ANNEX VTechnical documentation

1.SPACE HEATERS

For space heaters, the technical documentation referred to in Article 3(1)(c) shall include:

  1. (a)

    the name and address of the supplier;

  2. (b)

    a description of the space heater model sufficient for its unambiguous identification;

  3. (c)

    where appropriate, the references of the harmonised standards applied;

  4. (d)

    where appropriate, the other technical standards and specifications used;

  5. (e)

    the identification and signature of the person empowered to bind the supplier;

  6. (f)

    technical parameters:

    • for boiler space heaters and cogeneration space heaters, the technical parameters set out in Table 7, measured and calculated in accordance with Annex VII;

    • for heat pump space heaters, the technical parameters set out in Table 8, measured and calculated in accordance with Annex VII;

    • for heat pump space heaters where the information relating to a specific model comprising a combination of indoor and outdoor units has been obtained by calculation on the basis of design and/or extrapolation from other combinations, the details of such calculations and/or extrapolations, and of any tests undertaken to verify the accuracy of the calculations, including details of the mathematical model for calculating the performance of such combinations and details of the measurements taken to verify this model;

  7. (g)

    any specific precautions that shall be taken when the space heater is assembled, installed or maintained.

2.COMBINATION HEATERS

For combination heaters, the technical documentation referred to in Article 3(2)(c) shall include:

  1. (a)

    the name and address of the supplier;

  2. (b)

    a description of the combination heater model sufficient for its unambiguous identification;

  3. (c)

    where appropriate, the references of the harmonised standards applied;

  4. (d)

    where appropriate, the other technical standards and specifications used;

  5. (e)

    the identification and signature of the person empowered to bind the supplier;

  6. (f)

    technical parameters:

    • for boiler combination heaters, the technical parameters set out in Table 7, measured and calculated in accordance with Annex VII;

    • for heat pump combination heaters, the technical parameters set out in Table 8, measured and calculated in accordance with Annex VII;

    • for heat pump combination heaters where the information relating to a specific model comprising a combination of indoor and outdoor units has been obtained by calculation on the basis of design and/or extrapolation from other combinations, the details of such calculations and/or extrapolations, and of any tests undertaken to verify the accuracy of the calculations, including details of the mathematical model for calculating the performance of such combinations and details of the measurements taken to verify this model;

  7. (g)

    any specific precautions that shall be taken when the combination heater is assembled, installed or maintained.

Table 7Technical parameters for boiler space heaters, boiler combination heaters and cogeneration space heaters

Model(s): [information identifying the model(s) to which the information relates]

Condensing boiler: [yes/no]

Low-temperature14 boiler: [yes/no]

B11 boiler: [yes/no]

Cogeneration space heater: [yes/no]

If yes, equipped with a supplementary heater: [yes/no]

Combination heater: [yes/no]

Item

Symbol

Value

Unit

Item

Symbol

Value

Unit

Rated heat output

Prated

x

kW

Seasonal space heating energy efficiency

ηs

x

%

For boiler space heaters and boiler combination heaters: Useful heat output

For boiler space heaters and boiler combination heaters: Useful efficiency

At rated heat output and high-temperature regime13

P4

x,x

kW

At rated heat output and high-temperature regime13

η4

x,x

%

At 30 % of rated heat output and low-temperature regime14

P1

x,x

kW

At 30 % of rated heat output and low-temperature regime14

η1

x,x

%

For cogeneration space heaters: Useful heat output

For cogeneration space heaters: Useful efficiency

At rated heat output of cogeneration space heater with supplementary heater disabled

PCHP100+Sup0

x,x

kW

At rated heat output of cogeneration space heater with supplementary heater disabled

ηCHP100+Sup0

x,x

%

At rated heat output of cogeneration space heater with supplementary heater enabled

PCHP100+Sup100

x,x

kW

At rated heat output of cogeneration space heater with supplementary heater enabled

ηCHP100+Sup100

x,x

%

For cogeneration space heaters: Electrical efficiency

Supplementary heater

At rated heat output of cogeneration space heater with supplementary heater disabled

ηel,CHP100+Sup0

x,x

%

Rated heat output

Psup

x,x

kW

At rated heat output of cogeneration space heater with supplementary heater enabled

