xmlns:atom="http://www.w3.org/2005/Atom" xmlns:atom="http://www.w3.org/2005/Atom"

ANNEX VIIU.K.EMISSION LIMIT VALUES FOR DUST

A.Dust emission limit values expressed in mg/Nm3 (O2 content 6 % for solid fuels, 3 % for liquid and gaseous fuels) to be applied by new and existing plants pursuant to Article 4(1) and 4(3), respectively:U.K.

a

A limit value of 100 mg/Nm3 may be applied to plants with a rated thermal input of less than 500 MWth burning liquid fuel with an ash content of more than 0,06 %.

b

A limit value of 100 mg/Nm3 may be applied to plants licensed pursuant to Article 4(3) with a rated thermal input greater than or equal to 500 MWth burning solid fuel with a heat content of less than 5 800 kJ/kg (net calorific value), a moisture content greater than 45 % by weight, a combined moisture and ash content greater than 60 % by weight and a calcium oxide content greater than 10 %.

Type of fuelRated thermal input(MW)Emission limit values(mg/Nm3)
Solid

≥ 500

< 500

50b

100

Liquidaall plants50
Gaseousall plants

5 as a rule

10 for blast furnace gas

50 for gases produced by the steel industry which can be used elsewhere

B.Dust emission limit values expressed in mg/Nm3 to be applied by new plants, pursuant to Article 4(2) with the exception of gas turbines:U.K.

Solid fuels (O2 content 6 %)U.K.

50 to 100 MWth> 100 MWth
5030

Liquid fuels (O2 content 3 %)U.K.

50 to 100 MWth> 100 MWth
5030

In the case of two installations with a rated thermal input of 250 MWth on Crete and Rhodos to be licensed before 31 December 2007 the emission limit value of 50 mg/Nm3 shall apply.

Gaseous fuels (O2 content 3 %)U.K.

As a rule5
For blast furnace gas10