- Latest available (Revised)
- Original (As made)
This is the original version (as it was originally made).
Regulations 7(2), 8(2) and 12
1. The energy efficiency class of a regulated appliance shall be determined in accordance with the following tables. The energy efficiency ratio (EER) shall be determined in accordance with the test procedures of the harmonised standard at conditions T1 ‘moderate’.
Energy Efficiency class | Split and multi-split appliances |
---|---|
A | 3.20<EER |
B | 3.20≥EER>3.00 |
C | 3.00≥EER>2.80 |
D | 2.80≥EER>2.60 |
E | 2.60≥EER>2.40 |
F | 2.40≥EER>2.20 |
G | 2.20≥EER |
Energy Efficiency class | Packaged(1) |
---|---|
(1) Packaged ‘double ducts’ units (known commercially as `double ducts') defined as `Air conditioner completely positioned inside the conditioned space, with the condenser air intake and air discharge connected to the outside by means of two ducts', will be classified according to Table 1.2 with a correction factor of –0.4. | |
A | 3.00<EER |
B | 3.00≥EER>2.80 |
C | 2.80≥EER>2.60 |
D | 2.60≥EER>2.40 |
E | 2.40≥EER>2.20 |
F | 2.20≥EER>2.00 |
G | 2.00≥EER |
Energy Efficiency class | Single-duct |
---|---|
A | 2.60<EER |
B | 2.60≥EER>2.40 |
C | 2.40≥EER>2.20 |
D | 2.20≥EER>2.00 |
E | 2.00≥EER>1.80 |
F | 1.80≥EER>1.60 |
G | 1.60≥EER |
Energy Efficiency class | Split and multi-split appliances |
---|---|
A | 3.60<EER |
B | 3.60≥EER>3.30 |
C | 3.30≥EER>3.10 |
D | 3.10≥EER>2.80 |
E | 2.80≥EER>2.50 |
F | 2.50≥EER>2.20 |
G | 2.20≥EER |
Energy Efficiency class | Packaged |
---|---|
A | 4.40<EER |
B | 4.40≥EER>4.10 |
C | 4.10≥EER>3.80 |
D | 3.80≥EER>3.50 |
E | 3.50≥EER>3.20 |
F | 3.20≥EER>2.90 |
G | 2.90≥EER |
2. The heating mode energy efficiency class is then determined in accordance with the following tables: where COP (co-efficiency of performance) is determined in accordance with the test procedures of the harmonised standard at conditions T1 +7C.
Energy Efficiency class | Split and multi-split appliances |
---|---|
A | 3.60<COP |
B | 3.60≥COP>3.40 |
C | 3.40≥COP>3.20 |
D | 3.20≥COP>2.80 |
E | 2.80≥COP>2.60 |
F | 2.60≥COP>2.40 |
G | 2.40≥COP |
Energy Efficiency class | Single-duct |
---|---|
A | 3.00<COP |
B | 3.00≥COP>2.80 |
C | 2.80≥COP>2.60 |
D | 2.60≥COP>2.40 |
E | 2.40≥COP>2.10 |
F | 2.10≥COP>1.80 |
G | 1.80≥COP |
Energy Efficiency class | Split appliances |
---|---|
A | 4.00<COP |
B | 4.00≥COP>3.70 |
C | 3.70≥COP>3.40 |
D | 3.40≥COP>3.10 |
E | 3.10≥COP>2.80 |
F | 2.80≥COP>2.50 |
G | 2.50≥COP |
Energy Efficiency class | Packaged |
---|---|
A | 4.70<COP |
B | 4.70≥COP>4.40 |
C | 4.40≥COP>4.10 |
D | 4.10≥COP>3.80 |
E | 3.80≥COP>3.50 |
F | 3.50≥COP>3.20 |
G | 3.20≥COP |
Latest Available (revised):The latest available updated version of the legislation incorporating changes made by subsequent legislation and applied by our editorial team. Changes we have not yet applied to the text, can be found in the ‘Changes to Legislation’ area.
Original (As Enacted or Made): The original version of the legislation as it stood when it was enacted or made. No changes have been applied to the text.
Explanatory Memorandum sets out a brief statement of the purpose of a Statutory Instrument and provides information about its policy objective and policy implications. They aim to make the Statutory Instrument accessible to readers who are not legally qualified and accompany any Statutory Instrument or Draft Statutory Instrument laid before Parliament from June 2004 onwards.