xmlns:atom="http://www.w3.org/2005/Atom" xmlns:atom="http://www.w3.org/2005/Atom"
1.—(1) The Department must monitor for a Group A parameter in accordance with this Part.
(2) “Monitoring for a Group A parameter” means sampling for—
(a)each parameter listed in column 1 of Table 1 of this Schedule in the circumstances listed in the entry which corresponds with that parameter in column 2 of Table 1 of this Schedule; and
(b)any other parameter which may be identified as relevant by the Department in the monitoring programme.
1 A supply which consists of both groundwater and surface water shall be deemed to be a supply which consists only of surface water. | |
(1) Parameter | (2) Circumstances |
---|---|
Aluminium1 | If used as water treatment chemicals or where the water originates from, or is influenced by, surface waters |
Ammonium | Where chloramination is practised |
Coliform bacteria | In all supplies |
Colony Counts | In all supplies |
Colour | In all supplies |
Conductivity | In all supplies |
Disinfectant residual | When disinfection treatment is practised |
Escherichia coli (E. coli) | In all supplies |
Indicative Dose | Where there is treatment in place to reduce the level of radionuclides in water intended for human consumption. |
Iron1 | If used as water treatment chemicals or where the water originates from, or is influenced by, surface waters |
Manganese1 | Where the water originates from, or is influenced by, surface waters |
Nitrite | Where chloramination is practised |
Odour | In all supplies |
pH (Hydrogen ion) | In all supplies |
Radon | Where there is treatment in place to reduce the level of radionuclides in water intended for human consumption. |
Taste | In all supplies |
Tritium | Where there is treatment in place to reduce the level of radionuclides in water intended for human consumption. |
Turbidity | In all supplies |
2.—(1) Sampling for a Group A parameter which is not a radioactive substance must be undertaken at the frequencies specified in Table 2 for those parameters.N.I.
(2) Sampling for a Group A parameter which is a radioactive substance must be undertaken at the frequencies specified in Table 3 for those parameters.
Volume m3/day(calculated as averages taken over a calendar year) | Sampling frequency per year |
---|---|
≤10 | 1 |
> 10 ≤ 100 | 2 |
> 100 ≤ 1,000 | 4 |
> 1,000 ≤ 2,000 | 10 |
> 2,000 ≤ 3,000 | 13 |
> 3,000 ≤ 4,000 | 16 |
> 4,000 ≤ 5,000 | 19 |
> 5,000 ≤ 6,000 | 22 |
> 6,000 ≤ 7,000 | 25 |
> 7,000 ≤ 8,000 | 28 |
> 8,000 ≤ 9,000 | 31 |
> 9,000 ≤ 10,000 | 34 |
> 10,000 | 4 + 3 for each 1,000 m3/day of the total volume (rounding up to the nearest multiple of 1,000 m3/day) |
Volume m3 /day (calculated as averages taken over a calendar year) | Sampling frequency per year |
---|---|
≤ 1000 | 1 |
> 1000 ≤ 10,000 | 1 + 1 for each 3,300 m3/day of the total volume (rounding up to the nearest multiple of 3,300 m3/day) |
> 10,000 ≤ 100,000 | 3 + 1 for each 10,000 m3/day of the total volume (rounding up to the nearest multiple of 10,000 m3/day) |
> 100,000 | 10 + 1 for each 25,000 m3/day of the total volume (rounding up to the nearest multiple of 25,000 m3/day) |