- Y Diweddaraf sydd Ar Gael (Diwygiedig) - Saesneg
- Y Diweddaraf sydd Ar Gael (Diwygiedig) - Cymraeg
- Gwreiddiol (Fel y'i Gwnaed) - Saesneg
- Gwreiddiol (Fel y'i Gwnaed) - Cymraeg
Dyma’r fersiwn wreiddiol (fel y’i gwnaed yn wreiddiol).
Regulations 2, 6, 12, 15 and 19
(1) The water should not be aggressive. | ||||
(2) Where treatment to reduce the level of radionuclides in water intended for human consumption has been taken, monitoring must be carried out to ensure the continued efficacy of the treatment. | ||||
(3) Remedial action may be taken by the Welsh Ministers on radiological protection grounds without further consideration and deemed to be justified where radon concentrates exceed 1,000 Bq/1. | ||||
(4) If tritium concentration exceeds its parametric value, an investigation (which may include analysis) of the presence of artificial radionuclides is required. | ||||
(5) May be monitored from samples of water leaving treatment works or other supply point, as no significant change during distribution. | ||||
Item Parameters | Specification | Concentration or Value (maximum unless otherwise stated) or State | Units of Measurement | Point of compliance |
1 | Ammonium | 0.50 | μgAl/l | Consumers’ taps |
2 | Chloride (1) | 250 | mgCl/l | Supply point (5) |
3 | Clostridium perfringens (including spores) | 0 | Number/100 ml | Supply point (5) |
4 | Coliform bacteria | 0 | Number/100 ml | Consumers’ taps |
5 | Colony counts | No abnormal change | Number/1 ml at 22°C | Consumers’ taps, service reservoirs and treatment works |
6 | Conductivity (1) | 2500 | μS/cm at 20°C | Supply point (5) |
7 | Hydrogen ion | 9.5 | pHvalue | Consumers’ taps |
6.5 (minimum) | ||||
8 | Indicative dose (2) | 0.10 | mSv | Supply point (5) |
(a) gross alpha | 0.1 | Bq/l | Supply point (5) | |
(b) gross beta | 1 | Bq/l | Supply point (5) | |
9 | Radon (3) | 100 | Bq/l | Supply point |
10 | Sulphate 1 | 250 | mgSO4/l | Supply point (5) |
11 | Total organic carbon (TOC) | No abnormal change | mgC/l | Supply point |
12 | Tritium (for radioactivity) (4) | 100 | Bq/l | Supply point |
13 | Turbidity | 1 | NTU | Treatment works |
Notes: |
Y Diweddaraf sydd Ar Gael (diwygiedig):Y fersiwn ddiweddaraf sydd ar gael o’r ddeddfwriaeth yn cynnwys newidiadau a wnaed gan ddeddfwriaeth ddilynol ac wedi eu gweithredu gan ein tîm golygyddol. Gellir gweld y newidiadau nad ydym wedi eu gweithredu i’r testun eto yn yr ardal ‘Newidiadau i Ddeddfwriaeth’.
Gwreiddiol (Fel y’i Deddfwyd neu y’i Gwnaed): Mae'r wreiddiol fersiwn y ddeddfwriaeth fel ag yr oedd pan gafodd ei deddfu neu eu gwneud. Ni wnaed unrhyw newidiadau i’r testun.
Gallwch wneud defnydd o ddogfennau atodol hanfodol a gwybodaeth ar gyfer yr eitem ddeddfwriaeth o’r tab hwn. Yn ddibynnol ar yr eitem ddeddfwriaeth sydd i’w gweld, gallai hyn gynnwys:
Defnyddiwch y ddewislen hon i agor dogfennau hanfodol sy’n cyd-fynd â’r ddeddfwriaeth a gwybodaeth am yr eitem hon o ddeddfwriaeth. Gan ddibynnu ar yr eitem o ddeddfwriaeth sy’n cael ei gweld gall hyn gynnwys:
liciwch ‘Gweld Mwy’ neu ddewis ‘Rhagor o Adnoddau’ am wybodaeth ychwanegol gan gynnwys