xmlns:atom="http://www.w3.org/2005/Atom"

Regulation 2

SCHEDULEAMENDMENTS OF MERCHANT SHIPPING (FIRE APPLIANCES) REGULATIONS 1980

Regulation 1

1.—(1) In paragraph (2) of regulation (1)—

(a)after the definition of “Accommodation space” there shall be inserted the following definition—

“Approved” means approved by the Secretary of State;;

(b)after the definition of “Cargo spaces” there shall be inserted the following definitions—

“Chemical tanker” means a tanker constructed or adapted and used for the carriage in bulk of any liquid product of a flammable nature listed in Chapter VI of the I.M.C.O. Code for the Construction and Equipment of Ships Carrying Dangerous Chemicals in Bulk;

“Code for the Construction and Equipment of Ships Carrying Liquefied Gases in Bulk” means the code so entitled adopted by the International Maritime Organization by Resolution A.328(IX);;

(c)after the definition of “Fishing vessel” there shall be inserted the following definition—

“Gas carrier” means a tanker constructed or adapted and used for the carriage in bulk of any liquefied gas or other substance of a flammable nature listed in Chapter XIX of the Code for the Construction and Equipment of Ships Carrying Liquefied Gases in Bulk;;

(d)after the definition of “Reid vapour pressure” there shall be inserted the following definition—

(2) After paragraph (2) of regulation 1 there shall be inserted the following paragraph—

(2A) Any reference in these Regulations to any of the following—

(a)the Guidelines for Inert Gas Systems;

(b)a British Standard;

(c)the I.M.C.O. Code for the Construction and Equipment of Ships Carrying Dangerous Chemicals in Bulk;

(d)the Code for the Construction and Equipment of Ships Carrying Liquefied Gases in Bulk;

shall inmclude—

(i)a reference to any document amending that publication which is considered by the Secretary of State to be relevant from time to time and is specified in a Merchant Shipping Notice; and

(ii)as respects a reference to a British Standard, a reference to a relevant standard of a member State other than the United Kingdom..

(3) After paragraph (3) of regulation 1 there shall be inserted the following paragraph—

(4) An approval given in pursuance of these Regulations shall be given in writing and shall specify the date on which it takes effect and the conditions (if any) on which it is given.(1).

Regulation 10A

2.  After regulation 10 there shall be inserted the following regulation—

Paint lockers etc

10A.  In every ship of Class I, every paint locker and flammable liquid locker shall be protected by an approved fire–extinguishing system..

Regulation 33

3.  In paragraph (3) of regulation 33, for the words from “unseasoned timber” to the end there shall be substituted the words “unseasoned timber or non–combustible cargoes or of cargoes which, in the opinion of the Secretary of State, constitute a low fire risk.”.

Regulation 37A

4.  After regulation 37 there shall be inserted the following regulation—

Paint lockers etc

37A.  In every ship of Class VII of 500 tons or over, every paint locker and flammable liquid locker shall be protected by an approved fire–extinguishing system..

Regulation 44

5.  In the first sentence of regulation 44, the words from “having a valid Certificate” to the end of the sentence shall be omitted.

Regulation 46

6.—(1) At the beginning of regulation 46, there shall be inserted “(1) Subject to paragraph (1A) below”.

(2) In paragraph (1) of regulation 46 the words from “except that this requirement shall not apply” to the end shall be omitted.

(3) After the said paragraph (1) there shall be inserted the following paragraph—

(1A) A tanker referred to in paragraph (1) above need not be provided with an inert gas system complying with the requirements of regulation 51 if—

(a)being a chemical tanker carrying as cargo any substance mentioned in the said paragraph (1), it is provided with an inert gas system complying with the requirements of regulation 51A;

(b)being a chemical tanker carrying crude oil or petroleum products, it is provided with an inert gas system complying with the requirements of regulation 51B;

(c)being a gas carrier carrying as cargo a substance mentioned in the said paragraph (1), it is provided with cargo tank inerting arrangements equivalent to those specified in sub–paragraph (a) or (b) above;

(d)being a chemical tanker or gas carrier, it is carrying a flammable cargo other than crude oil or petroleum products.

