CHAPTER IICONTAINMENT

Article 5Leakage detection systems

1

Operators of the equipment listed in points (a) to (d) of Article 4(2) and containing fluorinated greenhouse gases in quantities of 500 tonnes of CO2 equivalent or more, shall ensure that the equipment is provided with a leakage detection system which alerts the operator or a service company of any leakage.

2

Operators of the equipment listed in points (f) and (g) of Article 4(2) and containing fluorinated greenhouse gases in quantities of 500 tonnes of CO2 equivalent or more and installed from 1 January 2017, shall ensure that this equipment is provided with a leakage detection system which alerts the operator or a service company of any leakage.

3

Operators of the equipment listed in points (a) to (d) and (g) of Article 4(2) that is subject to paragraph 1 or 2 of this Article shall ensure that leakage detection systems are checked at least once every 12 months to ensure their proper functioning.

4

Operators of the equipment listed in point (f) of Article 4(2) that is subject to paragraph 2 of this Article shall ensure that leakage detection systems are checked at least once every 6 years to ensure their proper functioning.