Changes and effects yet to be applied by the editorial team are only applicable when viewing the latest version or prospective version of legislation. They are therefore not accessible when viewing legislation as at a specific point in time. To view the ‘Changes to Legislation’ information for this provision return to the latest version view using the options provided in the ‘What Version’ box above.
Regulation 9
Textual Amendments
1.1 Every building must be designed and constructed in such a way that the loadings that are liable to act on it, taking into account the nature of the ground, will not lead to:
(a)the collapse of the whole or part of the building;
(b)deformations which would make the building unfit for its intended use, unsafe, or cause damage to other parts of the building or to fittings or to installed equipment; or
(c)impairment of the stability of any part of another building.
1.2 Every building must be designed and constructed in such a way that in the event of damage occurring to any part of the structure of the building the extent of any resultant collapse will not be disproportionate to the original cause.
2.1 Every building must be designed and constructed in such a way that in the event of an outbreak of fire within the building, fire and smoke are inhibited from spreading beyond the compartment of origin until any occupants have had the time to leave that compartment and any fire containment measures have been initiated.
This standard does not apply to domestic buildings.
2.2 Every building, which is divided into more than one area of different occupation, must be designed and constructed in such a way that in the event of an outbreak of fire within the building, fire and smoke are inhibited from spreading beyond the area of occupation where the fire originated.
2.3 Every building must be designed and constructed in such a way that in the event of an outbreak of fire within the building, the load-bearing capacity of the building will continue to function until all occupants have escaped, or been assisted to escape, from the building and any fire containment measures have been initiated.
2.4 Every building must be designed and constructed in such a way that in the event of an outbreak of fire within the building, the F2... spread of fire and smoke within [F3cavities] in its structure and fabric is inhibited.
Textual Amendments
F2Word in sch. 5 para. 2.4 omitted (1.10.2019) by virtue of The Building (Scotland) Amendment Regulations 2019 (S.S.I. 2019/210), regs. 1, 2(2)(a)
F3Word in sch. 5 para. 2.4 substituted (1.10.2019) by The Building (Scotland) Amendment Regulations 2019 (S.S.I. 2019/210), regs. 1, 2(2)(b)
2.5 Every building must be designed and constructed in such a way that in the event of an outbreak of fire within the building, the development of fire and smoke from the surfaces of walls and ceilings within the area of origin is inhibited.
2.6 Every building must be designed and constructed in such a way that in the event of an outbreak of fire within the building, the spread of fire to neighbouring buildings is inhibited.
2.7 Every building must be designed and constructed in such a way that in the event of an outbreak of fire within the building, or from an external source, the spread of fire on the external walls of the building is inhibited.
2.8 Every building must be designed and constructed in such a way that in the event of an outbreak of fire in a neighbouring building, the spread of fire to the building is inhibited.
2.9 Every building must be designed and constructed in such a way that in the event of an outbreak of fire within the building, the occupants, once alerted to the outbreak of the fire, are provided with the opportunity to escape from the building, before being affected by fire or smoke.
2.10 Every building must be designed and constructed in such a way that in the event of an outbreak of fire within the building, illumination is provided to assist in escape.
2.11 Every building must be designed and constructed in such a way that in the event of an outbreak of fire within the building, the occupants are alerted to the outbreak of fire.
F4...
Textual Amendments
F4Sch. 5 para. 2.11: limitation omitted (1.10.2010) by virtue of The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(a) (with reg. 3)
2.12 Every building must be accessible to the fire and rescue service.]
Textual Amendments
F5Sch. 5 para. 2.12 substituted (1.10.2010) by The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(b) (with reg. 3)
2.13 Every building must be provided with a water supply for use by the fire and rescue service.]
Textual Amendments
F6Sch. 5 para. 2.13 substituted (1.10.2010) by The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(c) (with reg. 3)
This standard does not apply to domestic buildings.
2.14 Every building must be designed and constructed in such a way that facilities are provided to assist fire-fighting or rescue operations.
Textual Amendments
F7Words in sch. 5 para. 2.14 heading inserted (1.10.2010) by The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(d) (with reg. 3)
2.15 Every building must be designed and constructed in such a way that in the event of an outbreak of fire within the building, fire growth will be inhibited by the operation of an automatic fire suppression system.