In sub–paragraph (d) above, the reference to a flammable cargo other than crude oil or petroleum products includes (without prejudice to the generality of that reference) a reference to any of the cargoes listed in Chapters VI and VII of the I.M.C.O. Code for the Construction and Equipment of Ships Carrying Dangerous Chemicals in Bulk..

Regulation 51

7.—(1) For the heading to regulation 51 there shall be substituted the following heading—

Inert gas systems: Standard requirements.

(2) In paragraph (1) of regulation 51, after the words “in accordance with” there shall be inserted the words “regulation 46(1) or 47(a) of”.

Regulations 51A and 51B

8.  After regulation 51 there shall be inserted the following regulations—

Inert gas systems: Alternative requirements for chemical tankers

51A.(1) (a) Every inert gas system fitted in accordance with regulation 46(1A)(a) of these Regulations shall be designed, constructed and tested to the satisfaction of the Secretary of State and shall comply with the following requirements of this regulation.

(b)In this regulation a reference to a cargo tank includes a reference to a slop tank containing cargo residues.

(2) The system shall be capable of:

(a)inerting empty cargo tanks by reducing the oxygen content of the atmosphere in each tank to a level at which combustion cannot be supported;

(b)maintaining the atmosphere, in all parts of each cargo tank designated to carry flammable products requiring protection by an inert gas system, with an oxygen content not exceeding 8 per cent by volume and at a positive pressure at all times in port and at sea except when it is necessary for such a tank to be gas–free;

(c)eliminating the need for air to enter a tank during normal operations except when it is necessary for such a tank to be gas–free;

(d)purging empty cargo tanks of flammable vapour, so that subsequent gas–freeing operations will at no time create a flammable atmosphere within the tanks.

(3) (a) The system shall be capable of delivering inert gas to the cargo tanks at a rate of at least 125 per cent of the maximum rate of discharge capacity of the ship expressed as a volume. The Secretary of State may accept an inert gas system having a lower delivery capacity provided that the maximum rate of discharge of cargoes from cargo tanks being protected by the system is restricted to 80 per cent of the inert gas capacity.

(b)The system shall be capable of delivering inert gas with an oxygen content of not more than 5 per cent by volume in the inert gas supply main to the cargo tanks at any required rate of flow.

(4) (a) Suitable fuel in sufficient quantity shall be provided for the inert gas generators.

(b)The inert gas generators shall be located outside the cargo tank area as defined in the I.M.C.O. Code for the Construction and Equipment of Ships Carrying Dangerous Chemicals in Bulk. Spaces containing inert gas generators shall have no direct access to accommodation, service or control station spaces, but may be located in machinery spaces. If they are not located in machinery spaces, they shall be located in a compartment reserved solely for their use. Such a compartment shall be separated by a gastight steel bulkhead or deck from accommodation, service and control station spaces. Adequate positive–pressure–type mechanical ventilation shall be provided for such a compartment. Access to such compartments located aft shall be only from an open deck outside the cargo tank area. Access shall be located on the end bulkhead not facing the cargo area or on the outboard side of the superstructure or deckhouse at a distance of at least 25 per cent of the length of the ship but not less than 5 metres from the end of the superstructure or deckhouse facing the cargo area. In the case of such a compartment being located in the forecastle, access shall be through the deckhead forward of the cargo area.

(c)Inert gas piping systems shall not pass through accommodation, service and control station spaces.

(5) (a) Means shall be provided which will effectively cool the volume of gas specified by paragraph (3) of this regulation and remove solids and sulphur combustion products. The cooling water arrangements shall be such that an adequate supply of water will always be available without interfering with any essential services on the ship. Provision shall also be made for an alternative supply of cooling water.

(b)Filters or equivalent devices shall be fitted to minimise the amount of water carried over to the inert gas main.

(6) (a) Two air blowers shall be fitted to each inert gas generator, which together shall be capable of delivering to the cargo tanks required to be protected by the system at least the volume of gas required by paragraph (3) of this regulation. The Secretary of State may permit only one blower if it is capable of delivering to the protected cargo tanks the total volume of gas required by paragraph (3) of this regulation, provided that sufficient spares for the air blower and its prime mover are carried on board to enable any failure of the air blower and its prime mover to be rectified.

