ANNEX IIIU.K.

Frequency quality defining parameters referred to in Article 127:

Table 1

Frequency quality defining parameters of [F1the GB synchronous area]

F2...GBF2...F2...
standard frequency rangeF2...± 200 mHzF2...F2...
maximum instantaneous frequency deviationF2...800 mHzF2...F2...
maximum steady-state frequency deviationF2...500 mHzF2...F2...
time to recover frequencyF2...1 minuteF2...F2...
frequency recovery rangeF2...± 500 mHzF2...F2...
time to restore frequencyF2...15 minutesF2...F2...
frequency restoration rangeF2...± 200 mHzF2...F2...
alert state trigger timeF2...10 minutesF2...F2...

Frequency quality target parameters referred to in Article 127:

Table 2

Frequency quality target parameters of [F3the GB synchronous area]

F4...GBF4...F4...
maximum number of minutes outside the standard frequency rangeF4...15 000F4...F4...