Limitation
This standard applies only to a building which–
(a)is an enclosed shopping centre;
(b)is a residential care building;
F9(c). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
(d)forms the whole or part of a sheltered housing complex; F10...
(e)is a school building [F11, other than a building forming part of an existing school or an extension to a school building where it is not reasonably practicable to install an automatic fire suppression system in that building or extension].
[F12(f)is a building containing a flat or maisonette,
(g)is a social housing dwelling, or
(h)is a shared multi-occupancy residential building.]]
Textual Amendments
F8Sch. 5 para. 2.15 substituted (1.10.2010) by The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(e) (with reg. 3)
F9Words in Sch. 5 para. 2.15 omitted (1.3.2021) by virtue of The Building (Scotland) Amendment Regulations 2020 (S.S.I. 2020/275), regs. 1, 2(3)(a)
F10Word in Sch. 5 para. 2.15 omitted (1.3.2021) by virtue of The Building (Scotland) Amendment Regulations 2020 (S.S.I. 2020/275), regs. 1, 2(3)(b)
F11Words in Sch. 5 para. 2.15 inserted (1.10.2013) by The Building (Miscellaneous Amendments) (Scotland) Regulations 2013 (S.S.I. 2013/143), regs. 1, 2(2)(a) (with reg. 5)
F12Word in Sch. 5 para. 2.15 inserted (1.3.2021) by virtue of The Building (Scotland) Amendment Regulations 2020 (S.S.I. 2020/275), regs. 1, 2(3)(c)
3.1 Every building must be designed and constructed in such a way that there will not be a threat to the building or the health of people in or around the building due to the presence of harmful or dangerous substances.
This standard does not apply to the removal of unsuitable material, including turf, vegetable matter, wood, roots and topsoil on the site of a building (other than a dwelling) intended to have a life not exceeding the period specified in regulation 6.
3.2 Every building must be designed and constructed in such a way that there will not be a threat to the health of people in or around the building due to the emission and containment of radon gas.
3.3 Every building must be designed and constructed in such a way that there will not be a threat to the building or the health of the occupants as a result of flooding and the accumulation of ground water.
3.4 Every building must be designed and constructed in such a way that there will not be a threat to the building or the health of the occupants as a result of moisture penetration from the ground.
3.5 Every building must not be constructed over an existing drain (including a field drain) that is to remain active.
This standard does not apply where it is not reasonably practicable to re-route an existing drain.
3.6 Every building, and hard surface within the curtilage of a building, must be designed and constructed with a surface water drainage system that will–
(a)ensure the disposal of surface water without threatening the building and the health and safety of the people in and around the building; and
(b)have facilities for the separation and removal of silt, grit and pollutants.
3.7 Every wastewater drainage system serving a building must be designed and constructed in such a way as to ensure the removal of wastewater from the building without threatening the health and safety of the people in and around the building, and–
(a)that facilities for the separation and removal of oil, fat, grease and volatile substances from the system are provided;
(b)that discharge is to a public sewer or public wastewater treatment plant, where it is reasonably practicable to do so; and
(c)where discharge to a public sewer or public wastewater treatment plant is not reasonably practicable that discharge is to a private wastewater treatment plant or septic tank.
Standard 3.7(a) does not apply to a dwelling.
3.8 Every private wastewater treatment plant or septic tank serving a building must be designed and constructed in such a way that it will ensure the safe temporary storage and treatment of wastewater prior to discharge.
3.9 Every private wastewater treatment system serving a building must be designed and constructed in such a way that the disposal of the wastewater to ground is safe and is not a threat to the health of the people in or around the building.
3.10 Every building must be designed and constructed in such a way that there will not be a threat to the building or the health of the occupants as a result of moisture from precipitation penetrating to the inner face of the building.
This standard does not apply to a building where penetration of moisture from the outside will result in effects no more harmful than those likely to arise from use of the building.
3.11 Every building must be designed and constructed in such a way that–
(a)the size of any apartment or kitchen will ensure the welfare and convenience of all occupants and visitors; and
(b)an accessible space is provided to allow for the safe, convenient and sustainable drying of washing.
This standard applies only to a dwelling.
3.12 Every building must be designed and constructed in such a way that sanitary facilities are provided for all occupants of, and visitors to, the building in a form that allows convenience of use and that there is no threat to the health and safety of occupants or visitors.