(b)The inert gas system shall be so designed that the maximum pressure which it can exert on any cargo tank will not exceed the test pressure of that tank.

(c)Where more than one inert gas generator is provided, suitable shut–off arrangements shall be provided on the discharge outlet of each generator plant.

(d)Arrangements shall be made to vent the inert gas to the atmosphere in case the inert gas produced is sub–standard, eg during starting–up or in case of equipment failure.

(e)Where inert gas generators are served by positive displacement blowers, a pressure relief device shall be provided to prevent excess pressure being developed on the discharge of the blower.

(7) Two fuel oil pumps shall be fitted to each inert gas generator. The Secretary of State may permit only one fuel oil pump on condition that sufficient spares for the fuel oil pump and its prime mover are carried on board to enable any failure of the fuel oil pump and its prime mover to be rectified by the ship’s crew.

(8) A gas–regulating valve shall be fitted in the inert gas supply main. This valve shall be automatically controlled to close as required by paragraph (17)(b) and (c) of this regulation. It shall also be capable of automatically regulating the flow of inert gas to the cargo tanks unless other means are provided to control automatically the inert gas flow rate.

(9) (a) At least two non–return devices, one of which shall be a water seal, shall be fitted in the inert gas supply main in order to prevent the return of flammable vapour to the inert gas generator and to any gas–safe space under all normal conditions of trim, list and motion of the ship. They shall be located between the automatic valve required by paragraph (8) of this regulation and the first connection to any cargo tank or cargo pipeline. The Secretary of State may permit an alternative arrangement or device providing a measure of safety equivalent to that of a water seal.

(b)The devices referred to in sub–paragraph (a) of this paragraph shall be located in the cargo tank area on deck.

(c)The water seal referred to in sub–paragraph (a) of this paragraph shall be capable of being supplied by two separate pumps, each of which shall be capable of maintaining an adequate supply at all times.

(d)The arrangement of the water seal and its associated provisions shall be such that it will prevent backflow of flammable vapours and will ensure the proper functioning of the water seal under operating conditions.

(e)Provision shall be made to ensure that any water seal is protected against freezing, in such a way that the integrity of the water seal is not impaired by overheating.

(f)A water loop or other approved arrangement shall also be fitted to all associated water supply and drain piping and to all venting or pressure–sensing piping leading to gas–safe spaces. Means shall be provided to prevent such loops from being emptied by vacuum.

(g)Any water seal or equivalent device and all loop arrangements shall be capable of preventing the return of flammable vapours to an inert gas generator at a pressure equal to the test pressure of the cargo tanks.

(h)The second device shall be a non–return valve or equivalent capable of preventing the return of vapours or liquids or both and fitted between the water seal or the equivalent device required by sub–paragraph (a) of this paragraph and the first connection from the inert gas main to a cargo tank. It shall be provided with positive means of closure. As an alternative to positive means of closure, an additional valve having such means of closure may be provided between the non– return valve and the first connection to the cargo tanks to isolate the water seal or equivalent device.

(i)As an additional safeguard against the possible leakage of flammable liquids or vapours back from the deck main, means shall be provided to permit the section of the line between the valve having positive means of closure referred to in sub– paragraph (h) of this paragraph and the valve referred to in paragraph (8) of this regulation to be vented in a safe manner when the first of these valves is closed.

(10) (a) The inert gas main may be divided into two or more branches between the non– return devices required by paragraph (9) of this regulation and the cargo tanks.

(b)Inert gas supply mains shall be fitted with branch piping leading to each cargo tank designated for the carriage of flammable products required to be inerted by this regulation. Each cargo tank containing or loading products not required to be inerted shall be separated from the inert gas main by:

(i)removing spool pieces, valves or other pipe sections, and blanking the pipe ends; or

(ii)an arrangement of two spectacle flanges in series with provision for detecting leakage into the pipe between the two spectacle flanges.

