ANNEX III

Annotations:

Frequency quality defining parameters referred to in Article 127:

Table 1Frequency quality defining parameters of F1the GB synchronous area

F3...

GB

F3...

F3...

standard frequency range

F3...

± 200 mHz

F3...

F3...

maximum instantaneous frequency deviation

F3...

800 mHz

F3...

F3...

maximum steady-state frequency deviation

F3...

500 mHz

F3...

F3...

time to recover frequency

F3...

1 minute

F3...

F3...

frequency recovery range

F3...

± 500 mHz

F3...

F3...

time to restore frequency

F3...

15 minutes

F3...

F3...

frequency restoration range

F3...

± 200 mHz

F3...

F3...

alert state trigger time

F3...

10 minutes

F3...

F3...

Frequency quality target parameters referred to in Article 127:

Table 2Frequency quality target parameters of F2the GB synchronous area

F4...

GB

F4...

F4...

maximum number of minutes outside the standard frequency range

F4...

15 000

F4...

F4...