3.13 Every building must be designed and constructed in such a way that it can be heated and maintain heat at temperature levels that will not be a threat to the health of the occupants.
This standard applies only to a dwelling.
3.14 Every building must be designed and constructed in such a way that ventilation is provided so that the air quality inside the building is not a threat to the building or the health of the occupants.]
Textual Amendments
F13Sch. 5 para. 3.14 substituted (1.10.2010) by The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(f) (with reg. 3)
3.15 Every building must be designed and constructed in such a way that there will not be a threat to the building or the health of the occupants as a result of moisture caused by surface or interstitial condensation.
F14...
Textual Amendments
F14Sch. 5 para. 3.15: limitation omitted (1.10.2010) by virtue of The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(g) (with reg. 3)
3.16 Every building must be designed and constructed in such a way that natural lighting is provided to ensure that the health of the occupants is not threatened.
This standard applies only to a dwelling.
3.17 Every building must be designed and constructed in such a way that each fixed combustion appliance installation operates safely.
3.18 Every building must be designed and constructed in such a way that any component part of each fixed combustion appliance installation used for the removal of combustion gases will withstand heat generated as a result of its operation without any structural change that would impair the stability or performance of the installation.
3.19 Every building must be designed and constructed in such a way that any component part of each fixed combustion appliance installation will not cause damage to the building in which it is installed by radiated, convected or conducted heat or from hot embers expelled from the appliance.
3.20 Every building must be designed and constructed in such a way that the products of combustion are carried safely to the external air without harm to the health of any person through leakage, spillage, or exhaust nor permit the re-entry of dangerous gases from the combustion process of fuels into the building.
3.21 Every building must be designed and constructed in such a way that each fixed combustion appliance installation receives air for combustion and operation of the chimney so that the health of persons within the building is not threatened by the build-up of dangerous gases as a result of incomplete combustion.
3.22 Every building must be designed and constructed in such a way that each fixed combustion appliance installation receives air for cooling so that the fixed combustion appliance installation will operate safely without threatening the health and safety of persons within the building.
3.23 Every building must be designed and constructed in such a way that–
(a)an oil storage installation, incorporating oil storage tanks used solely to serve a fixed combustion appliance installation providing space heating or cooking facilities in a building, will inhibit fire from spreading to the tank and its contents from within, or beyond, the boundary; or
(b)a container for the storage of woody biomass fuel will inhibit fire from spreading to its contents from within or beyond the boundary.
This standard does not apply to portable containers.
3.24 Every building must be designed and constructed in such a way that–
(a)an oil storage installation, incorporating oil storage tanks used solely to serve a fixed combustion appliance installation providing space heating or cooking facilities in a building, will–
(i)reduce the risk of oil escaping from the installation;
(ii)contain any oil spillage likely to contaminate any water supply, groundwater, watercourse, drain or sewer; and
(iii)permit any spill to be disposed of safely.
(b)it allows the number of journeys by delivery vehicles to be minimised due to the volume of woody biomass fuel storage.
This standard does not apply to portable containers.
3.25 Every building must be designed and constructed in such a way that accommodation for solid waste storage is provided which–
(a)permits access for storage and for the removal of its contents;
(b)does not threaten the health of people in and around the building; and
(c)does not contaminate any water supply, ground water or surface water.
This standard applies only to a [F15flat or maisonette].
Textual Amendments
F15Words in Sch. 5 para. 3.25 substituted (1.10.2013) by The Building (Miscellaneous Amendments) (Scotland) Regulations 2013 (S.S.I. 2013/143), regs. 1, 2(2)(b) (with reg. 5)
3.26 Every building must be designed and constructed in such a way that there will not be a threat to the health and safety of people from a dungstead and farm effluent tank.
3.27 Every building must be designed and constructed in such a way that sanitary facilities with water efficient fittings which are designed for the prevention of undue consumption of water are installed.
Textual Amendments
F16Sch. 5 para. 3.27 inserted (1.10.2013) by The Building (Miscellaneous Amendments) (Scotland) Regulations 2013 (S.S.I. 2013/143), regs. 1, 2(2)(c) (with reg. 5)
This standard applies only to dwellings.]
