xmlns:atom="http://www.w3.org/2005/Atom" xmlns:atom="http://www.w3.org/2005/Atom"

Regulations 2 and 4

SCHEDULE 2S INDICATOR PARAMETERS

Notes:

{s011} The water should not be aggressive.

{s012} Excluding tritium, potassium – 40, radon and radon decay products.

{s013} May be monitored from samples of water leaving treatment works or other supply point, as no significant change during distribution.

ItemParametersConcentration or Value (maximum) or StateUnits of MeasurementPoint of monitoring
1.Ammonium0.50mgNH4/lconsumers’ taps
2.Chloride {s011}250mgCl/lsupply point {s013}
3.Clostridium perfringens (including spores)0Number/100 mlsupply point {s013}
4.Coliform bacteria0Number/100mlconsumers’ taps
5.Colony countNo abnormal changeNumber/1 ml at 22°Cconsumers’ taps
Number/1 ml at 37°Cservice reservoirs and treatment works
6.Conductivity {s011}2500μS/cm at 20°Csupply point {s013}
7.Sulphate {s011}250mgSO4/lsupply point {s013}
8.Total indicative dose (for radioactivity) {s012}0.10mSv/yearsupply point {s013}
9.Total organic carbon (TOC)No abnormal changemgC/lsupply point {s013}
10.Tritium (for radioactivity)100Bq/lsupply point {s013}
11.Turbidity1NTUtreatment works