(c)Means shall be provided to protect cargo tanks against the effect of overpressure or vacuum caused by thermal variations when the tanks are isolated from the inert gas mains.

(d)Piping systems shall be so designed as to prevent the accumulation of cargo or water in the pipelines under all normal conditions.

(e)Suitable arrangements shall be provided to enable the inert gas main to be connected to an external supply of inert gas.

(11) Unless the arrangements for venting of all vapours displaced from the cargo tanks during loading and ballasting comply with the requirements of the I.M.C.O. Code for the Construction and Equipment of Ships Carrying Dangerous Chemicals in Bulk for controlled venting, such arrangements shall comply with regulation 12 of the Merchant Shipping (Cargo Ship Construction and Survey) Regulations 1984(2) and shall consist either of one or more mast risers or of a number of high velocity vents.

(12) The arrangements for inerting, purging or gas–freeing of empty tanks as required by paragraph (2) of this regulation shall be to the satisfaction of the Secretary of State and shall be such that the accumulation of hydrocarbon vapours in pockets formed by the internal structural members in a tank is minimised and that:

(a)on individual cargo tanks the gas outlet pipe, if fitted, shall be positioned as far as practicable from the inert gas/air inlet and in accordance with regulation 12(5)(c) of the Merchant Shipping (Cargo Ship Construction and Survey) Regulations 1984. The inlet of such outlet pipes may be located either at deck level or at not more than 1 metre above the bottom of the tank;

(b)the cross–sectional area of such gas outlet pipe referred to in sub–paragraph (a) of this paragraph shall be such that an exit velocity of at least 20 metres per second can be maintained when any three tanks are being simultaneously supplied with inert gas. Their outlets shall extend not less than 2 metres above deck level. When in accordance with paragraph (3) of this regulation the Secretary of State permits a system designed to supply only one tank or two tanks simultaneously, the outlet pipes shall be sized such that an exit velocity in the outlet pipes of 20 metres per second can be maintained;

(c)each gas outlet referred to in sub–paragraph (b) of this paragraph shall be fitted with suitable blanking arrangements.

(13) Means shall be provided for continuously indicating the temperature and pressure of the inert gas at the discharge side of the system, whenever it is operating.

(14) (a) Instrumentation shall be fitted for continuously indicating and permanently recording, when the inert gas is being supplied:

(i)the pressure of the inert gas supply mains between the non–return devices required by paragraph (9)(a) of this regulation and the cargo tanks; and

(ii)the oxygen content of the inert gas in the inert gas supply main.

(b)The devices referred to in sub–paragraph (a) of this paragraph shall be placed in the cargo control room where provided. Where no cargo control room is provided, they shall be placed in a position easily accessible to the officer in charge of cargo operations.

(c)In addition, meters shall be fitted:

(i)in the navigating bridge to indicate at all times the pressure referred to in sub– paragraph (a)(i) of this paragraph; and

(ii)in the machinery control room or in the machinery space to indicate the oxygen content referred to in sub–paragraph (a)(ii) of this paragraph.

(15) Portable instruments for measuring oxygen and flammable vapour concentration shall be provided. In addition, suitable arrangements shall be made on each cargo tank such that the condition of the tank atmosphere can be determined using these portable instruments.

(16) Suitable means shall be provided for the zero and span calibration of both fixed and portable gas concentration measurement instruments, referred to in paragraphs (14) and (15) of this regulation.

(17) (a) Audible and visual alarms shall be provided to indicate:

(i)low water pressure or low water flow rate to the cooling and scrubbing arrangements referred to in paragraph (5)(a) of this regulation;

(ii)low fuel supply;

(iii)high gas temperature referred to in paragraph (13) of this regulation;

(iv)failure of the power supply to the inert gas generators;

(v)oxygen content in excess of 8 per cent by volume referred to in paragraph (14)(a)(ii) of this regulation;

(vi)failure of the power supply to the indicating devices referred to in paragraph (14)(a) of this regulation and to the automatic control systems for the gas– regulating valve referred to in paragraph (8) of this regulation and the inert gas generator;

(vii)low water level in the water seal referred to in paragraph (9) of this regulation;

(viii)gas pressure less than 100 millimetres water gauge referred to in paragraph (14)(a) of this regulation;

(ix)high gas pressure referred to in paragraph (14)(a)(i) of this regulation.

