The test procedures to be applied for the type-approval of hydrogen containers designed to use liquid hydrogen must include:
Burst test: the purpose of the test is to provide evidence that the hydrogen container does not fail before a specified level of high pressure, the burst pressure (safety factor multiplied by the MAWP) is exceeded. In order to obtain type-approval, the value of the real burst pressure during the test must exceed the required minimum burst pressure.
Bonfire test: the purpose of the test is to provide evidence that the container with its fire protection system does not burst when tested under specified fire conditions.
Maximum filling level test: the purpose of the test is to provide evidence that the system, which prevents overfilling of the container, works adequately and that the level of hydrogen during the filling procedure never causes the opening of the pressure relief devices.
Pressure test: the purpose of the test is to provide evidence that the hydrogen container can withstand a specified level of high pressure. In order to prove this, the container is pressurised to a given value for a specified time. After the test the container must not show any signs of visible permanent deformation or visible leaks.
Leak test: the purpose of the test is to provide evidence that the hydrogen container does not show evidence of leakage under specified conditions. In order to prove this, the container is pressurised to its nominal working pressure. It must not show any evidence of leakage detected through cracks, pores or other similar defects.