SCHEDULE 2Monitoring

PART 2Audit monitoring

Frequency of sampling

4.

(1)

Sampling must be carried out at the frequencies specified in Table 3.

Table 3

Sampling frequency for audit monitoring

Volume m3/day

Sampling frequency per year

≤ 10

1

> 10 ≤ 3,300

2

> 3,300 ≤ 6,600

3

> 6,600 ≤ 10,000

4

> 10,000 ≤ 100,000

3 + 1 for each 10,000 m3/day of the total volume (rounding up to the nearest multiple of 10,000 m3/day)

> 100,000

10 + 1 for each 25,000 m3/day of the total volume (rounding up to the nearest multiple of 25,000 m3/day)

(2)