ANNEX I SAFETY REQUIREMENTS FOR NEW AND EXISTING PASSENGER SHIPS ENGAGED ON DOMESTIC VOYAGES

CHAPTER II-2 FIRE PROTECTION, FIRE DETECTION AND FIRE EXTINCTION

PART A GENERAL

7 Special arrangements in machinery spaces (R 11)
NEW CLASS B, C AND D AND EXISTING CLASS B SHIPS:
.1The number of skylights, doors, ventilators, openings in funnels to permit exhaust ventilation and other openings to machinery spaces shall be reduced to a minimum consistent with the needs of ventilation and the proper and safe working of the ship.
.2Skylights shall be of steel and shall not contain glass panels. Suitable arrangements shall be made to permit the release of smoke in the event of fire, from the space to be protected.
NEW CLASS B, C AND D SHIPS:
.3Doors other than power-operated watertight doors, shall be so arranged that positive closure is assured in case of fire in the space, by power-operated closing arrangements or by the provision of self-closing doors capable of closing against an inclination of 3,5° opposing closure and having a fail-safe hold-back facility, provided with a remotely operated release device.
NEW CLASS B, C AND D AND EXISTING CLASS B SHIPS:
.4Windows shall not be fitted in machinery space boundaries. This does not preclude the use of glass in control rooms within the machinery spaces.
.5Means of control shall be provided for:
.1

opening and closure of skylights, closure of openings in funnels which normally allow exhaust ventilation, and closure of ventilator dampers;

.2

permitting the release of smoke;

.3

closing power-operated doors or actuating release mechanism on doors other than power-operated watertight doors;

.4

stopping ventilating fans; and

.5

stopping forced and induced draught fans, oil fuel transfer pumps, oil fuel unit pumps and other similar fuel pumps. Other similar fuel pumps means for ships constructed on or after 1 January 2003 lubricating oil service pumps, thermal oil circulating pumps and oil separators. However paragraph .6 of this Regulation need not apply to oily water separators.

.6The controls required in paragraph .5 and Regulation II-2/A/10.2.5 shall be located outside the space concerned, where they will not be cut off in the event of fire in the space they serve. Such controls and the controls for any required fire-extinguishing system shall be situated at one control position or grouped in as few positions as possible. Such positions shall have a safe access from the open deck.
.7When access to any machinery space of category A is provided at a low level from an adjacent shaft tunnel, there shall be provided in the shaft tunnel, near the watertight door, a light steel fire-screen door operable from each side.