Textual Amendments
F16Sch. 5 para. 3.27 inserted (1.10.2013) by The Building (Miscellaneous Amendments) (Scotland) Regulations 2013 (S.S.I. 2013/143), regs. 1, 2(2)(c) (with reg. 5)
4.1 Every building must be designed and constructed in such a way that all occupants and visitors are provided with safe, convenient and unassisted means of access to the building.
There is no requirement to provide access for a wheelchair user to–
(a)a house, between either the point of access to or from any car parking within the curtilage of a building and an entrance to the house where it is not reasonably practicable to do so; or
(b)a common entrance of a domestic building not served by a lift, where there are no dwellings entered from a common area on the entrance storey.
4.2 Every building must be designed and constructed in such a way that–
(a)in non-domestic buildings, safe, unassisted and convenient means of access is provided throughout the building;
(b)in residential buildings, a proportion of the rooms intended to be used as bedrooms must be accessible to a wheelchair user;
(c)in domestic buildings, safe and convenient means of access is provided within common areas and to each dwelling;
(d)in dwellings, safe and convenient means of access is provided throughout the dwelling; and
(e)in dwellings, unassisted means of access is provided to, and throughout, at least one level.
There is no requirement to provide access suitable for a wheelchair user–
(a)in a non-domestic building not served by a lift, to a room, intended to be used as a bedroom, that is not on an entrance storey; or
(b)in a domestic building not served by a lift, within common areas and to each dwelling, other than on an entrance storey.
4.3 Every building must be designed and constructed in such a way that every level can be reached safely by stairs or ramps.
4.4 Every building must be designed and constructed in such a way that every sudden change of level that is accessible in, or around, the building is guarded by the provision of pedestrian protective barriers.
This standard does not apply where the provision of pedestrian protective barriers would obstruct the use of areas so guarded.
4.5 Every building must be designed and constructed in such a way that the electrical installation does not–
(a)threaten the health and safety of the people in, and around, the building; and
(b)become a source of fire.
This standard does not apply to an electrical installation–
(a)serving a building or any part of a building to which the Mines and Quarries Act 1954 F17 or the Factories Act 1961 F18 applies; or
(b)forming part of the works of an undertaker to which regulations for the supply and distribution of electricity made under the Electricity Act 1989 F19 apply.
Textual Amendments
F171954 c. 70, as extended by the Mines and Quarries (Tips) Act 1969 (c. 10), and the Mines Management Act 1971 (c. 20) and as amended by the Constitutional Reform Act 2005 (c. 4).
4.6 Every building must be designed and constructed in such a way that electric lighting points and socket outlets are provided to ensure the health, safety and convenience of occupants and visitors.
This standard applies only to domestic buildings where a supply of electricity is available.
4.7 Every building must be designed and constructed in such a way that it is provided with aids to assist those with a hearing impairment.
This standard does not apply to domestic buildings.
4.8 Every building must be designed and constructed in such a way that–
(a)people in and around the building are protected from injury that could result from fixed glazing, projections or moving elements on the building;
(b)fixed glazing in the building is not vulnerable to breakage where there is the possibility of impact by people in and around the building;
(c)both faces of a window and rooflight in a building are capable of being cleaned such that there will not be a threat to the cleaner from a fall resulting in severe injury;
(d)a safe and secure means of access is provided to a roof; and
(e)manual controls for ventilation and for electrical fixtures can be operated safely.
Standard 4.8(d) does not apply to domestic buildings.
4.9 Every building must be designed and constructed in such a way that protection is provided for people in, and around, the building from the danger of severe burns or scalds from the discharge of steam or hot water.
4.10 Every building, which contains fixed seating accommodation for an audience or spectators, must be designed and constructed in such a way that a number of level spaces for wheelchairs are provided proportionate to the potential audience or spectators.
This standard does not apply to domestic buildings.
4.11 Every building must be designed and constructed in such a way that each liquefied petroleum gas storage installation, used solely to serve a combustion appliance providing space heating, water heating, or cooking facilities, will–
(a)be protected from fire spreading to any liquefied petroleum gas container; and
(b)not permit the contents of any such container to form explosive gas pockets in the vicinity of any container.
This standard does not apply to a liquefied petroleum gas storage container, or containers, for use with portable appliances.
4.12 Every building accessible to vehicular traffic must be designed and constructed in such a way that every change in level is guarded.
