European seasonal conditions, as defined in Table 1 of this Annex;
Reference design conditions, as defined in Table 3 of this Annex;
Electric energy consumption for all relevant modes of operation, using time periods as defined in Table 4 of this Annex;
Effects of the degradation of the energy efficiency caused by on/off cycling (if applicable) depending on the type of control of the cooling and/or heating capacity;
Corrections on the seasonal coefficients of performance in conditions where the heating load can not be met by the heating capacity;
The contribution of a back-up heater (if applicable) in the calculation of the seasonal efficiency of a unit in heating mode.
Bin number (j), outdoor temperature (Tj) in °C and number of hours per bin (hj) for the cooling season and for heating seasons ‘average’, ‘warmer’ and ‘colder’. ‘db’ = dry bulb temperature
COOLING SEASON | HEATING SEASON | |||||||
---|---|---|---|---|---|---|---|---|
Average | Warmer | Colder | ||||||
j# | Tj°C | hjh | j# | Tj°C | hjAh | hj Wh | hjCh | |
db | db | |||||||
1 | 17 | 205 | 1 to 8 | – 30 to – 23 | 0 | 0 | 0 | |
2 | 18 | 227 | 9 | -22 | 0 | 0 | 1 | |
3 | 19 | 225 | 10 | -21 | 0 | 0 | 6 | |
4 | 20 | 225 | 11 | -20 | 0 | 0 | 13 | |
5 | 21 | 216 | 12 | -19 | 0 | 0 | 17 | |
6 | 22 | 215 | 13 | -18 | 0 | 0 | 19 | |
7 | 23 | 218 | 14 | -17 | 0 | 0 | 26 | |
8 | 24 | 197 | 15 | -16 | 0 | 0 | 39 | |
9 | 25 | 178 | 16 | -15 | 0 | 0 | 41 | |
10 | 26 | 158 | 17 | -14 | 0 | 0 | 35 | |
11 | 27 | 137 | 18 | -13 | 0 | 0 | 52 | |
12 | 28 | 109 | 19 | -12 | 0 | 0 | 37 | |
13 | 29 | 88 | 20 | -11 | 0 | 0 | 41 | |
14 | 30 | 63 | 21 | -10 | 1 | 0 | 43 | |
15 | 31 | 39 | 22 | -9 | 25 | 0 | 54 | |
16 | 32 | 31 | 23 | -8 | 23 | 0 | 90 | |
17 | 33 | 24 | 24 | -7 | 24 | 0 | 125 | |
18 | 34 | 17 | 25 | -6 | 27 | 0 | 169 | |
19 | 35 | 13 | 26 | -5 | 68 | 0 | 195 | |
20 | 36 | 9 | 27 | -4 | 91 | 0 | 278 | |
21 | 37 | 4 | 28 | -3 | 89 | 0 | 306 | |
22 | 38 | 3 | 29 | -2 | 165 | 0 | 454 | |
23 | 39 | 1 | 30 | -1 | 173 | 0 | 385 | |
24 | 40 | 0 | 31 | 0 | 240 | 0 | 490 | |
32 | 1 | 280 | 0 | 533 | ||||
33 | 2 | 320 | 3 | 380 | ||||
34 | 3 | 357 | 22 | 228 | ||||
35 | 4 | 356 | 63 | 261 | ||||
36 | 5 | 303 | 63 | 279 | ||||
37 | 6 | 330 | 175 | 229 | ||||
38 | 7 | 326 | 162 | 269 | ||||
39 | 8 | 348 | 259 | 233 | ||||
40 | 9 | 335 | 360 | 230 | ||||
41 | 10 | 315 | 428 | 243 | ||||
42 | 11 | 215 | 430 | 191 | ||||
43 | 12 | 169 | 503 | 146 | ||||
44 | 13 | 151 | 444 | 150 | ||||
45 | 14 | 105 | 384 | 97 | ||||
46 | 15 | 74 | 294 | 61 | ||||
Total | 2 602 | 4 910 | 3 590 | 6 446 |
Standard rating conditions, temperatures in ‘dry bulb’ air temperature (‘wet bulb’ indicated in brackets)
a In case of single ducts, the condensor (evaporator) when cooling (heating), is not supplied with outdoor air, but indoor air. | |||
Appliance | Function | Indoor air temperature(°C) | Outdoor air temperature(°C) |
---|---|---|---|
air conditioners, excluding single duct | cooling | 27 (19) | 35 (24) |
heating | 20 (max. 15) | 7(6) | |
single duct | cooling | 35 (24) | 35 (24)a |
heating | 20 (12) | 20 (12)a |
Reference design conditions, temperatures in ‘dry bulb’ air temperature (‘wet bulb’ indicated in brackets)
Function / season | Indoor air temperature(°C) | Outdoor air temperature(°C) | Bivalent temperature(°C) | Operating limit temperature(°C) |
---|---|---|---|---|
Tin | Tdesignc/Tdesignh | Tbiv | Tol | |
cooling | 27 (19) | Tdesignc = 35 (24) | n.a. | n.a. |
heating / Average | 20 (15) | Tdesignh = – 10 (– 11) | max. 2 | max. – 7 |
heating / Warmer | Tdesignh = 2 (1) | max. 7 | max. 2 | |
heating / Colder | Tdesignh = – 22 (– 23) | max. – 7 | max. – 15 |
Operational hours per type of appliance per functional mode to be used for calculation of electricity consumption
Type of appliance / functionality (if applicable) | Unit | Heating season | On mode | Thermostat-off mode | Standby mode | Off mode | Crankcase heater mode | |
---|---|---|---|---|---|---|---|---|
cooling: HCEheating: HHE | HTO | HSB | HOFF | HCK | ||||
Air conditioners, except double ducts and single duct | ||||||||
Cooling mode, if appliance offers cooling only | h/annum | 350 | 221 | 2 142 | 5 088 | 7 760 | ||
Cooling and heating modes, if appliance offers both modes | Cooling mode | h/annum | 350 | 221 | 2 142 | 0 | 2 672 | |
Heating mode | h/annum | Average | 1 400 | 179 | 0 | 0 | 179 | |
Warmer | 1 400 | 755 | 0 | 0 | 755 | |||
Colder | 2 100 | 131 | 0 | 0 | 131 | |||
Heating mode, if appliance offers heating only | h/annum | Average | 1 400 | 179 | 0 | 3 672 | 3 851 | |
Warmer | 1 400 | 755 | 0 | 4 345 | 4 476 | |||
Colder | 2 100 | 131 | 0 | 2 189 | 2 944 | |||
Double duct air conditioner | cooling: HCEheating: HHE | HTO | HSB | HOFF | HCK | |||
Cooling mode, if appliance offers cooling only | h/60 min | 1 | n/a | n/a | n/a | n/a | ||
Cooling and heating modes, if appliance offers both modes | Cooling mode | h/60 min | 1 | n/a | n/a | n/a | n/a | |
Heating mode | h/60 min | 1 | n/a | n/a | n/a | n/a | ||
Heating mode, if appliance offers heating only | h/60 min | 1 | n/a | n/a | n/a | n/a | ||
Single duct air conditioner | cooling: HCEheating: HHE | |||||||
Cooling mode | h/60 min | 1 | n/a | n/a | n/a | n/a | ||
Heating mode | h/60 min | 1 | n/a | n/a | n/a | n/a |