO, is connected;

(150)

‘reserve connecting TSO’ means the TSO responsible for the monitoring area to which a reserve providing unit or reserve providing group is connected;

(151)

‘reserve receiving TSO’ means the TSO involved in an exchange with a reserve connecting TSO and/or a reserve providing unit or a reserve providing group connected to another monitoring or LFC area;

(152)

‘reserve replacement process’ or ‘RRP’ means a process to restore the activated FRR and F36... the activated FCR;

(153)

‘RR availability requirements’ means a set of requirements defined by the TSOs of a LFC block regarding the availability of RR;

(154)

‘RR dimensioning rules’ means the specifications of the RR dimensioning process of a LFC block;

(155)

‘standard frequency range’ means a defined symmetrical interval around the nominal frequency within which the system frequency of a synchronous area is supposed to be operated;

(156)

‘standard frequency deviation’ means the absolute value of the frequency deviation that limits the standard frequency range;

(157)

‘steady state frequency deviation’ means the absolute value of frequency deviation after occurrence of an imbalance, once the system frequency has been stabilised;

(158)

‘synchronous area monitor’ means a TSO responsible for collecting the frequency quality evaluation criteria data and applying the frequency quality evaluation criteria for the synchronous area;

(159)

‘time control process’ means a process for time control, where time control is a control action carried out to return the electrical time deviation between synchronous time and UTC time to zero.

(160)

[F37‘ancillary service’ means a service necessary for the operation of a transmission or distribution system;

(161)

‘authorised certifier’ means an entity that issues equipment certificates and power-generating module documents and whose accreditation is given by the United Kingdom Accreditation Service or such other relevant entity established for such purpose from time to time;

(162)

‘closed distribution system’ means a distribution system classified as a closed distribution system by the regulatory authority, which distributes electricity within a geographically confined industrial, commercial or shared services site and does not supply household customers, without prejudice to incidental use by a small number of households located within the area served by the system and with employment or similar associations with the owner of the system;

(163)

‘closed distribution system operator’ or ‘CDSO’ means a distribution system operator which is responsible for operating a closed distribution system;

(164)

‘equipment certificate’ means a document issued by an authorised certifier for equipment used by a power generating module, demand unit, distribution system, demand facility or HVDC system. Where a range of permitted values for equipment is specified in this Regulation or another enactment, the equipment certificate must state a specific value within that range for the equipment;

(165)

‘GB synchronous area’ means the area within the jurisdiction of Great Britain covered by synchronously interconnected TSOs;

(166)

‘individual grid model’ means a data set describing power system characteristics (generation, load and grid topology) and related rules to change these characteristics during capacity calculation, prepared by the responsible TSOs;

(167)

‘the jurisdiction of Great Britain’ has the meaning given in section 4(3F)(a) of the Electricity Act 1989;

(168)

‘national electricity transmission system operator’ means the person operating the national transmission system for Great Britain (and for this purpose “transmission system” has the same meaning as in section 4(4) of the Electricity Act 1989);

(169)

‘regulatory authority’ means the Gas and Electricity Markets Authority;

(170)

‘renewable energy sources’ means renewable non-fossil energy sources (wind, solar, geothermal, wave, tidal, hydropower, biomass, landfill gas, sewage treatment plant gas and biogases);

(171)

‘synchronous area’ means an area covered by synchronously interconnected TSOs, such as the GB synchronous area and for this purpose “TSO” has the meaning given in Article 2 of Directive 2009/72/EC;

(172)

‘Type A’, ‘Type B’, ‘Type C’ or ‘Type D’, in relation to a power generating module, has the meaning given in Article 5 of Commission Regulation (EU) 2016/631.]