(b)Automatic shutdown of the gas–regulating valve and of the fuel oil supply to the inert gas generator shall be arranged on predetermined limits being reached in respect of sub–paragraph (a)(i) and (iii) of this paragraph.

(c)Automatic shutdown of the gas–regulating valve shall be arranged in respect of sub– paragraph (a)(iv) of this paragraph.

(d)In respect of sub–paragraph (a)(v) of this paragraph, when the oxygen content of the inert gas exceeds 8 per cent by volume, immediate action shall be taken to improve the gas quality. Unless the quality of the inert gas improves, all operations in those tanks to which inert gas is being supplied shall be suspended so as to avoid air being drawn into the tanks. The deck isolation valve referred to in paragraph (9)(h) of this regulation shall be closed, and the sub–standard gas shall be vented to atmosphere.

(e)The alarms required by sub–paragraph (a)(v), (vi) and (viii) of this paragraph shall be fitted in the machinery space and cargo control room, where provided, but in each case in such a position that they are immediately received by responsible members of the crew. All other alarms required by this paragraph shall be audible to responsible members of the crew either as individual alarms or as a group alarm.

(f)In respect of sub–paragraph (a)(vii) of this paragraph, the Secretary of State shall be satisfied as to the maintenance of an adequate reserve of water at all times and the integrity of the arrangements to permit the automatic formation of the water seal when the gas flow ceases. The audible and visual alarm on the low level of water in the water seal shall operate when the inert gas is not being supplied.

(g)An audible alarm system, independent of that required by sub–paragraph (a)(viii) of this paragraph, or automatic shutdown of cargo pumps shall be provided to operate on pre–determined limits of low pressure in the inert gas mains being reached.

(18) Detailed instruction manuals shall be provided on board, covering the operations, safety and maintenance requirements and occupational health hazards relevant to the inert gas system and its application to the cargo tank system. The manuals shall include guidance on procedures to be followed in the event of a fault or failure of the inert gas system.

Inert gas systems: Alternative requirements for chemical tankers carrying crude oil or petroleum products

51B.(1) (a) Every inert gas system fitted in accordance with regulation 46(1A)(b) of these Regulations shall be designed, constructed and tested to the satisfaction of the Secretary of State and shall comply with the following requirements of this regulation.

(b)In this regulation a reference to a cargo tank includes a reference to a slop tank containing oil residues.

(2) The system shall be capable of:

(a)inerting empty cargo tanks by reducing the oxygen content of the atmosphere in each tank to a level at which combustion cannot be supported;

(b)maintaining the atmosphere in all parts of each cargo tank designated to carry flammable products requiring protection by an inert gas system with an oxygen content not exceeding 8 per cent by volume and at a positive pressure at all times in port and at sea except when it is necessary for such a tank to be gas–free;

(c)eliminating the need for air to enter a tank during normal operations except when it is necessary for such a tank to be gas–free;

(d)purging empty cargo tanks of flammable vapour, so that subsequent gas–freeing operations will at no time create a flammable atmosphere within the tank.

(3) (a) The system shall be capable of delivering inert gas to the cargo tanks at a rate of at least 125 per cent of the maximum rate of discharge capacity of the ship expressed as a volume. The Secretary of State may accept an inert gas system having a lower delivery capacity provided that the maximum rate of discharge of cargoes from cargo tanks being protected by the system is restricted to 80 per cent of the inert gas capacity.

(b)The system shall be capable of delivering inert gas with an oxygen content of not more than 5 per cent by volume in the inert gas supply main to the cargo tanks at any required rate of flow.

(4) (a) Suitable fuel in sufficient quantity shall be provided for the inert gas generators.

