ANNEX VVoltage-against-time-profile referred to in Article 25

Annotations:
Amendments (Textual)

Image_r00006

Figure 6: Fault-ride-through profile of an HVDC converter station. The diagram represents the lower limit of a voltage-against-time profile at the connection point, expressed by the ratio of its actual value and its reference 1 pu value in per unit before, during and after a fault. Uret is the retained voltage at the connection point during a fault, tclear is the instant when the fault has been cleared, Urec1 and trec1 specify a point of lower limits of voltage recovery following fault clearance. Ublock is the blocking voltage at the connection point. The time values referred to are measured from tfault.

Voltage parameters [pu]

Time parameters [seconds]

Uret

F10.00-F20.30

tclear

F30.14-F40.25

Urec1

F40.25-F50.85

trec1

F61.5-F72.5

Urec2

F50.85-F80.90

trec2

Trec1-F910.0

Table 7: Parameters for Figure 6 for the fault-ride-through capability of an HVDC converter station.