Editorial Information

X1Editorial note: Art. 3(1A)(d) (as inserted by S.I. 2019/533, Sch. 1 para. 4(3)) is subject to two conflicting amendments: it is stated to be omitted (16.9.2020) by virtue of S.I. 2020/1006, regs. 1(2), 3(2)(a)(i) and also substituted (in the form shown here) (15.9.2020) by S.I. 2020/1016, regs. 1(2), 6(3)(c)(i)

Textual Amendments

Article 4U.K.Objectives and regulatory aspects

1.This Regulation aims at:

(a)determining common operational security requirements and principles;

(b)determining common F38... system operational planning principles;

(c)determining common load-frequency control processes and control structures;

(d)ensuring the conditions for maintaining operational security F39...;

(e)ensuring the conditions for maintaining a frequency quality level [F40in the GB synchronous area];

(f)promoting the coordination of system operation and operational planning;

(g)ensuring and enhancing the transparency and reliability of information on transmission system operation;

(h)contributing to the efficient operation and development of the electricity transmission system and electricity sector F41....

2.When applying this Regulation, [F42the Secretary of State, the regulatory authority], and system operators shall:

(a)apply the principles of proportionality and non-discrimination;

(b)ensure transparency;

(c)apply the principle of optimisation between the highest overall efficiency and lowest total costs for all parties involved;

(d)ensure TSOs make use of market-based mechanisms as far as possible, to ensure network security and stability;

(e)respect the responsibility assigned to the relevant TSO in order to ensure system security F43...;

(f)consult with relevant DSOs and take account of potential impacts on their system; and

(g)take into consideration agreed F44... standards and technical specifications.

Textual Amendments

Article 5U.K.Terms and conditions or methodologies of TSOs

1.TSOs shall develop the terms and conditions or methodologies required by this Regulation and submit them for approval to [F45the regulatory authority in accordance with Article 6(3) and (4) within the respective deadlines set out in this Regulation].

2.Where a proposal for terms and conditions or methodologies pursuant to this Regulation needs to be developed and agreed by more than one TSO, the participating TSOs shall closely cooperate. [F46TSOs shall regularly inform the regulatory authority] about the progress of developing those terms and conditions or methodologies.

F473.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F474.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F475.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F476.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F477.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F478.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9.Where TSOs fail to submit a proposal for terms and conditions or methodologies [F48to the regulatory authority in accordance with Article 6(3) and (4) within the deadlines specified in this Regulation, they shall provide the regulatory authority] with the relevant drafts of the terms and conditions or methodologies, and explain why an agreement has not been reached. F49... The [F50regulatory authority] shall take the appropriate steps to make possible the adoption of the required terms and conditions or methodologies within 4 months from the receipt of [F51the relevant drafts].

Textual Amendments

Article 6U.K.Approval of terms and conditions or methodologies of TSOs

1.[F52The] regulatory authority shall approve the terms and conditions or methodologies developed by TSOs under paragraphs [F532, 3 and 4]. F54...

2.The proposals for the following terms and conditions or methodologies shall be subject to approval by [F55the regulatory authority, on which the Secretary of State] may provide an opinion to the [F56regulatory authority]:

(a)key organizational requirements, roles and responsibilities in relation to data exchange related to operational security in accordance with Article 40(6);

F57(b). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F58(c). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.The proposals for the following terms and conditions or methodologies shall be subject to approval by [F59the regulatory authority], on which [F60the Secretary of State] may provide an opinion to the F61... regulatory authority:

(a)methodology F62... for the definition of minimum inertia in accordance with Article 39(3)(b);

F63(b). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F64(c). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

(d)methodologies, conditions and values included in the synchronous area operational agreements in Article 118 concerning:

(i)

the frequency quality defining parameters and the frequency quality target parameter in accordance with Article 127;

(ii)

the dimensioning rules for FCR in accordance with Article 153;

(iii)

the additional properties of the FCR in accordance with Article 154(2);

(iv)

for the GB [F65synchronous area], the measures to ensure the recovery of energy reservoirs in accordance with Article 156(6)(b);

(v)

F66...

(vi)

F67...

(vii)

F68... if applicable, the limits for the exchange of FCR between TSOs in accordance with Article 163(2);

(viii)

F69...

(ix)

F69...

(x)

F69...

(e)methodologies and conditions included in the LFC block operational agreements in Article 119, concerning:

(i)

ramping restrictions for active power output in accordance with Article 137(3) and (4);

(ii)

coordination actions aiming to reduce FRCE as defined in Article 152(14);

(iii)

measures to reduce FRCE by requiring changes in the active power production or consumption of power generating modules and demand units in accordance with Article 152(16);

(iv)

the FRR dimensioning rules in accordance with Article 157(1);

(f)mitigation measures per synchronous area or LFC block in accordance with Article 138;

(g)common proposal per synchronous area for the determination of LFC blocks in accordance with Article 141(2).