4.13 Every building must be designed and constructed in such a way that doors and windows, vulnerable to unlawful entry, can be secured to deter housebreaking and protect the safety and welfare of occupants.
Textual Amendments
F20Sch. 5 para. 4.13 inserted (1.10.2010) by The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(h) (with reg. 3)
This standard applies only to domestic buildings.]
Textual Amendments
F20Sch. 5 para. 4.13 inserted (1.10.2010) by The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(h) (with reg. 3)
4.14. Every building and building unit must be designed and constructed in such a way that—
(a)a high-speed ready in-building physical infrastructure up to a network termination point for high-speed electronic communications network is provided; and
(b)in the case of a building which contains more than one building unit, a common access point for high-speed electronic communications networks is provided.
Textual Amendments
F21Sch. 5 para. 4.14 inserted (1.7.2016) by The Building (Scotland) Amendment Regulations 2016 (S.S.I. 2016/70), regs. 1, 2(2) (with reg. 2)
This standard does not apply to—
(a)alterations or extensions to buildings that do not include major renovation works; or
(b)buildings having an area not exceeding 30 square metres, ancillary to and within the curtilage of a dwelling.
Interpretation of this standard
In this standard—
“access point” means a physical point, located inside or outside the building, accessible to undertakings providing or authorised to provide public communications networks, where connection to the high-speed ready in-building physical infrastructure is made available;
“building unit” means a part of a building which is designed or altered to be used separately;
“high-speed electronic communications network” means an electronic communications network which is capable of delivering broadband access services at speeds of at least 30 Mbps;
“high-speed ready in-building physical infrastructure” means in-building physical infrastructure intended to host elements, or enable delivery, of high-speed electronic communications networks;
“in-building physical infrastructure” means physical infrastructure or installations at the end-user’s location, including elements under joint ownership, intended to host wired or wireless access networks, where such access networks are capable of delivering electronic communications services and connecting the building access point with the network termination point;
“major renovation works” means works at the end-user’s location encompassing structural modifications of the entire in-building physical infrastructure, or of a significant part of it; and
“network termination point” means a physical point located inside or outside the building at which an occupier is provided with access to high-speed electronic communications networks.]
Textual Amendments
F21Sch. 5 para. 4.14 inserted (1.7.2016) by The Building (Scotland) Amendment Regulations 2016 (S.S.I. 2016/70), regs. 1, 2(2) (with reg. 2)
5.1 Every building, which is divided into more than one area of different occupation, must be designed and constructed in such a way to limit the transmission of source noise from normal domestic type activities, between such areas, to a level that will not threaten the health of, or cause inconvenience to the building occupants.
Textual Amendments
F22Sch. 5 paras. 5.1, 5.2 substituted for sch. 5 para. 5.1 (1.10.2010) by The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(i) (with reg. 3)
This standard only applies to a building in different occupation incorporating—
(a)attached dwellings;
(b)attached residential buildings; or
(c)a roof, walkway or access deck located directly above an area that is either a dwelling or a residential building.
Textual Amendments
F22Sch. 5 paras. 5.1, 5.2 substituted for sch. 5 para. 5.1 (1.10.2010) by The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(i) (with reg. 3)
5.2 Every building must be designed and constructed in such a way to limit the transmission of source noise from normal domestic type activities, through a wall or floor, between a room and internal space where noise is likely to occur, to a level that will not cause inconvenience to the building occupants.
Textual Amendments
F22Sch. 5 paras. 5.1, 5.2 substituted for sch. 5 para. 5.1 (1.10.2010) by The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(i) (with reg. 3)
This standard only applies to a wall or floor forming an apartment in a dwelling and a room in a residential building which is capable of being used for sleeping; other than—
(a)a wall between an en-suite bathroom and the apartment or room it serves;
(b)a hospital; or
(c)a place of lawful detention.]
Textual Amendments
F22Sch. 5 paras. 5.1, 5.2 substituted for sch. 5 para. 5.1 (1.10.2010) by The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(i) (with reg. 3)
6.1 Every building must be designed and constructed in such a way that–
[F23(a)the energy performance is estimated in accordance with a methodology of calculation approved under regulation 7(a) of the Energy Performance of Buildings (Scotland) Regulations 2008 F24;] F25...
