[F1ANNEX III U.K. DISPOSAL, RECOVERY AND USE AS A FUEL]

CHAPTER IU.K. GENERAL REQUIREMENTS FOR INCINERATION AND CO-INCINERATION

Section 2 U.K. Operating conditions

Incineration or co-incineration plants shall be designed, equipped, built and operated in such a way that the gas resulting from the process is raised in a controlled and homogeneous fashion, even under the most unfavourable conditions, to a temperature of 850 °C for at least 2 seconds or to a temperature of 1 100 °C for 0.2 seconds, as measured near the inner wall or at another representative point of the chamber where the incineration or the co-incineration is carried out, as authorised by the competent authority.