(b)The inert gas generators shall be located outside the cargo tank area as defined in the I.M.C.O. Code for the Construction and Equipment of Ships Carrying Dangerous Chemicals in Bulk. Spaces containing inert gas generators shall have no direct access to accommodation, service or control station spaces, but may be located in machinery spaces. If they are not located in machinery spaces they shall be located in a compartment reserved solely for their use. Such a compartment shall be separated by a gastight steel bulkhead or deck from accommodation, service and control station spaces. Adequate positive–pressure–type mechanical ventilation shall be provided for such a compartment. Access to such compartments located aft shall be only from an open deck outside the cargo tank area. Access shall be located on the end bulkhead not facing the cargo area or on the outboard side of the superstructure or deckhouse at a distance of at least 25 per cent of the length of the ship but not less than 5 metres from the end of the superstructure or deckhouse facing the cargo area. In the case of such a compartment being located in the forecastle, access shall be through the deckhead forward of the cargo area.

(c)Inert gas piping systems shall not pass through accommodation, service and control station spaces.

(5) (a) Means shall be provided which will effectively cool the volume of gas specified by paragraph (3) of this regulation and remove solids and sulphur combustion products. The cooling water arrangements shall be such that an adequate supply of water will always be available without interfering with any essential services on the ship. Provision shall also be made for an alternative supply of cooling water.

(b)Filters or equivalent devices shall be fitted to minimise the amount of water carried over to the inert gas main.

(6) (a) Two air blowers shall be fitted to each inert gas generator, which together shall be capable of delivering to the cargo tanks required to be protected by the system at least the volume of gas required by paragraph (3) of this regulation. The Secretary of State may permit only one blower if it is capable of delivering to the protected cargo tanks the total volume of gas required by paragraph (3) of this regulation, provided that sufficient spares for the air blower and its prime mover are carried on board to enable any failure of the air blower and its prime mover to be rectified.

(b)The inert gas system shall be so designed that the maximum pressure which it can exert on any cargo tank will not exceed the test pressure of that tank.

(c)Where more than one inert gas generator is provided, suitable shut–off arrangements shall be provided on the discharge outlet of each generator plant.

(d)Arrangements shall be made to vent the inert gas to the atmosphere in case the inert gas produced is sub–standard, eg during starting–up or in case of equipment failure.

(e)Where inert gas generators are served by positive displacement blowers, a pressure relief device shall be provided to prevent excess pressure being developed on the discharge side of the blower.

(7) Two fuel oil pumps shall be fitted to each inert gas generator. The Secretary of State may permit only one fuel oil pump on condition that sufficient spares for the fuel oil pump and its prime mover are carried on board to enable any failure of the fuel oil pump and its prime mover to be rectified by the ship’s crew.

(8) A gas–regulating valve shall be fitted in the inert gas supply main. This valve shall be automatically controlled to close as required by paragraph (17)(b) and (c) of this regulation. It shall also be capable of automatically regulating the flow of inert gas to the cargo tanks unless other means are provided to control automatically the inert gas flow rate.

(9) (a) At least two non–return devices, one of which shall be a water seal, shall be fitted in the inert gas supply main in order to prevent the return of flammable vapour to the inert gas generator and to any gas–safe space under all normal conditions of trim, list and motion of the ship. They shall be located between the automatic valve required by paragraph (8) of this regulation and the first connection to any cargo tank or cargo pipeline. The Secretary of State may permit an alternative arrangement or device providing a measure of safety equivalent to that of a water seal.

(b)The devices referred to in sub–paragraph (a) of this paragraph shall be located in the cargo tank area on deck.

(c)The water seal referred to in sub–paragraph (a) of this paragraph shall be capable of being supplied by two separate pumps, each of which shall be capable of maintaining an adequate supply at all times.

(d)The arrangement of the water seal and its associated provisions shall be such that it will prevent backflow of flammable vapours and will ensure the proper functioning of the water seal under operating conditions.

(e)Provision shall be made to ensure that any water seal is protected against freezing, in such a way that the integrity of the water seal is not impaired by overheating.

(f)A water loop or other approved arrangement shall also be fitted to all associated water supply and drain piping and to all venting or pressure–sensing piping leading to gas–safe spaces. Means shall be provided to prevent such loops from being emptied by vacuum.

