Schedule 3 (exempt facilities: descriptions and conditions)13
In Schedule 3, in Part 3, after paragraph 3 insert—
Open-loop ground source heating and cooling systems4
1
For the purpose of paragraph 5(a)(i) of Schedule 2, the description is the discharge of water to groundwater from a heating or cooling system to which sub-paragraph (3) applies with altered temperature.
2
For the purpose of paragraph 5(a)(ii) of that Schedule, the conditions in relation to a groundwater activity of that description are—
a
that nothing should be added to water discharged from the system;
b
that the temperature of water discharged from the system—
i
subject to sub-paragraph (ii), must not exceed 25o C, and
ii
must not vary by more than 10o C compared to that in the aquifer from which it was abstracted;
c
that the system must not be on a known contaminated site or have had a previous contaminative use;
d
that water from the system must not be discharged less than 50 metres from a watercourse or groundwater-fed wetland;
e
that water from the system must not be discharged within—
i
50 metres of a point at which water is abstracted from underground strata, or
ii
a zone defined by a 50-day travel time for groundwater to reach a groundwater abstraction point that is used to supply water for domestic or food production purposes;
f
that the discharge of water from the system must be to the same aquifer as that from which it was abstracted;
g
that water within the system must not be used for any other purpose.
3
This sub-paragraph applies to a system—
a
that involves—
i
the abstraction of groundwater to obtain heating or (as the case may be) cooling, and
ii
the subsequent discharge of that water; and
b
that is—
i
a cooled aquifer system with a volume of less than 1500 cubic metres per day;
ii
a balanced system with a volume of less than 430 cubic metres per day; or
iii
a heated aquifer system with a volume of less than 215 cubic metres per day.
4
In this paragraph—
“balanced system” means a system used for both heating and cooling and where in a 5-year period the ratio of the discharge water temperature to the abstracted water temperature is within the range 0.8 to 1.2;
“cooled aquifer system” means a system used for both heating and cooling and where in a 5-year period the ratio of the discharge water temperature to the abstracted water temperature is less than 0.8;
“groundwater-fed wetland” means a terrestrial ecosystem directly depending on a body of groundwater (within the meaning of the Water Framework Directive) and includes—
“heated aquifer system” means a system used for both heating and cooling and where in a 5-year period the ratio of the discharge water temperature to the abstracted water temperature exceeds 1.2.