Regulation 2(1) and (4)

SCHEDULE 1SPRESCRIBED CONCENTRATIONS AND VALUES

TABLE A

MICROBIOLOGICAL PARAMETERS

1 The parametric values in Part 2 are not required to protect human health (since the parametric values in Part 1 are sufficient for that purpose). The values in Part 2 are not therefore set for the purposes of Article 5(3) of the Directive.

2 Compliance required as to 95% of samples from each service reservoir (regulation 4(4)).

(1)Item(2)Parameter(3)Concentration orvalue (maximum)(4)Units ofmeasurement(5)Point ofcompliance
Part 1
1.Enterococci0Number/100mlConsumer's tap
2.Escherichia coli0Number/100mlConsumer's tap
Part 21
3.Coliform bacteria0Number/100mlService reservoir2
0Number/100mlTreatment works
4.Escherichia coli0Number/100mlService reservoir
0Number/100mlTreatment works
Notes—

[F1TABLE B

CHEMICAL PARAMETERS

(1)(2)(3)(4)(5)(6)
Notes—
Note 1: The parametric value of 0.10 μg/l refers to the residual monomer concentration in the water as calculated according to specifications of the maximum release from the corresponding polymer in contact with the water.
Note 2: A parametric value of 2.4 mgB/l must be applied when desalinated water is the predominant water source of the supply system concerned or in regions where geological conditions could lead to high levels of boron in groundwater.
Note 3: A parametric value of 0.70 mg/l must be applied where a disinfection method that generates this parameter, in particular chlorine dioxide, is used for disinfection of water intended for human consumption. This parametric value applies only if such disinfection methods are used.
Note 4: This parameter must be measured only when disinfection methods that can generate HAAs are used for the disinfection of water intended for human consumption.
Note 5: This parameter must be measured only in the event of potential blooms in source water (increasing cyanobacterial cell density or bloom forming potential).
Note 6: See also regulation 4(2)(c).
Note 7: The corresponding parametric value applies to each “other pesticide” individually.
Note 8: A parametric value of 30 μg/l must be applied for regions where geological conditions could lead to high levels of selenium in groundwater.
Note 9: The sum of concentrations of these two parameters.
Note 10: The parametric value of 0.50 μg/l refers to the residual monomer concentration in the water as calculated according to specifications of the maximum release from the corresponding polymer in contact with the water.]
ItemParameterConcentrat-ion or value (maximum)Units of measurementPoint of complianceNotes
Part 1
1.Acrylamide0.10μg/lConsumer’s tapNote 1
2.Antimony10μgSb/lConsumer’s tap
3.Arsenic10μgAs/lConsumer’s tap
4.Benzene1.0μg/lConsumer’s tap
5.Benzo(a)pyrene0.010μg/lConsumer’s tap
6.Bisphenol A2.5μg/lConsumer’s tap
7.Boron1.5mgB/lConsumer’s tapNote 2
8.Bromate10μgBrO3/lConsumer’s tap
9.Cadmium5.0μgCd/lConsumer’s tap
10.Chlorate0.25mg/lConsumer’s tapNote 3
11.Chlorite0.25mg/lConsumer’s tapNote 3
12.Chromium50μgCr/lConsumer’s tap
13.Copper2.0mgCu/lConsumer’s tap
14.Cyanide50μgCN/lConsumer’s tap
15.1,2-dichloroethane3.0μg/lConsumer’s tap
16.Epichlorohydrin0.10μg/lConsumer’s tapNote 1
17.Fluoride1.5mgF/lConsumer’s tap
18.HAAs60μg/lConsumer’s tapNote 4
19.Lead10μgPb/lConsumer’s tap
20.Mercury1.0μgHg/lConsumer’s tap
21.Microcystin-LR1.0μg/lConsumer’s tapNote 5
22.Nickel20μgNi/lConsumer’s tap
23.Nitrate50mgNO3/lConsumer’s tapNote 6
24.Nitrite0.50mgNO2/lConsumer’s tapNote 6
0.10mgNO2/lTreatment works
25.Pesticides—
Aldrin0.030μg/lConsumer’s tap
Dieldrin0.030μg/lConsumer’s tap
Heptachlor0.030μg/lConsumer’s tap
Heptachlor epoxide0.030μg/lConsumers’ tap
Other pesticide0.10μg/lConsumer’s tapNote 7
26.Pesticides: total0.50μg/lConsumer’s tap
27.Sum of PFAS0.1μg/lConsumer’s tap
28.PAH Total0.10μg/lConsumer’s tap
29.Selenium20μgSe/lConsumer’s tapNote 8
30.Tetrachloroethene and trichloroethene10μg/lConsumer’s tapNote 9
31.THM: Total100μg/lConsumer’s tap
32.Uranium30μg/lConsumer’s tap
33.Vinyl chloride0.50μg/lNote 10
Part 2
34.Aluminium200μgAl/lConsumer’s tap
35.Colour20mg/1 Pt/CoConsumer’s tap
36.Iron200μgFe/lConsumer’s tap
37.Manganese50μgMn/lConsumer’s tap
38.Sodium200mgNa/1Consumer’s tap
39.Tetrachlorometh-ane3μg/lConsumer’s tap
40.Turbidity4NTUConsumer’s tap