(g)Any water seal or equivalent device and all loop arrangements shall be capable of preventing the return of flammable vapours to an inert gas generator at a pressure equal to the test pressure of the cargo tanks.

(h)The second device shall be a non–return valve or equivalent capable of preventing the return of vapours or liquids or both and fitted between the water seal or the equivalent device required by sub–paragraph (a) of this paragraph and the first connection from the inert gas main to a cargo tank. It shall be provided with positive means of closure. As an alternative to positive means of closure, an additional valve having such means of closure may be provided between the non– return valve and the first connection to the cargo tanks to isolate the water seal or equivalent device.

(i)As an additional safeguard against the possible leakage of flammable liquids or vapours back from the deck main, means shall be provided to permit the section of the line between the valve having positive means of closure referred to in sub– paragraph (h) of this paragraph and the valve referred to in paragraph (8) of this regulation to be vented in a safe manner when the first of these valves is closed.

(10) (a) The inert gas main may be divided into two or more branches between the non– return devices required by paragraph (9) of this regulation and the cargo tanks.

(b)Inert gas supply mains shall be fitted with branch piping leading to each cargo tank designated for the carriage of flammable products required to be inerted by this regulation. Each cargo tank containing or loading products not required to be inerted shall be separated from the inert gas main by:

(i)removing spool pieces, valves or other pipe sections, and blanking the pipe ends; or

(ii)an arrangement of two spectacle flanges in series with provision for detecting leakage into the pipe between the two spectacle flanges.

(c)Means shall be provided to protect cargo tanks against the effect of overpressure or vacuum caused by thermal variations when the cargo tanks are isolated from the inert gas mains.

(d)Piping systems shall be so designed as to prevent the accumulation of cargo or water in the pipelines under all normal conditions.

(e)Suitable arrangements shall be provided to enable the inert gas main to be connected to an external supply of inert gas.

(11) Unless the arrangements for venting of all vapours displaced from the cargo tanks during loading and ballasting comply with the requirements of the I.M.C.O. Code for the Construction and Equipment of Ships Carrying Dangerous Chemicals in Bulk for controlled venting, such arrangements shall comply with regulation 70(3) of the Merchant Shipping (Cargo Ship Construction and Survey) Regulations 1981(3) and shall consist either of one or more mast risers or a number of high velocity vents. The inert gas supply mains shall not be used for such venting.

(12) (a) The arrangements for inerting, purging or gas–freeing of empty tanks as required by paragraph (2) of this regulation shall be to the satisfaction of the Secretary of State and shall be such that the accumulation of flammable vapours in pockets formed by the internal structural members in a tank is minimised.

(b)When in accordance with paragraph (3) of this regulation the Secretary of State permits a system designed to supply only one tank or two tanks simultaneously, the outlet pipes shall be sized such that an exit velocity in the outlet pipes of 20 metres per second can be maintained.

(13) Means shall be provided for continuously indicating the temperature and pressure of the inert gas at the discharge side of the system, whenever it is operating.

(14) (a) Instrumentation shall be fitted for continuously indicating and permanently recording, when the inert gas is being supplied:

(i)the pressure of the inert gas supply mains between the non–return devices required by paragraph (9)(a) of this regulation and the cargo tanks; and

(ii)the oxygen content of the inert gas in the inert gas supply main.

(b)The devices referred to in sub–paragraph (a) of this paragraph shall be placed in the cargo control room where provided. Where no cargo control room is provided, they shall be placed in a position easily accessible to the officer in charge of cargo operations.

(c)In addition, meters shall be fitted:

(i)in the navigating bridge, to indicate at all times the pressure referred to in sub– paragraph (a)(i) of this paragraph; and

(ii)in the machinery control room or in the machinery space to indicate the oxygen content referred to in sub–paragraph (a)(ii) of this paragraph.

(15) Portable instruments for measuring oxygen and flammable vapour concentration shall be provided. In addition, suitable arrangements shall be made on each cargo tank such that the condition of the tank atmosphere can be determined using these portable instruments.

