The Public Water Supplies (Scotland) Regulations 2014

[F1PART BSStandard parameters and frequencies

1.(1) Each monitoring programme must take into account—S

(a)each parameter; and

(b)any other micro-organism, parasite or substance which needs to be monitored by virtue of regulation 5(2) or (3),

including those that are important for assessing the impact of any part of the public water supply system on the quality of water at a point of compliance.

(2) When choosing appropriate parameters and other micro-organisms, parasites or substances for monitoring (as required by, or in accordance with, this schedule), local conditions for the parts of the public water supply system in question must be taken into consideration.

2.(1) The following parameters (“Group A parameters”) must be monitored at least at the minimum frequencies determined in accordance with the table in paragraph 3:—S

(a)Escherichia coli, [F2enterococci,] coliform bacteria, colony count 22 °C, colour, turbidity, taste, odour, hydrogen ion concentration (pH), and conductivity; and

(b)any other parameter, or other micro-organism, parasite or substance, (except radon, tritium and indicative dose) identified as relevant in the monitoring programme—

(i)by virtue of regulation 5(2) (as read with regulation 6(2)(a)); or

(ii)where relevant, through a risk assessment.

(2) Ammonium and nitrite must be included as Group A parameters, if chloramination is used.

(3) Aluminium and iron must be included as Group A parameters, if used as water treatment chemicals.

(4) Aluminium, iron and manganese must be included as Group A parameters, if the water in question originates from, or is influenced by surface waters.

3.(1) Other parameters, except radon, tritium and indicative dose, (“Group B parameters”) must be monitored at least at the frequencies determined in accordance with the table below.S

(2) In the table, “Group A parameters” is to be construed in accordance with paragraph 2.

Minimum frequency of sampling and analysis for compliance monitoring

Volume of water (in m3) distributed or produced each day within a water supply zone (Notes 1 and 2)

Group A parameters:

number of samples per year

Group B parameters:

number of samples per year

> 0≤ 1021
> 10≤ 1,00041
> 1,000≤ 10,0004 for the first 1,000 m3/day of the total volume, plus 3 for each additional 1,000 m3/day and part thereof1 for the first 1,000 m3/day of the total volume, plus 1 for each additional 4,500 m3/day and part thereof
> 10,000≤ 100,0004 for the first 1,000 m3/day of the total volume, plus 3 for each additional 1,000 m3/day and part thereof3 for the first 10,000 m3/day of the total volume, plus 1 for each additional 10,000 m3/day and part thereof
> 100,0004 for the first 1,000 m3/day of the total volume, plus 3 for each additional 1,000 m3/day and part thereof12 for the first 100,000 m3/day of the total volume, plus 1 for each additional 25,000 m3/day and part thereof
Note 1: The volumes are calculated as averages taken over a year.
Note 2: The number of inhabitants in a water supply zone may be used instead of the volume of water to determine the minimum frequency, assuming water consumption of 200 litres/day per person.]