Commission Regulation (EU) 2016/1388Show full title

Commission Regulation (EU) 2016/1388 of 17 August 2016 establishing a Network Code on Demand Connection (Text with EEA relevance)

ANNEX IU.K. Frequency ranges and time periods referred to in Article 12(1)

Synchronous areaFrequency rangeTime period for operation
Continental Europe47,5 Hz-48,5 HzTo be specified by each TSO, but not less than 30 minutes
48,5 Hz-49,0 HzTo be specified by each TSO, but not less than the period for 47,5 Hz-48,5 Hz
49,0 Hz-51,0 HzUnlimited
51,0 Hz-51,5 Hz30 minutes
Nordic47,5 Hz-48,5 Hz30 minutes
48,5 Hz-49,0 HzTo be specified by each TSO, but not less than 30 minutes
49,0 Hz-51,0 HzUnlimited
51,0 Hz-51,5 Hz30 minutes
Great Britain47,0 Hz-47,5 Hz20 seconds
47,5 Hz-48,5 Hz90 minutes
48,5 Hz-49,0 HzTo be specified by each TSO, but not less than 90 minutes
49,0 Hz-51,0 HzUnlimited
51,0 Hz-51,5 Hz90 minutes
51,5 Hz-52,0 Hz15 minutes
Ireland and Northern Ireland47,5 Hz-48,5 Hz90 minutes
48,5 Hz-49,0 HzTo be specified by each TSO, but not less than 90 minutes
49,0 Hz-51,0 HzUnlimited
51,0 Hz-51,5 Hz90 minutes
Baltic47,5 Hz-48,5 HzTo be specified by each TSO, but not less than 30 minutes
48,5 Hz-49,0 HzTo be specified by each TSO, but not less than the period for 47,5 Hz-48,5 Hz
49,0 Hz-51,0 HzUnlimited
51,0 Hz-51,5 HzTo be specified by each TSO, but not less than 30 minutes

The table shows the minimum time periods for which a transmission-connected demand facility, a transmission-connected distribution facility or a distribution system has to be capable of operating on different frequencies, deviating from a nominal value, without disconnecting from the network.

ANNEX IIU.K. Voltage ranges and time periods referred to in Article 13(1)

Synchronous areaVoltage rangeTime period for operation
Continental Europe0,90 pu-1,118 puUnlimited
1,118 pu-1,15 puTo be specified by each TSO but not less than 20 minutes and not more than 60 minutes
Nordic0,90 pu-1,05 puUnlimited
1,05 pu-1,10 pu60 minutes
Great Britain0,90 pu-1,10 puUnlimited
Ireland and Northern Ireland0,90 pu-1,118 puUnlimited
Baltic0,90 pu-1,118 puUnlimited
1,118 pu-1,15 pu20 minutes

The table shows the minimum time periods during which a transmission-connected demand facility, a transmission-connected distribution facility or a transmission-connected distribution system has to be capable of operating for voltages deviating from the reference 1 pu value at the connection point without disconnecting from the network where the voltage base for pu values is at or above 110 kV and up to (not including) 300 kV.

Synchronous areaVoltage rangeTime period for operation
Continental Europe0,90 pu-1,05 puUnlimited
1,05 pu-1,10 puTo be specified by each TSO but not less than 20 minutes and not more than 60 minutes
Nordic0,90 pu-1,05 puUnlimited
1,05 pu-1,10 puTo be specified by each TSO but not more than 60 minutes
Great Britain0,90 pu-1,05 puUnlimited
1,05 pu-1,10 pu15 minutes
Ireland and Northern Ireland0,90 pu-1,05 puUnlimited
Baltic0,90 pu-1,097 puUnlimited
1,097 pu-1,15 pu20 minutes

The table shows the minimum time periods during which a transmission-connected demand facility, a transmission-connected distribution facility or a transmission-connected distribution system has to be capable of operating for voltages deviating from the reference 1 pu value at the connection point without disconnecting from the network, where the voltage base for pu values is from 300 kV to 400 kV (including).