(b)the energy performance of the building is capable of reducing carbon dioxide emissions [F26; and
(c)it is a nearly zero-energy building].
Textual Amendments
F23Sch. 5 para. 6.1(a) substituted (1.10.2010) by The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(j)(i) (with reg. 3)
F25Word in sch. 5 para. 6.1.(a) omitted (with application in accordance with reg. 1(2) of the amending S.S.I.) by virtue of The Building (Energy Performance of Buildings) (Scotland) Amendment Regulations 2016 (S.S.I. 2016/71), regs. 1(3), 2(3)(a)
F26Sch. 5 para. 6.1.(c) and word inserted (with application in accordance with reg. 1(2) of the amending S.S.I.) by The Building (Energy Performance of Buildings) (Scotland) Amendment Regulations 2016 (S.S.I. 2016/71), regs. 1(3), 2(3)(b)
In this standard—
“energy from renewable sources” means energy from renewable non-fossil sources, namely wind, solar, aero-thermal, geothermal, hydrothermal and ocean energy, hydropower, biomass, landfill gas, sewage treatment plant gas and biogases; and
“nearly zero-energy building” means a building that has a very high energy performance, as determined in accordance with a methodology approved under regulation 7 of the Energy Performance of Buildings (Scotland) Regulations 2008 F28, where the nearly zero or very low amount of energy required should be covered to a very significant extent by energy from renewable sources, including energy from renewable sources produced on site or nearby.]
Textual Amendments
F27Words in sch. 5 para. 6.1 inserted (with application in accordance with reg. 1(2) of the amending S.S.I.) by The Building (Energy Performance of Buildings) (Scotland) Amendment Regulations 2016 (S.S.I. 2016/71), regs. 1(3), 2(3)(c)
F28S.S.I. 2008/309. Regulation 7 was substituted by S.S.I. 2012/315.
This standard does not apply to–
[F29(a)alterations and extensions to buildings other than—
(i)alterations and extensions to stand-alone buildings having an area less than 50 square metres that would increase the area to 50 square metres or more;
(ii)extensions to non-domestic buildings where the extension will have an area which is both greater than 100 square metres and greater than 25% of the area of the existing building; and
(iii)alterations to buildings involving the fit-out of the building shell which is the subject of a continuing requirement;]
(b)conversions of buildings;
(c)non-domestic buildings and buildings that are ancillary to a dwelling that are stand-alone having an area less than 50 square metres;
(d)buildings, which will not be heated or cooled other than by heating provided solely for the purpose of frost protection; or
(e)limited life buildings which have an intended life of less than 2 years.
Textual Amendments
F29Words in Sch. 5 para. 6.1 substituted (1.10.2015) by The Building (Scotland) Amendment Regulations 2014 (S.S.I. 2014/219), regs. 1, 2(2) (with reg. 3)
6.2 Every building must be designed and constructed in such a way that an insulation envelope is provided which reduces heat loss.
This standard does not apply to–
(a)non-domestic buildings which will not be heated, other than heating provided solely for the purposes of frost protection;
(b)communal parts of domestic buildings which will not be heated, other than heating provided solely for the purposes of frost protection; or
(c)buildings which are ancillary to dwellings, other than conservatories, which are either unheated or provided with heating which is solely for the purpose of frost protection.
6.3 Every building must be designed and constructed in such a way that the heating and hot water service systems installed are energy efficient and are capable of being controlled to achieve optimum energy efficiency.
This standard does not apply to–
(a)buildings which do not use fuel or power for controlling the temperature of the internal environment;
(b)heating provided solely for the purpose of frost protection; F30...
F30(c). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Textual Amendments
F30Words in Sch. 5 para. 6.3 omitted (1.10.2015) by virtue of The Building (Scotland) Amendment Regulations 2015 (S.S.I. 2015/218), regs. 1(3), 3(2) (with reg. 4)
6.4 Every building must be designed and constructed in such a way that temperature loss from heated pipes, ducts and vessels, and temperature gain to cooled pipes and ducts, is resisted.
This standard does not apply to–
(a)buildings which do not use fuel or power for heating or cooling either the internal environment or water services;
[F31(b)buildings, or parts of a building, which will not be heated, other than heating provided solely for the purpose of frost protection; or
(c)pipes, ducts or vessels that form part of an isolated industrial or commercial process.]
