SCHEDULE 2REQUIREMENTS FOR WATER FITTINGS

Requirements for water fittings

7.—(1) No water fitting shall be embedded in any wall or solid floor.

(2) No fitting which is designed to be operated or maintained, whether manually or electronically, or which consists of a joint, shall be a concealed water fitting.

(3) Any concealed water fitting or mechanical backflow prevention device, not being a terminal fitting, shall be made of gunmetal, or another material resistant to dezincification.

(4) Any water fitting laid below ground level shall have a depth of cover sufficient to prevent water freezing in the fitting.

(5) In this paragraph “concealed water fitting” means a water fitting which–

(a)is installed below ground;

(b)passes through or under any wall, footing or foundation;

(c)is enclosed in any chase or duct; or

(d)is in any other position which is inaccessible or renders access difficult.