4.[F70The following terms and conditions or methodologies shall be subject to individual approval by the regulatory authority—]

(a)for the GB [F71synchronous area], the proposal of each TSO specifying the level of demand loss at which the transmission system shall be in the blackout state;

(b)scope of data exchange with DSOs and significant grid users in accordance with Article 40(5);

(c)additional requirements for FCR providing groups in accordance with Article 154(3);

(d)exclusion of FCR providing groups from the provision of FCR in accordance with Article 154(4);

F72(e). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

(f)FRR technical requirements defined by the TSO in accordance with Article 158(3);

(g)rejection of FRR providing groups from the provision of FRR in accordance with Article 159(7);

(h)technical requirements for the connection of RR providing units and RR providing groups defined by the TSO in accordance with Article 161(3); and

(i)rejection of RR providing groups from the provision of RR in accordance with Article 162(6).

5.Where an individual relevant system operator or TSO is required or permitted under this Regulation to specify or agree on requirements that are not subject to paragraph 4, [F73the regulatory authority may require the relevant system operator or TSO to obtain its prior approval] of these requirements.

6.The proposal for terms and conditions or methodologies shall include a proposed timescale for their implementation and a description of their expected impact on the objectives of this Regulation. F74...

F757.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F768.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9.Where the approval of the terms and conditions or methodologies requires a decision by [F77the regulatory authority] in accordance with paragraph 4, the [F78regulatory authority] shall reach a decision within 6 months following the receipt of the terms and conditions or methodologies.

10.Any party can complain against a relevant system operator or TSO in relation to that relevant system operator's or TSO's obligations or decisions under this Regulation and may refer the complaint to the regulatory authority which, acting as dispute settlement authority, shall issue a decision within 2 months after receipt of the complaint. That period may be extended by a further 2 months where additional information is sought by the regulatory authority. That extended period may be further extended with the agreement of the complainant. The regulatory authority's decision shall be binding unless and until overruled on appeal.

Textual Amendments

Article 7U.K.Amendments to the terms and conditions or methodologies of TSOs

1.Where [F79the regulatory authority requires] an amendment in order to approve the terms and conditions or methodologies submitted in accordance with paragraphs [F803 and 4] of Article 6, the relevant TSOs shall submit a proposal for amended terms and conditions or methodologies for approval within 2 months following the requirement from the regulatory [F81authority]. The [F82regulatory authority] shall decide on the amended terms and conditions or methodologies within 2 months following their submission.

2.Where [F83the regulatory authority] requires an amendment in order to approve the terms and conditions or methodologies submitted in accordance with Article 6(4), the relevant TSO shall submit a proposal for amended terms and conditions or methodologies for approval within 2 months following the requirement from [F84the regulatory authority]. The [F85regulatory authority] shall decide on the amended terms and conditions or methodologies within 2 months following their submission.

F863.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.TSOs responsible for developing a proposal for terms and conditions or methodologies or [F87the regulatory authority] in accordance with paragraphs 2, 3 and 4 of Article 6 may request amendments of those terms and conditions or methodologies. Proposals for amendment to the terms and conditions or methodologies shall be submitted to consultation if applicable in accordance with the procedure set out in Article 11 and approved in accordance with the procedure set out in Articles 5 and 6.

Textual Amendments

Article 8U.K.Publication on internet

1.TSOs responsible for specifying the terms and conditions or methodologies in accordance with this Regulation shall publish them on the internet following approval by the [F88regulatory authority] or, where no such approval is required, following their specification, except where such information is considered confidential in accordance with Article 12.

2.The publication shall also concern:

(a)enhancements of network operation tools in accordance with Article 55(1)(e);

(b)FRCE target parameters in accordance with Article 128;

(c)ramping restrictions on synchronous area level in accordance with Article 137(1);

(d)ramping restrictions on LFC block level in accordance with Article 137(3);

(e)measures taken in the alert state due to there being insufficient active power reserves in accordance with Article 152(11); and

(f)request of the reserve connecting TSO to an FCR provider to make the information available in real time in accordance with Article 154(11).