[F2TABLE C

Indicator Parameters

(1)(2)(3)(4)(5)(6)
Notes—
Note 1: Water must not be aggressive or corrosive. This applies particularly to water undergoing treatment (demineralisation, softening, membrane treatment, reverse osmosis, etc.).
Note 2: Where water intended for human consumption is derived from treatment that significantly demineralises or softens water, calcium and magnesium salts could be added to condition the water in order to reduce any possible negative health impact, as well as to reduce the corrosiveness or aggressivity of water and to improve taste. Minimum concentrations of calcium and magnesium or total dissolved solids in softened or demineralised water could be established taking into account the characteristics of water that enters those processes.
Note 3: The water must not be corrosive.
Note 4: This parameter must be measured if a risk assessment under regulation 30(2) indicates that it is appropriate to do so.
Note 5: For water put into bottles or containers (which is not intended for sale for drinking by humans), the unit is number/250ml.
Note 6: The water must not be aggressive.
Note 7: For water put into bottles or containers (which is not intended for sale for drinking by humans), the minimum value is 4.5 pH units.
Note 8: This parameter need not be measured for supplies of less than 10,000 m³ a day.
Note 9: Remedial action is to be deemed justified on radiological protection grounds, without further consideration where radon concentrations exceed 1,000 Bq/l.
Note 10: If the concentration of tritium exceeds this value, an analysis of the presence of other artificial radionuclides must also be carried out by Scottish Water.]
ItemParameterConcentration or value (maximum) or stateUnits of measurementPoint of monitoringNotes
Part 1
1.Ammonium0.50mgNH4/1Consumer’s tap
2.Chloride250mgCl/1Supply pointNote 3
3. Clostridium perfringens (including spores)0Number/100mlSupply pointNote 4
4.Coliform bacteria0Number/100mlConsumer’s tapNote 5
5.Colony countNo abnormal changeNumber/1ml at 22°CConsumer’s tap, service reservoir and treatment works
6.ColourAcceptable to consumers and no abnormal changeConsumer’s tap
7.Conductivity2500μS/cm at 20°CSupply pointNote 6
8.Hydrogen ion9.5pH valueConsumer’s tapNotes 6 and 7
6.5 (minimum)
9.OdourAcceptable to consumers and no abnormal changeConsumer’s tap
10.Sulphate250mgSO4/lSupply pointNote 3
11.TasteAcceptable to consumers and no abnormal changeConsumer’s tap
12.Total organic carbonNo abnormal changemgC/1Supply pointNote 8
13.Turbidity1NTUTreatment works
Part 2
14.Indicative dose0.10mSvSupply point
15.Radon100Bq/lSupply pointNote 9
16.Tritium100Bq/lSupply pointNote 10

In this Schedule—

F3...

[F4HAAs” means the sum of the following haloacetic acides: monochloro-, dichloro-, and trichloro-acetic acid, and mono- and dibromo-acetic acid,]

NTU” means Nephelometric Turbidity Unit;

PAH: Total” means the sum of the concentrations of the following polyaromatic hydrocarbons: benzo(b)fluoranthene, benzo(k)fluoranthene, benzo(ghi)perylene and indeno(1,2,3-cd)pyrene;

Pesticide” means an organic insecticide, herbicide, fungicide, nematocide, acaricide, algicide, rodenticide, slimicide, F5... or related product (including a growth regulator), and includes [F6their metabolites as defined in point (32) of Article 3 of Regulation (EC) No 1107/2009 of the European Parliament and of the Council that are relevant metabolites];

Pesticides: Total” refers to the sum of the concentrations of each pesticide detected and quantified in the monitoring procedure;

[F7relevant metabolite” means a pesticide metabolite that has intrinsic properties comparable to those of the parent substance in terms of its pesticide target activity or that either itself or its transformation products generate a health risk for consumers,

Sum of PFAS” means the sum of the following perfluoroalkyl substances considered a concern as regards water intended for human consumption—

  • Perfluorobutanoic acid,

  • Perfluoropentanoic acid,

  • Perfluorohexanoic acid,

  • Perfluoroheptanoic acid,

  • Perfluorooctanoic acid,

  • Perfluorononanoic acid,

  • Perfluorodecanoic acid,

  • Perfluoroundecanoic acid,

  • Perfluorododecanoic acid,

  • Perfluorotridecanoic acid,

  • Perfluorobutane sulfonic acid,

  • Perfluoropentane sulfonic acid,

  • Perfluorohexane sulfonic acid,

  • Perfluoroheptane sulfonic acid,

  • Perfluorooctane sulfonic acid,

  • Perfluorononane sulfonic acid,

  • Perfluorodecane sulfonic acid,

  • Perfluoroundecane sulfonic acid,

  • Perfluorododecane sulfonic acid,

  • Perfluorotridecane sulfonic acid,]

Tetrachloroethene and Trichloroethene” means the sum of the concentrations of tetrachloroethene and trichloroethene; and

THM: Total” means the sum of the concentrations of the following trihalomethanes: chloroform, bromoform, dibromochloromethane and bromodichloromethane.