ηel,CHP100+Sup100

x,x

%

Type of energy input

Auxiliary electricity consumption

Other items

At full load

elmax

x,x

kW

Standby heat loss

Pstby

x,x

kW

At part load

elmin

x,x

kW

Ignition burner power consumption

Pign

x,x

kW

In standby mode

PSB

x,xxx

kW

Annual energy consumption

QHE

x

kWh or GJ

Sound power level, indoors

LWA

x

dB

For combination heaters:

Declared load profile

Water heating energy efficiency

ηwh

x

%

Daily electricity consumption

Qelec

x,xxx

kWh

Daily fuel consumption

Qfuel

x,xxx

kWh

Annual electricity consumption

AEC

x

kWh

Annual fuel consumption

AFC

x

GJ

Contact details

Name and address of the supplier.

High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.

Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C return temperature (at heater inlet).

Table 8Technical parameters for heat pump space heaters and heat pump combination heaters

Model(s): [information identifying the model(s) to which the information relates]

Air-to-water heat pump: [yes/no]

Water-to-water heat pump: [yes/no]

Brine-to-water heat pump: [yes/no]

Low-temperature heat pump: [yes/no]

Equipped with a supplementary heater: [yes/no]

Heat pump combination heater: [yes/no]

Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pumps, parameters shall be declared for low-temperature application.

Parameters shall be declared for average, colder and warmer climate conditions.

Item

Symbol

Value

Unit

Item

Symbol

Value

Unit

Rated heat output15

Prated

x

kW

Seasonal space heating energy efficiency

ηs

x

%

Declared capacity for heating for part load at indoor temperature 20 °C and outdoor temperature Tj

Declared coefficient of performance or primary energy ratio for part load at indoor temperature 20 °C and outdoor temperature Tj

Tj = – 7 °C

Pdh

x,x

kW

Tj = – 7 °C

COPd or PERd

x,xx or x,x

– or %

Tj = + 2 °C

Pdh

x,x

kW

Tj = + 2 °C

COPd or PERd

x,xx or x,x

– or %

Tj = + 7 °C

Pdh

x,x

kW

Tj = + 7 °C

COPd or PERd

x,xx or x,x

– or %

Tj = + 12 °C

Pdh

x,x

kW

Tj = + 12 °C

COPd or PERd

x,xx or x,x

– or %

Tj = bivalent temperature

Pdh

x,x

kW

Tj = bivalent temperature

COPd or PERd

x,xx or x,x

– or %

Tj = operation limit temperature

Pdh

x,x

kW

Tj = operation limit temperature

COPd or PERd

x,xx or x,x

– or %

For air-to-water heat pumps: Tj = – 15 °C (if TOL < – 20 °C)

Pdh

x,x

kW

For air-to-water heat pumps: Tj = – 15 °C (if TOL < – 20 °C)

COPd or PERd

x,xx or x,x

– or %

Bivalent temperature

Tbiv

x

°C

For air-to-water heat pumps: Operation limit temperature

TOL

x

°C

Cycling interval capacity for heating

Pcych

x,x

kW

Cycling interval efficiency

COPcyc or PERcyc

x,xx or x,x

– or %

Degradation co-efficient16

Cdh

x,x

Heating water operating limit temperature

WTOL

x

°C

Power consumption in modes other than active mode

Supplementary heater

Off mode

POFF

x,xxx

kW

Rated heat output16

Psup

x,x

kW

Thermostat-off mode

PTO

x,xxx

kW

Standby mode

PSB

x,xxx

kW

Type of energy input

Crankcase heater mode

PCK

x,xxx

kW

Other items

Capacity control

fixed/variable

For air-to-water heat pumps: Rated air flow rate, outdoors

x

m3/h

Sound power level, indoors/outdoors

LWA

x / x

dB

For water- or brine-to-water heat pumps: Rated brine or water flow rate, outdoor heat exchanger

x

m3/h

Annual energy consumption

QHE

x

kWh or GJ

For heat pump combination heater:

Declared load profile

x

Water heating energy efficiency

ηwh

x

%

Daily electricity consumption

Qelec

x,xxx

kWh

Daily fuel consumption

Qfuel

x,xxx

kWh

Annual electricity consumption

AEC

x

kWh

Annual fuel consumption

AFC

x

GJ

Contact details

Name and address of the supplier.