Article 9U.K.Recovery of costs

1.The costs borne by system operators subject to network tariff regulation and stemming from the obligations laid down in this Regulation shall be assessed by the [F89regulatory authority]. Costs assessed as reasonable, efficient and proportionate shall be recovered through network tariffs or other appropriate mechanisms.

2.If requested by the [F90regulatory authority], system operators referred to in paragraph 1 shall, within 3 months of the request, provide the information necessary to facilitate assessment of the costs incurred.

Article 10U.K.Stakeholder involvement

The [F91national electricity transmission system operator] shall organise stakeholder involvement regarding secure system operation and other aspects of the implementation of this Regulation. Such involvement shall include regular meetings with stakeholders to identify problems and propose improvements related to the secure system operation.

Article 11U.K.Public consultation

1.TSOs responsible for submitting proposals for terms and conditions or methodologies or their amendments in accordance with this Regulation shall consult stakeholders, including the [F92regulatory authority], on the draft proposals for terms and conditions or methodologies listed in [F93Article 6(2)(a) and (3)]. The consultation shall last for a period of not less than 1 month.

F942.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

[F952A.Any consultation undertaken before IP completion day in respect of draft proposals for terms and conditions or methodologies listed in Article 6(2)(a) is as effective for the purposes of this Regulation as consultation undertaken after IP completion day.]

3.The TSOs responsible for developing the proposal for terms and conditions or methodologies shall duly take into account the views of stakeholders resulting from the consultations prior to its submission for regulatory approval. In all cases, a sound justification for including or not including the views resulting from the consultation shall be provided together with the submission of the proposal and published in a timely manner before, or simultaneously with the publication of the proposal for terms and conditions or methodologies.

Article 12U.K.Confidentiality obligations

1.Any confidential information received, exchanged or transmitted pursuant to this Regulation shall be subject to the conditions of professional secrecy laid down in paragraphs 2, 3 and 4.

2.The obligation of professional secrecy shall apply to any persons subject to the provisions of this Regulation.

3.Confidential information received by the persons or regulatory authorities referred to in paragraph 2 in the course of their duties may not be divulged to any other person or authority, without prejudice to cases covered by [F96the other provisions of this Regulation or any other enactment].

4.Without prejudice to [F97any enactment], regulatory authorities, bodies or persons who receive confidential information pursuant to this Regulation may use it only for the purpose of carrying out their duties under this Regulation.

F98Article 13U.K.Agreements with TSOs not bound by this Regulation

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Article 14U.K.Monitoring

1.[F99The regulatory authority] shall monitor the implementation of this Regulation F100.... Monitoring shall cover at least the following matters:

(a)operational security indicators in accordance with Article 15;

F101(b). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F101(c). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F101(d). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F101(e). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

F101(f). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

(g)identification of any difficulties concerning cooperation on secure system operation with [F102neighbouring] TSOs.

F1032.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.Relevant TSOs shall submit to [F104the regulatory authority] the information required to perform the tasks referred to in [F105paragraph 1].

F1064.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Textual Amendments

Article 15U.K.Annual report on operational security indicators

1.By 30 September, [F107the national electricity transmission system operator] shall publish an annual report based on the incidents classification scale adopted in accordance with [F108Article 30(1)(i) of Regulation (EU) 2019/943 as that provision applied in EU law immediately before IP completion day]. The [F109regulatory authority] may provide its opinion on the format and contents of that annual report, including the geographical scope of the incidents reported F110... and any relevant historical information.

F1112.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.The annual reports referred to in paragraph 1 shall contain at least the following operational security indicators relevant to operational security:

(a)number of tripped transmission system elements per year per TSO;

(b)number of tripped power generation facilities per year per TSO;

(c)energy not supplied per year due to unscheduled disconnection of demand facilities per TSO;

(d)time duration and number of instances of being in the alert and emergency states per TSO;

(e)time duration and number of events within which there was a lack of reserves identified per TSO;

(f)time duration and number of voltage deviations exceeding the ranges from Tables 1 and 2 of Annex II per TSO;

(g)number of minutes outside the standard frequency range and number of minutes outside the 50 % of maximum steady state frequency deviation per synchronous area;

(h)number of system-split separations or local blackout states; and

(i)number of blackouts involving two or more TSOs.

