PART IVU.K.LOAD-FREQUENCY CONTROL AND RESERVES

TITLE 2U.K.FREQUENCY QUALITY

Article 130U.K.Frequency quality evaluation data

1.The frequency quality evaluation data shall be:

(a)for the synchronous area:

(i)

the instantaneous frequency data; and

(ii)

the instantaneous frequency deviation data;

(b)for each LFC block of the synchronous area, the instantaneous FRCE data.

2.The measurement accuracy of the instantaneous frequency data and of the instantaneous FRCE data, where measured in Hz, shall be 1 mHz or better.