For heat pump space heaters and heat pump combination heaters, the rated heat output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup(Tj).

If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.

3.TEMPERATURE CONTROLS

For temperature controls, the technical documentation referred to in Article 3(3)(b) shall include:

  1. (a)

    the name and address of the supplier;

  2. (b)

    a description of the temperature control model sufficient for its unambiguous identification;

  3. (c)

    where appropriate, the references of the harmonised standards applied;

  4. (d)

    where appropriate, the other technical standards and specifications used;

  5. (e)

    the identification and signature of the person empowered to bind the supplier;

  6. (f)

    technical parameters:

    • the class of the temperature control;

    • the contribution of the temperature control to seasonal space heating energy efficiency in %, rounded to one decimal place;

  7. (g)

    any specific precautions that shall be taken when the temperature control is assembled, installed or maintained.

4.SOLAR DEVICES

For solar devices, the technical documentation referred to in Article 3(4)(b) shall include:

  1. (a)

    the name and address of the supplier;

  2. (b)

    a description of the solar device model sufficient for its unambiguous identification;

  3. (c)

    where appropriate, the references of the harmonised standards applied;

  4. (d)

    where appropriate, the other technical standards and specifications used;

  5. (e)

    the identification and signature of the person empowered to bind the supplier;

  6. (f)

    technical parameters (for pumps in the collector loop if applicable):

    • the collector aperture area Asol in m2, to two decimal places;

    • the collector efficiency ηcol in %, rounded to the nearest integer;

    • the energy efficiency class of the solar hot water storage tank, determined in accordance with point 3 of Annex II;

    • the standing loss S of the solar hot water storage tank in W, rounded to the nearest integer;

    • the storage volume V of the solar hot water storage tank in litres and m3;

    • the annual non-solar heat contribution Qnonsol in kWh in terms of primary energy for electricity and/or in kWh in terms of GCV for fuels, for the load profiles M, L, XL and XXL under average climate conditions, rounded to the nearest integer;

    • the pump power consumption solpump in W, rounded to the nearest integer;

    • the standby power consumption solstandby in W, to two decimal places;

    • the annual auxiliary electricity consumption Qaux in kWh in terms of final energy, rounded to the nearest integer;

  7. (g)

    any specific precautions that shall be taken when the solar device is assembled, installed or maintained.

5.PACKAGES OF SPACE HEATER, TEMPERATURE CONTROL AND SOLAR DEVICE

For packages of space heater, temperature control and solar device, the technical documentation referred to in Article 3(5)(c) shall include:

  1. (a)

    the name and address of the supplier;

  2. (b)

    a description of the package of space heater, temperature control and solar device model sufficient for its unambiguous identification;

  3. (c)

    where appropriate, the references of the harmonised standards applied;

  4. (d)

    where appropriate, the other technical standards and specifications used;

  5. (e)

    the identification and signature of the person empowered to bind the supplier;

  6. (f)

    technical parameters:

    • the seasonal space heating energy efficiency in %, rounded to the nearest integer;

    • the technical parameters set out in points 1, 3 and 4 of this Annex;

  7. (g)

    any specific precautions that shall be taken when the package of space heater, temperature control and solar device is assembled, installed or maintained.

6.PACKAGES OF COMBINATION HEATER, TEMPERATURE CONTROL AND SOLAR DEVICE

For packages of combination heater, temperature control and solar device, the technical documentation referred to in Article 3(6)(c) shall include:

  1. (a)

    the name and address of the supplier;

  2. (b)

    a description of the package of combination heater, temperature control and solar device model sufficient for its unambiguous identification;

  3. (c)

    where appropriate, the references of the harmonised standards applied;

  4. (d)

    where appropriate, the other technical standards and specifications used;

  5. (e)

    the identification and signature of the person empowered to bind the supplier;

  6. (f)

    technical parameters:

    • the seasonal space heating energy efficiency and water heating energy efficiency in %, rounded to the nearest integer;

    • the technical parameters set out in points 2, 3 and 4 of this Annex;

  7. (g)

    any specific precautions that shall be taken when the package of combination heater, temperature control and solar device is assembled, installed or maintained.