Regulations 5 and 6

SCHEDULEN.I.Aspects of Energy Efficiency

Table 1

Low-carbon home

Column 1 – Aspects of energy efficiencyColumn 2 – Evidence

Dwelling CO2 emission rate (“DER”)

The DER of the dwelling-house over the course of a year calculated in accordance with the approved methodology must be no more than 56% of the TER calculated in accordance with the approved methodology.

Space Heating Requirement (“SHR”)

The SHR of the dwelling-house over the course of a year calculated in accordance with the approved methodology must be no more than 23 kilowatt-hours per square metre (kWh/m2/year).

Table 2

Zero-carbon home

Column 1 – Aspects of energy efficiencyColumn 2 – Evidence

Heat loss parameter (“HLP”)

The HLP of the dwelling-house calculated in accordance with the approved methodology must be no more than 0.8 Watts per square metre Kelvin (W/m2K).

Dwelling CO2 emission rate (“DER”)

The DER of the dwelling-house over the course of a year calculated in accordance with the approved methodology must be no more than zero kilograms per square metre (kg/ m2/year).

Net CO2 emissions

The net CO2 emissions from the dwelling-house over the course of a year calculated in accordance with the approved methodology must be no more than zero kilograms per square metre (kg/ m2/year).