4.The annual report referred to in paragraph 1 shall contain the following operational security indicators relevant to operational planning:

(a)number of events in which an incident contained in the contingency list led to a degradation of the system operation state;

(b)number of the events referred to in point (a) in which a degradation of system operation conditions occurred as a result of unexpected discrepancies from load or generation forecasts;

(c)number of events in which there was a degradation in system operation conditions due to an exceptional contingency;

(d)number of the events referred to in point (c) in which a degradation of system operation conditions occurred as a result of unexpected discrepancies from load or generation forecasts; and

(e)number of events leading to a degradation in system operation conditions due to lack of active power reserves.

5.The annual reports shall contain explanations of the reasons for incidents at the operational security ranking scales 2 and 3 as per the incidents classification scale [F112referred to in paragraph 1]. Those explanations shall be based on an investigation of the incidents by TSOs which process shall be set out in the incidents classification scale. TSOs shall inform the [F113regulatory authority] about an investigation in due time before it is launched. [F114The regulatory authority] may be involved in the investigation upon [F115its] request.

Textual Amendments

Article 16U.K.Annual report on load-frequency control

1.By 30 September, [F116the national electricity transmission system operator] shall publish an annual report on load-frequency control based on the information provided by the TSOs in accordance with paragraph 2. The annual report on load-frequency control shall include the information listed in paragraph 2 F117....

2.[F118TSOs shall notify to the national electricity transmission system operator], by 1 March every year, the following information for the previous year:

(a)the identification of the LFC blocks, LFC areas and monitoring areas F119...;

(b)the identification of LFC blocks that F120... contain LFC areas and monitoring areas F121...;

F122(c). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

(d)the data related to the frequency quality evaluation criteria for each synchronous area and each LFC block in subparagraphs [F123(a) and (b)] covering each month of at least 2 previous calendar years;

(e)the FCR obligation and the initial FCR obligation of each TSO F124... covering each month of at least 2 previous calendar years; and

(f)a description and date of implementation of any mitigation measures and ramping requirements to alleviate deterministic frequency deviations taken in the previous calendar year in accordance with Articles 137 and 138, in which TSOs F125... were involved.

3.The data provided by the TSOs shall cover the preceding year. The information concerning F126... LFC blocks, LFC areas and monitoring areas in subparagraphs [F127(a) and (b)] shall be reported once. Where these areas change, this information shall be reported by 1 March of the following year.

4.Where appropriate, all TSOs of a synchronous area or LFC block shall cooperate in collecting the data listed in paragraph 2.

Textual Amendments

F128Article 17U.K.Annual report on regional coordination assessment

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

(1)

Commission Regulation (EU) 2016/631 of 14 April 2016 establishing a network code on requirements for grid connection of generators (OJ L 112, 27.4.2016, p. 1).

(2)

Commission Regulation (EU) 2016/1447 of 26 August 2016 establishing a network code on requirements for grid connection of high voltage direct current systems and direct current-connected power park modules (OJ L 241, 8.9.2016, p. 1).

(3)

Commission Regulation (EU) 2015/1222 of 24 July 2015 establishing a guideline on capacity allocation and congestion management (OJ L 197, 25.7.2015, p. 24).

(4)

Commission Regulation (EU) No 543/2013 of 14 June 2013 on submission and publication of data in electricity markets and amending Annex I to Regulation (EC) No 714/2009 of the European Parliament and of the Council (OJ L 163, 15.6.2013, p. 1).

Yn ôl i’r brig

Options/Help

Print Options

You have chosen to open the Whole Regulation

The Whole Regulation you have selected contains over 200 provisions and might take some time to download. You may also experience some issues with your browser, such as an alert box that a script is taking a long time to run.

Would you like to continue?