Textual Amendments
F31Words in Sch. 5 para. 6.4 substituted (1.10.2010) by The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(k) (with reg. 3)
6.5 Every building must be designed and constructed in such a way that the artificial or display lighting installed is energy efficient and is capable of being controlled to achieve optimum energy efficiency.
This standard does not apply to–
(a)process and emergency lighting components in a building; or
(b)alterations to a dwelling or a building ancillary to a dwelling.]
Textual Amendments
F32Sch. 5 para. 6.5: limitation substituted (1.10.2010) by The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(l) (with reg. 3)
6.6 Every building must be designed and constructed in such a way that–
(a)the form and fabric of the building minimises the use of mechanical ventilating or cooling systems for cooling purposes; and
(b)F33... the ventilating and cooling systems installed are energy efficient and are capable of being controlled to achieve optimum energy efficiency.
Textual Amendments
F33Words in sch. 5 para. 6.6(b) omitted (1.10.2010) by virtue of The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(m) (with reg. 3)
This standard does not apply to buildings which do not use fuel or power for ventilating or cooling the internal environment.
6.7 Every building must be designed and constructed in such a way that energy supply systems and building services which use fuel or power for heating, lighting, ventilating and cooling the internal environment and heating the water, are commissioned to achieve optimum energy efficiency.
This standard does not apply to–
(a)major power plants serving the National Grid;
(b)the process and emergency lighting components of a building;
(c)heating provided solely for the purpose of frost protection; or
(d)energy supply systems used solely for industrial and commercial processes, leisure use and emergency use within a building.
6.8 The occupiers of a building must be provided with written information by the owner–
(a)on the operation and maintenance of the building services and energy supply systems; and
(b)where any air conditioning system in the building is subject to regulation 17, stating a time based interval for inspection of the system.
This standard does not apply to–
(a)major power plants serving the National Grid;
(b)buildings which do not use fuel or power for heating, lighting, ventilating and cooling the internal environment and heating the water supply services;
(c)the process and emergency lighting components of a building;
(d)heating provided solely for the purpose of frost protection;
(e)lightingF34... systems in a domestic building; or
(f)energy supply systems used solely for industrial and commercial processes, leisure use and emergency use within a building.
Textual Amendments
F34Sch. 5 para. 6.8: words omitted (1.10.2010) by virtue of The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(n) (with reg. 3)
6.9 Every building must be designed and constructed in such a way that–
[F35(a) an energy performance certificate for the building is affixed to the building; and]
(c)the energy performance certificate is displayed in a prominent place within the building.
Textual Amendments
F35Sch. 5 para. 6.9(a) substituted for para. 6.9(a)(b) (4.1.2009) by The Building (Scotland) Amendment Regulations 2008 (S.S.I. 2008/310), regs. 1, 2(4)
(a)This standard does not apply to–
(i)buildings which do not use fuel or power for controlling the temperature of the internal environment;
(ii)non-domestic buildings and buildings that are ancillary to a dwelling that are stand-alone having an area less than 50 square metres;
[F36(iii)conversions, alterations and extensions to buildings other than—
(aa)alterations and extensions to stand-alone buildings having an area less than 50 square metres that would increase the area to 50 square metres or more; and
(bb)alterations to buildings involving the fit-out of the building shell which is the subject of a continuing requirement;]
(iv)limited life buildings which have an intended life of less than 2 years.
[F37(b)Standard 6.9(c) only applies to buildings—
(i)with a floor area of more than [F38250] square metres;
(ii)into which members of the public have an express or implied licence to enter; and
(iii)which are visited by members of the public on at least a weekly basis.]
Textual Amendments
F36Words in Sch. 5 para. 6.9 substituted (1.10.2015) by The Building (Scotland) Amendment Regulations 2014 (S.S.I. 2014/219), regs. 1, 2(3) (with reg. 3)
F37Words in Sch. 5 para. 6.9 substituted (9.1.2013) by The Building (Scotland) Amendment Regulations 2012 (S.S.I. 2012/209), regs. 1, 2(3)
F38Word in Sch. 5 para. 6.9 substituted (9.7.2015) by The Building (Scotland) Amendment Regulations 2015 (S.S.I. 2015/218), regs. 1(2), 2(2)
6.10 Every building must be designed and constructed in such a way that each [F39building, or] part of a building designed for different occupation is fitted with fuel [F40and power] meters.
