4. Seasonal space heating energy efficiency and consumption of heat pump space heaters and heat pump combination heaters
(a)For establishing the rated coefficient of performance COPrated or rated primary energy ratio PERrated , or the sound power level, the operating conditions shall be the standard rating conditions set out in Table 9 and the same declared capacity for heating shall be used.
(b)The active mode coefficient of performance SCOPon for average, colder and warmer climate conditions shall be calculated on the basis of the part load for heating Ph(Tj), the supplementary capacity for heating sup(Tj) (if applicable), and the bin-specific coefficient of performance COPbin(Tj) or bin-specific primary energy ratio PERbin(Tj), weighted by the bin-hours for which the bin conditions apply, using the following conditions:
the reference design conditions set out in Table 10;
the European reference heating season under average, colder and warmer climate conditions set out in Table 12;
if applicable, the effects of any degradation of energy efficiency caused by cycling, depending on the type of control of the heating capacity.
(c)The reference annual heating demand QH shall be the design load for heating Pdesignh for average, colder and warmer climate conditions, multiplied by the annual equivalent active mode hours HHE of 2 066, 2 465 and 1 336 for average, colder and warmer climate conditions, respectively.
(d)The annual energy consumption QHE shall be calculated as the sum of:
the ratio of the reference annual heating demand QH and the active mode coefficient of performance SCOPon or active mode primary energy ratio SPERon ; and
the energy consumption for off, thermostat-off, standby, and crankcase heater mode during the heating season.