Commission Regulation (EU) No 813/2013Show full title

Commission Regulation (EU) No 813/2013 of 2 August 2013 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for space heaters and combination heaters (Text with EEA relevance)

3.REQUIREMENTS FOR SOUND POWER LEVEL

From 26 September 2015 the sound power level of heat pump space heaters and heat pump combination heaters shall not exceed the following values:

Rated heat output ≤ 6 kWRated heat output > 6 kW and ≤ 12 kWRated heat output > 12 kW and ≤ 30 kWRated heat output > 30 kW and ≤ 70 kW
Sound power level (LWA ), indoorsSound power level (LWA ), outdoorsSound power level (LWA ), indoorsSound power level (LWA ), outdoorsSound power level (LWA ), indoorsSound power level (LWA ), outdoorsSound power level (LWA ), indoorsSound power level (LWA ), outdoors
60 dB65 dB65 dB70 dB70 dB78 dB80 dB88 dB