(16) Suitable means shall be provided for the zero and span calibration of both fixed and portable gas concentration measurement instruments, referred to in paragraphs (14) and (15) of this regulation.

(17) (a) Audible and visual alarms shall be provided to indicate:

(i)low water pressure or low water flow rate to the cooling and scrubbing arrangement referred to in paragraph (5)(a) of this regulation;

(ii)low fuel supply;

(iii)high gas temperature referred to in paragraph (13) of this regulation;

(iv)failure of the power supply to the inert gas generators;

(v)oxygen content in excess of 8 per cent by volume referred to in paragraph (14)(a)(ii) of this regulation;

(vi)failure of the power supply to the indicating devices referred to in paragraph (14)(a) of this regulation and to the automatic control systems for the gas– regulating valve referred to in paragraph (8) of this regulation and the inert gas generator;

(vii)low water level in the water seal referred to in sub–paragraph (9)(a) of this regulation;

(viii)gas pressure less than 100 millimetres water gauge referred to in paragraph (14)(a) of this regulation;

(ix)high gas pressure referred to in paragraph (14)(a)(i) of this regulation.

(b)Automatic shutdown of the gas–regulating valve and of the fuel supply to the inert gas generator shall be arranged on pre–determined limits being reached in respect of sub–paragraph (a)(i) and (iii) of this paragraph.

(c)Automatic shutdown of the gas–regulating valve shall be arranged in respect of sub– paragraph (a)(iv) of this paragraph.

(d)In respect of sub–paragraph (a)(v) of this paragraph, when the oxygen content of the inert gas exceeds 8 per cent by volume, immediate action shall be taken to improve the gas quality. Unless the quality of the inert gas improves, all operations in those tanks to which inert gas is being supplied shall be suspended so as to avoid air being drawn into the tanks. The deck isolation valve referred to in paragraph (9)(h) of this regulation shall be closed, and the sub–standard gas shall be vented to atmosphere.

(e)The alarms required by sub–paragraph (a)(v), (vi) and (viii) of this paragraph shall be fitted in the machinery space and cargo control room, where provided, but in each case in such a position that they are immediately received by responsible members of the crew. All other alarms required by this paragraph shall be audible to responsible members of the crew either as individual alarms or as a group alarm.

(f)In respect of sub–paragraph (a)(vii) of this paragraph, the Secretary of State shall be satisfied as to the maintenance of an adequate reserve of water at all times and the integrity of the arrangements to permit the automatic formation of the water seal when the gas flow ceases. The audible and visual alarm on the low level of water in the water seal shall operate when the inert gas is not being supplied.

(g)An audible alarm system, independent of that required by sub–paragraph (a)(viii) of this paragraph, or automatic shutdown of cargo pumps shall be provided to operate on predetermined limits of low pressure in the inert gas mains being reached.

(18) Detailed instruction manuals shall be provided on board, covering the operations, safety and maintenance requirements and occupational health hazards relevant to the inert gas system and its application to the cargo tank system. The manuals shall include guidance on procedures to be followed in the event of a fault or failure of the inert gas system.

Regulation 68

9.  In regulation 68(1) for the sentence beginning “Such hoses” there shall be substituted the following sentences—

Regulation 76

10.—(1) In paragraph (1) of regulation 76, for the words “the Secretary of State may approve” there shall be substituted the words “the Secretary of State shall approve”.

(2) After paragraph (1) of regulation 76 there shall be inserted the following paragraph—

(1A) For the purposes of these Regulations, the results of a verification or test shall be accepted if the verification or test is carried out—

(a)in accordance with these Regulations or with a standard, code of practice, specification or technical description of a member State other than the United Kingdom offering equivalent levels of safety, suitability and fitness for purpose; and

(b)by a body or laboratory of a member State other than the United Kingdom offering suitable and satisfactory guarantees of technical and professional competence and independence..

(1)

The original paragraph (4) was deleted by S.I. 1985/1194.

(2)

S.I. 1984/1217; relevant applying or amending instruments are S.I. 1985/661, 1986/1067.

(3)

S.I. 1981/572, amended by S.I. 1984/1219, 1985/663.