The type of minimum protection for permanently installed parts of an installation shall be as set out in the following table:
a Where appliances release large amounts of heat: IP 12. | ||||||
b Where appliances or panels do not have this type of protection their location shall meet the conditions applying to that type of protection. | ||||||
c Electrical equipment of the certified safety type as in accordance with (a) European standards EN 50014: 1997; 50015: 1998; 50016: 2002; 50017: 1998; 50018: 2000; 50019: 2000 and 50020: 2002; or (b) IEC publication 60079 as of 1 October 2003. | ||||||
Location | Type of minimum protection(in accordance with IEC publ. 60529: 1992) | |||||
---|---|---|---|---|---|---|
Generators | Motors | Trans-formers | PanelsDistributorsSwitches | Fittings | Lighting equipment | |
Operation rooms, engine rooms, steering-gear compartments | IP 22 | IP 22 | IPb 22 | IPa b 22 | IP 44 | IP 22 |
Holds | IP 55 | IP 55 | ||||
Battery and paint lockers | IP 44 u. (Ex)c | |||||
Free decks and open steering positions | IP 55 | IP 55 | IP 55 | IP 55 | ||
Wheelhouse | IP 22 | IP 22 | IP 22 | IP 22 | IP 22 | |
Accommodation apart from sanitary facilities and washrooms | IP 22 | IP 20 | IP 20 | |||
Sanitary facilities and washrooms | IP 44 | IP 44 | IP 44 | IP 55 | IP 44 |