xmlns:atom="http://www.w3.org/2005/Atom" xmlns:atom="http://www.w3.org/2005/Atom"

Part IIE+W+S Safety (General Provisions)

[F135 Steam receivers and steam containers.E+W+S

(1)Every steam receiver, not so constructed and maintained as to withstand with safety the maximum permissible working pressure of the boiler or the maximum pressure which can be obtained in the pipe connecting the receiver with any other source of supply, shall be fitted with—

(a)a suitable reducing valve or other suitable automatic appliance to prevent the safe working pressure being exceeded; and

(b)a suitable safety valve so adjusted as to permit the steam to escape as soon as the safe working pressure is exceeded, or a suitable appliance for cutting off automatically the supply of steam as soon as the safe working pressure is exceeded; and

(c)a correct steam pressure gauge, which must indicate the pressure of steam in the receiver . . . F2; and

(d)a suitable stop valve; and

(e)except where only one steam receiver is in use, a plate bearing a distinctive number which shall be easily visible.

(2)The safety valve and pressure gauge shall be fitted either on the steam receiver or on the supply pipe between the receiver and the reducing valve or other appliance to prevent the safe working pressure being exceeded.

(3)Where any set of receivers is supplied with steam through a single pipe and the reducing valve or other appliance required by paragraph (a) of subsection (1) of this section is fitted on that pipe, the set shall be treated as one receiver for the purposes of paragraphs (a) to (c) of subsection (1) and for the purposes of subsection (2) of this section, and if the set forms part of a single machine, also for the purposes of paragraph (d) of the said subsection (1).

(4)Every part of every steam receiver shall be of good construction, sound material, adequate strength and free from patent defect.

(5)Every steam receiver and its fittings shall be properly maintained, and shall be throughly examined by a competent person, so far as the construction of the receiver permits, at least once in every period of twenty-six months.

(6)A report of the result of every such examination containing the prescribed particulars (including particulars of the safe working pressure) shall be entered in or attached to the general register.

(7)Every steam container shall be so maintained as to secure that the outlet is at all times kept open and free from obstruction.

(8)In this section—

Textual Amendments

F1Ss. 32, 35, 36, 125, 127(2)(c) repealed (1.7.1994) by S.I. 1989/2169, reg. 26, Sch. 6 Pt. I

F2Words repealed by S.I. 1974/1941, reg. 7, Sch. 1

Modifications etc. (not altering text)