Textual Amendments
F39Words in sch. 5 para. 6.10 inserted (1.10.2010) by The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(o)(i) (with reg. 3)
F40Words in sch. 5 para. 6.10 substituted (1.10.2010) by The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(o)(ii) (with reg. 3)
This standard does not apply to–
(a)communal areas of buildings in different occupation;
F41(b). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
(c)heating fired by solid fuel or biomass; or
(d)heating for individual dwellings fired by LPG or oil.
Textual Amendments
F41Words in Sch. 5 para. 6.10 omitted (1.10.2010) by virtue of The Building (Scotland) Amendment Regulations 2010 (S.S.I. 2010/32), regs. 1, 2(3)(o)(iii) (with reg. 3)
Textual Amendments
F42Sch. 5 Section 7 inserted (1.5.2011) by The Building (Scotland) Amendment Regulations 2011 (S.S.I. 2011/120), regs. 1, 2(4)
7.1 Every building must be designed and constructed in such a way that—
(a)with regard to a dwelling [F43or school building containing classrooms], a level of sustainability specified by the Scottish Ministers in respect of carbon dioxide emissions, resource use, building flexibility, adaptability and occupant well-being is achieved;
(b)with regard to a non-domestic building, [F44other than a school building containing classrooms,] a level of sustainability specified by the Scottish Ministers in respect of carbon dioxide emissions is achieved; and
(c)a statement of the level of sustainability achieved is affixed to the dwelling or non-domestic building.
Textual Amendments
F43Words in sch. 5 para. 7.1(a) inserted (1.10.2013) by The Building (Miscellaneous Amendments) (Scotland) Regulations 2013 (S.S.I. 2013/143), regs. 1, 2(2)(d)(i) (with reg. 5)
F44Words in sch. 5 para. 7.1(b) inserted (1.10.2013) by The Building (Miscellaneous Amendments) (Scotland) Regulations 2013 (S.S.I. 2013/143), regs. 1, 2(2)(d)(ii) (with reg. 5)
This standard does not apply to—
(a)alterations and extensions to buildingsF45...;
(b)conversions of buildings;
(c)buildings that are ancillary to a dwelling that are stand-alone having an area less than 50 square metres;
(d)buildings which will not be heated or cooled other than by heating provided solely for the purpose of frost protection;
(e)buildings intended to have a life not exceeding the period specified in regulation 6; or
(f)conservatories.]]
Textual Amendments
F45Words in Sch. 5 para. 7.1 omitted (1.10.2013) by virtue of The Building (Miscellaneous Amendments) (Scotland) Regulations 2013 (S.S.I. 2013/143), regs. 1, 2(2)(d)(iii) (with reg. 5)
Latest Available (revised):The latest available updated version of the legislation incorporating changes made by subsequent legislation and applied by our editorial team. Changes we have not yet applied to the text, can be found in the ‘Changes to Legislation’ area.
Original (As Enacted or Made): The original version of the legislation as it stood when it was enacted or made. No changes have been applied to the text.
Point in Time: This becomes available after navigating to view revised legislation as it stood at a certain point in time via Advanced Features > Show Timeline of Changes or via a point in time advanced search.
Geographical Extent: Indicates the geographical area that this provision applies to. For further information see ‘Frequently Asked Questions’.
Show Timeline of Changes: See how this legislation has or could change over time. Turning this feature on will show extra navigation options to go to these specific points in time. Return to the latest available version by using the controls above in the What Version box.
Access essential accompanying documents and information for this legislation item from this tab. Dependent on the legislation item being viewed this may include:
This timeline shows the different points in time where a change occurred. The dates will coincide with the earliest date on which the change (e.g an insertion, a repeal or a substitution) that was applied came into force. The first date in the timeline will usually be the earliest date when the provision came into force. In some cases the first date is 01/02/1991 (or for Northern Ireland legislation 01/01/2006). This date is our basedate. No versions before this date are available. For further information see the Editorial Practice Guide and Glossary under Help.
Use this menu to access essential accompanying documents and information for this legislation item. Dependent on the legislation item being viewed this may include:
Click 'View More' or select 'More Resources' tab for additional information including: