Revised legislation carried on this site may not be fully up to date. At the current time any known changes or effects made by subsequent legislation have been applied to the text of the legislation you are viewing by the editorial team. Please see ‘Frequently Asked Questions’ for details regarding the timescales for which new effects are identified and recorded on this site.
Regulation 12
1.—(1) A local authority must ensure that each sample is—
(a)taken by a competent person using suitable equipment,
(b)representative of the water at the sampling point at the time of sampling,
(c)not contaminated in the course of being taken,
(d)kept at such a temperature and in such condition as will secure that there is no material change in what is to be measured, and
(e)analysed without delay by a competent person using suitable equipment.
(2) It must ensure that the sample is analysed using a system of analytical quality control.
(3) The system must be subjected to checking by a person who is—
(a)not under the control of either the analyst or the local authority, and
(b)approved by the Secretary of State for that purpose.
2.—(1) A local authority must ensure that each sample is analysed in accordance with this paragraph.
(2) For each parameter specified in the first column of Table 1 in Part 2 of this Schedule, the method of analysis is specified in the second column of that Table.
(3) For each parameter specified in the first column of Table 2 in Part 2 of this Schedule, the method is one that is capable of—
(a)measuring concentrations and values with the trueness and precision specified in the second and third columns of that Table, and
(b)detecting the parameter at the limit of detection specified in the fourth column of that Table.
(4) For hydrogen ion, the method of analysis must be capable of measuring a value with a trueness of 0.2 pH unit and a precision of 0.2 pH unit.
(5) The method of analysis used for odour and taste parameters must be capable of measuring values equal to the parametric value with a precision of 1 dilution number at 25°C.
(6) For these purposes—
“limit of detection” is —
three times the relative within-batch standard deviation of a natural sample containing a low concentration of the parameter, or
five times the relative within-batch standard deviation of a blank sample;
“precision” (the random error) is twice the standard deviation (within a batch and between batches) of the spread of results about the mean;
“trueness” (the systematic error) is the difference between the mean value of the large number of repeated measurements and the true value.
3.—(1) The Secretary of State may authorise a method different from that set out in paragraph 2(2) if satisfied that it is at least as reliable.
(2) An authorisation may be time-limited and may be revoked at any time.
4.—(1) A local authority may enter into an arrangement for any person to take and analyse samples on its behalf.
(2) A local authority must not enter into an arrangement under sub-paragraph (1) unless—
(a)it is satisfied that the task will be carried out promptly by a person competent to perform it, and
(b)it has made arrangements that ensure that any breach of these Regulations is communicated to it immediately, and any other result is communicated to it within 28 days.
Parameter | Method |
---|---|
Clostridium perfringens (including spores) | Membrane filtration followed by anaerobic incubation of the membrane on m-CP agar* at 44 ± 1°C for 21 ± 3 hours. Count opaque yellow colonies that turn pink or red after exposure to ammonium hydroxide vapours for 20 to 30 seconds. |
Coliform bacteria and Escherichia coli (E. coli) | BS-EN ISO 9308-1 and BS-EN ISO 9308-2 |
Colony count 22°C-enumeration of culturable microorganisms | BS-EN ISO 6222 |
Colony count 37°C-enumeration of culturable microorganisms | BS-EN ISO 6222 |
Enterococci | BS-EN ISO 7899-2 |
Pseudomonas aeruginosa | BS-EN ISO 12780 |
*Use the following method to make m-CP agar: | ||
Make a basal medium consisting of— | ||
Tryptose | 30.0g | |
Yeast extract | 20.0g | |
Sucrose | 5.0g | |
L-cysteine hydrochloride | 1.0g | |
MgSO4.7H2O | 0.1g | |
Bromocresol purple | 40.0mg | |
Agar | 15.0g | |
Water | 1,000.0ml | |
Dissolve the ingredients of the basal medium; adjust pH to 7.6 and autoclave at 121°C for 15 minutes. Allow the medium to cool. | ||
Dissolve— | ||
D-cycloserine | 400.0mg | |
Polymyxine-B sulphate | 25.0mg | |
Indoxyl-β-D-glucoside | 60.0mg | |
into 8ml sterile water and add it to the medium. | ||
Add to the medium— | ||
Filter-sterilised 0.5% phenolphthalein diphosphate solution | 20.0ml | |
Filter-sterilised 4.5% FeCl3.6H2O | 2.0ml |
1 The method of analysis should determine total cyanide in all forms | |||
2 The performance characteristics apply to each individual pesticide and will depend on the pesticide concerned. | |||
3 The performance characteristics apply to the individual substances specified at 25% of the parametric value in Part I of Table B in Part 1 of Schedule 1. | |||
4 The performance characteristics apply to the individual substances specified at 50% of the parametric value in Part I of Table B in Part 1 of Schedule 1. | |||
5 The performance characteristics apply to the prescribed value of 4 NTU. | |||
6 The performance characteristic apply to the specification of 1 NTU for surface waters or ground waters influenced by surface water. | |||
Parameters | Trueness % of prescribed concentration or value or specification | Precision % of prescribed concentration or value or specification | Limit of detection % of prescribed concentration or value or specification |
---|---|---|---|
Aluminium | 10 | 10 | 10 |
Ammonium | 10 | 10 | 10 |
Antimony | 25 | 25 | 25 |
Arsenic | 10 | 10 | 10 |
Benzene | 25 | 25 | 25 |
Benzo(a)pyrene | 25 | 25 | 25 |
Boron | 10 | 10 | 10 |
Bromate | 25 | 25 | 25 |
Cadmium | 10 | 10 | 10 |
Chloride | 10 | 10 | 10 |
Chromium | 10 | 10 | 10 |
Colour | 10 | 10 | 10 |
Conductivity | 10 | 10 | 10 |
Copper | 10 | 10 | 10 |
Cyanide1 | 10 | 10 | 10 |
1,2-dichloroethane | 25 | 25 | 10 |
Fluoride | 10 | 10 | 10 |
Iron | 10 | 10 | 10 |
Lead | 10 | 10 | 10 |
Manganese | 10 | 10 | 10 |
Mercury | 20 | 10 | 20 |
Nickel | 10 | 10 | 10 |
Nitrate | 10 | 10 | 10 |
Nitrite | 10 | 10 | 10 |
Pesticides and related products2 | 25 | 25 | 25 |
Polycyclic aromatic hydrocarbons3 | 25 | 25 | 25 |
Selenium | 10 | 10 | 10 |
Sodium | 10 | 10 | 10 |
Sulphate | 10 | 10 | 10 |
Tetrachloroethene4 | 25 | 25 | 10 |
Tetrachloromethane | 20 | 20 | 20 |
Trichloroethene4 | 25 | 25 | 10 |
Trihalomethanes: Total3 | 25 | 25 | 10 |
Turbidity5 | 10 | 10 | 10 |
Turbidity6 | 25 | 25 | 25 |
5.—(1) A local authority may use various reliable screening strategies to indicate the presence of radioactivity in water intended for human consumption.
(2) These strategies may include screening for—
(a)certain radionuclides, or screening for an individual radionuclide;
(b)gross alpha activity or gross beta activity screening.
6.—(1) If one of the activity concentrations exceeds 20% of the corresponding derived value or the tritium concentration exceeds its parametric value specified in the radioactive parameters table, an analysis of additional radionuclides is required.
(2) A local authority must take into account, in deciding which radionuclides are required to be measured for each supply, all relevant information about likely sources of radioactivity.
7.—(1) Subject to paragraph 6(1), the recommended screening values are—
(a)0.1 Bq/l for gross alpha activity, and
(b)1.0 Bq/l for gross beta activity M1.