Close

Mae deddfwriaeth ar gael mewn fersiynau gwahanol:

Y Diweddaraf sydd Ar Gael (diwygiedig):Y fersiwn ddiweddaraf sydd ar gael o’r ddeddfwriaeth yn cynnwys newidiadau a wnaed gan ddeddfwriaeth ddilynol ac wedi eu gweithredu gan ein tîm golygyddol. Gellir gweld y newidiadau nad ydym wedi eu gweithredu i’r testun eto yn yr ardal ‘Newidiadau i Ddeddfwriaeth’.

Gwreiddiol (Fel y’i mabwysiadwyd gan yr UE): Mae'r wreiddiol version of the legislation as it stood when it was first adopted in the EU. No changes have been applied to the text.

Close

Gweler y wybodaeth ychwanegol ochr yn ochr â’r cynnwys

Rhychwant ddaearyddol: Indicates the geographical area that this provision applies to. For further information see ‘Frequently Asked Questions’.

Dangos Llinell Amser Newidiadau: See how this legislation has or could change over time. Turning this feature on will show extra navigation options to go to these specific points in time. Return to the latest available version by using the controls above in the What Version box.

Close

Dewisiadau Agor

Dewisiadau gwahanol i agor deddfwriaeth er mwyn gweld rhagor o gynnwys ar y sgrin ar yr un pryd

Close

Rhagor o Adnoddau

Gallwch wneud defnydd o ddogfennau atodol hanfodol a gwybodaeth ar gyfer yr eitem ddeddfwriaeth o’r tab hwn. Yn ddibynnol ar yr eitem ddeddfwriaeth sydd i’w gweld, gallai hyn gynnwys:

  • y PDF print gwreiddiol y fel adopted version that was used for the EU Official Journal
  • rhestr o newidiadau a wnaed gan a/neu yn effeithio ar yr eitem hon o ddeddfwriaeth
  • pob fformat o’r holl ddogfennau cysylltiedig
  • slipiau cywiro
  • dolenni i ddeddfwriaeth gysylltiedig ac adnoddau gwybodaeth eraill
Close

Llinell Amser Newidiadau

Mae’r llinell amser yma yn dangos y fersiynau gwahanol a gymerwyd o EUR-Lex yn ogystal ag unrhyw fersiynau dilynol a grëwyd ar ôl y diwrnod ymadael o ganlyniad i newidiadau a wnaed gan ddeddfwriaeth y Deyrnas Unedig.

Cymerir dyddiadau fersiynau’r UE o ddyddiadau’r dogfennau ar EUR-Lex ac efallai na fyddant yn cyfateb â’r adeg pan ddaeth y newidiadau i rym ar gyfer y ddogfen.

Ar gyfer unrhyw fersiynau a grëwyd ar ôl y diwrnod ymadael o ganlyniad i newidiadau a wnaed gan ddeddfwriaeth y Deyrnas Unedig, bydd y dyddiad yn cyd-fynd â’r dyddiad cynharaf y daeth y newid (e.e. ychwanegiad, diddymiad neu gyfnewidiad) a weithredwyd i rym. Am ragor o wybodaeth gweler ein canllaw i ddeddfwriaeth ddiwygiedig ar Ddeall Deddfwriaeth.

Close

Rhagor o Adnoddau

Defnyddiwch y ddewislen hon i agor dogfennau hanfodol sy’n cyd-fynd â’r ddeddfwriaeth a gwybodaeth am yr eitem hon o ddeddfwriaeth. Gan ddibynnu ar yr eitem o ddeddfwriaeth sy’n cael ei gweld gall hyn gynnwys:

  • y PDF print gwreiddiol y fel adopted fersiwn a ddefnyddiwyd am y copi print
  • slipiau cywiro

liciwch ‘Gweld Mwy’ neu ddewis ‘Rhagor o Adnoddau’ am wybodaeth ychwanegol gan gynnwys

  • rhestr o newidiadau a wnaed gan a/neu yn effeithio ar yr eitem hon o ddeddfwriaeth
  • manylion rhoi grym a newid cyffredinol
  • pob fformat o’r holl ddogfennau cysylltiedig
  • dolenni i ddeddfwriaeth gysylltiedig ac adnoddau gwybodaeth eraill