ANNEX VIIIU.K.Reactive power and voltage requirements referred to in Article 48

Voltage rangeTime period for operation
[F10.85] pu-[F20.90] pu60 minutes
[F20.90] pu-[F31.10] puUnlimited
[F31.10] pu-[F41.12] puUnlimited, unless specified otherwise by the relevant system operator, in coordination with the relevant TSO.
[F41.12] pu-[F51.15] puTo be specified by the relevant system operator, in coordination with the relevant TSO.

Table 12: Minimum time periods for which a remote-end HVDC converter station shall be capable of operating for different voltages deviating from a reference 1 pu value without disconnecting from the network where the voltage base for pu values is from 110 kV to (not including) 300 kV.

Voltage rangeTime period for operation
[F60.85] pu-[F70.90] pu60 minutes
[F70.90] pu-[F81.05] puUnlimited
[F81.05] pu-[F91.15] puTo be specified by the relevant system operator, in coordination with the relevant TSO. Various sub-ranges of voltage withstand capability may be specified.

Table 13: Minimum time periods for which a remote-end HVDC converter station shall be capable of operating for different voltages deviating from a reference 1 pu value without disconnecting from the network where the voltage base for pu values is from 300 kV to 400 kV (included).

Maximum range of Q/PmaxMaximum range of steady-state voltage level in PU
[F100.95][F110.225]

Table 14: Maximum range of both Q/Pmax and steady-state voltage for a remote-end HVDC converter station.