F1SCHEDULE 1BMEDIUM COMBUSTION PLANT DIRECTIVE

Annotations:

PART 1Permit conditions

Monitoring6

1

The operator of a medium combustion plant must—

a

where the plant is using more than one fuel type, monitor emissions—

i

while the fuel or fuel mix likely to result in the highest level of emissions is being fired, and

ii

during a period which is representative of normal operating conditions,

b

keep a record of, and process, all monitoring results in such a way as to enable verification of compliance with the applicable emission limit values,

c

keep a record of, or information proving, the effective continuous operation of secondary abatement equipment in use at the plant,

d

keep the following:—

i

the permit and, if relevant, variations and related information,

ii

the monitoring results and information referred to in sub-paragraphs (b) and (c),

iii

a record of the plant’s operating hours if applicable for the purposes of paragraph 1(3) or 2(2),

iii

a record of the type and quantities of fuel used in the plant,

iv

a record of any breakdown or malfunction of secondary abatement equipment,

v

a record of a breach of an emission limit value, and the measures taken by the operator to restore compliance,

e

keep the information referred to in head (d)(ii) to (v) for a period of at least 6 years.

2

The operator of a medium combustion plant must either—

a

measure emissions at least every three years; or

b

measure emissions continuously.

3

But where sub-paragraph (4) applies, the operator must measure emissions at the most frequent of—

a

after the elapse of three times the maximum permitted average annual operating hours,

b

every five years.

4

This paragraph applies to a medium combustion plant which is—

a

exempted from the requirements of paragraph 1(1) and (2) by paragraph 1(3), or

b

exempted from the requirements of paragraph 2(1) by paragraph 2(2).

5

The operator of a medium combustion plant is only required to measure emissions of—

a

pollutants for which an emission limit value is included in the operator’s permit by virtue of this schedule, and

b

carbon monoxide.

6

The operator of a medium combustion plant must take the first measurement of emissions by the later of the date falling 4 months after—

a

the grant of the permit,

b

the date of the start of operation of the plant.

7

As an alternative to the requirements of sub-paragraphs (2), (3) and (5)(a), the operator of a medium combustion plant may use other procedures which have been verified and approved by SEPA to determine SO2 emissions from the plant.

8

Where an operator is required to measure emissions continuously—

a

the measuring systems must be subject to checking by means of parallel measurements with the reference methods at least annually, and

b

the operator must provide the results of the check to SEPA.

9

Measurements must be taken when—

a

the plant is operating under stable conditions at a representative even load, and

b

the plant is not starting-up or shutting down.