Regulations 7(2), 8(2) and 12
SCHEDULE 3Energy Efficiency Classification
1. The energy efficiency class of a regulated appliance shall be determined in accordance with the following tables. The energy efficiency ratio (EER) shall be determined in accordance with the test procedures of the harmonised standard at conditions T1 “moderate”.
Table 1 Air-cooled air conditioners
Table 1.1
Energy Efficiency class | Split and multi-split appliances |
---|
A | 3.20<EER |
B | 3.20≥EER>3.00 |
C | 3.00≥EER>2.80 |
D | 2.80≥EER>2.60 |
E | 2.60≥EER>2.40 |
F | 2.40≥EER>2.20 |
G | 2.20≥EER |
Table 1.2
Energy Efficiency class | Packaged (1) |
---|
A | 3.00<EER |
B | 3.00≥EER>2.80 |
C | 2.80≥EER>2.60 |
D | 2.60≥EER>2.40 |
E | 2.40≥EER>2.20 |
F | 2.20≥EER>2.00 |
G | 2.00≥EER |
(1) Packaged “double ducts” units (known commercially as `double ducts') defined as `Air conditioner completely positioned inside the conditioned space, with the condenser air intake and air discharge connected to the outside by means of two ducts', will be classified according to Table 1.2 with a correction factor of –0.4.
Table 1.3
Energy Efficiency class | Single-duct |
---|
A | 2.60<EER |
B | 2.60≥EER>2.40 |
C | 2.40≥EER>2.20 |
D | 2.20≥EER>2.00 |
E | 2.00≥EER>1.80 |
F | 1.80≥EER>1.60 |
G | 1.60≥EER |
Table 2—Water-cooled air conditioners
Table 2.1
Energy Efficiency class | Split and multi-split appliances |
---|
A | 3.60<EER |
B | 3.60≥EER>3.30 |
C | 3.30≥EER>3.10 |
D | 3.10≥EER>2.80 |
E | 2.80≥EER>2.50 |
F | 2.50≥EER>2.20 |
G | 2.20≥EER |
Table 2.2
Energy Efficiency class | Packaged |
---|
A | 4.40<EER |
B | 4.40≥EER>4.10 |
C | 4.10≥EER>3.80 |
D | 3.80≥EER>3.50 |
E | 3.50≥EER>3.20 |
F | 3.20≥EER>2.90 |
G | 2.90≥EER |
2. The heating mode energy efficiency class is then determined in accordance with the following tables: where COP (co-efficiency of performance) is determined in accordance with the test procedures of the harmonised standard at conditions T1 +7C.
Table 3—Air-cooled air conditioners—heating mode
Table 3.1
Energy Efficiency class | Split and multi-split appliances |
---|
A | 3.60<COP |
B | 3.60≥COP>3.40 |
C | 3.40≥COP>3.20 |
D | 3.20≥COP>2.80 |
E | 2.80≥COP>2.60 |
F | 2.60≥COP>2.40 |
G | 2.40≥COP |
Table 3.2
Energy Efficiency class | Packaged suplpar;1) |
---|
A | 3.40<COP |
B | 3.40≥COP>3.20 |
C | 3.20≥COP>3.00 |
D | 3.00≥COP>2.60 |
E | 2.60≥COP>2.40 |
F | 2.40≥COP>2.20 |
G | 2.20≥COP |
(1) Packaged “double ducts” units (known commercially as `double ducts') defined as `Air conditioner completely positioned inside the conditioned space, with the condenser air intake and air discharge connected to the outside by means of two ducts', will be classified according to Table 3.2 with a correction factor of –0.4.
Table 3.3
Energy Efficiency class | Single-duct |
---|
A | 3.00<COP |
B | 3.00≥COP>2.80 |
C | 2.80≥COP>2.60 |
D | 2.60≥COP>2.40 |
E | 2.40≥COP>2.10 |
F | 2.10≥COP>1.80 |
G | 1.80≥COP |
Table 4—Water-cooled air conditioners—heating mode
Table 4.1
Energy Efficiency class | Split appliances |
---|
A | 4.00<COP |
B | 4.00≥COP>3.70 |
C | 3.70≥COP>3.40 |
D | 3.40≥COP>3.10 |
E | 3.10≥COP>2.80 |
F | 2.80≥COP>2.50 |
G | 2.50≥COP |
Table 4.2
Energy Efficiency class | Packaged |
---|
A | 4.70<COP |
B | 4.70≥COP>4.40 |
C | 4.40≥COP>4.10 |
D | 4.10≥COP>3.80 |
E | 3.80≥COP>3.50 |
F | 3.50≥COP>3.20 |
G | 3.20≥COP |