(2) If the gross alpha activity exceeds 0.1 Bq/l or the gross beta activity exceeds 1.0 Bq/l, analysis for specific radionuclides is required.
(3) The Secretary of State may set alternative screening levels for gross alpha activity and gross beta activity where it is demonstrated by the local authority that the alternative levels are in compliance with an ID of 0,1 mSv.
(4) The determination by the local authority of which radionuclides to measure must be based on all relevant information about likely sources of radioactivity.
Marginal Citations
M1Where appropriate, gross beta activity may be replaced by residual beta activity after subtraction of the K-40 activity concentration.
8.—(1) The ID must be calculated from—
(a)the measured radionuclide concentrations and the dose coefficients laid down in Annex III, Table A of Directive 96/29/Euratom laying down basic safety standards for the protection of the health of workers and the general public against the dangers arising from ionising radiation M2, or
(b)more recent information recognised by the Secretary of State, on the basis of the annual intake of water (730 litres for adults).
(2) Where the following formula is satisfied, it can be assumed that the ID is less than the parametric value of 0,1mSv and no further investigation is required—
Where—
“Ci(obs)” means the observed concentration of radionuclide I;
“Ci(der)” means the derived concentration of radionuclide I;
“n” means the number of radionuclides detected.
1 This Table allows only for the radiological properties of uranium, not for its chemical toxicity. | ||
Origin | Nuclide | Derived concentration |
---|---|---|
Natural | U-2381 | 3,0 Bq/1 |
U-2341 | 2,8 Bq/1 | |
Ra-226 | 0,5 Bq/1 | |
Ra-228 | 0,2 Bq/1 | |
Pb-210 | 0,2 Bq/1 | |
Po-210 | 0,1 Bq/1 | |
Artificial | C-14 | 240 Bq/1 |
Sr-90 | 4,9 Bq/1 | |
Pu-239/Pu-240 | 0,6 Bq/1 | |
Am-241 | 0,7 Bq/1 | |
Co-60 | 40 Bq/1 | |
Cs-134 | 7,2 Bq/1 | |
Cs-137 | 11 Bq/1 | |
1-131 | 6,2 Bq/1 |
Marginal Citations
M2OJ No L 159, 29.6.1996, p 1. It is prospectively repealed by Council Directive 2013/59/EURATOM (OJ No L 13, 17.01.2014, p 1 from 6 February 2018.
M3This Table includes values for the most common natural and artificial radionuclides; these are precise values, calculated for a dose of 0,1 mSv, an annual intake of 730 litres and using the dose coefficients laid down in Annex III, Table A of Directive 96/29/Euratom. Derived concentrations for other radionuclides can be calculated on the same basis, and values can be updated on the basis of more recent information recognised by the Secretary of State.
9. For the following parameters and radionuclides, the method of analysis used must, as a minimum, be capable of measuring activity concentrations with a limit of detection specified below—
Parameters and radionuclides | Limit of detection (Notes 1,2) | Notes |
---|---|---|
Tritium | 10 Bq/1 | Note 3 |
Radon | 10 Bq/1 | Note 3 |
gross alpha | 0,04 Bq/1 | Note 4 |
gross beta | 0,4 Bq/1 | Note 4 |
U-238 | 0,02 Bq/1 | |
U-234 | 0,02 Bq/1 | |
Ra-226 | 0,04 Bq/1 | |
Ra-228 | 0,02 Bq/1 | Note 5 |
Pb-210 | 0,02 Bq/1 | |
Po-210 | 0,01 Bq/1 | |
C-14 | 20 Bq/1 | |
Sr-90 | 0,4 Bq/1 | |
Pu-239/Pu-240 | 0,04 Bq/1 | |
Am-241 | 0,06 Bq/1 | |
Co-60 | 0,5 Bq/1 | |
Cs-134 | 0,5 Bq/1 | |
Cs-137 | 0,5 Bq/1 | |
I-131 | 0,5 Bq/1 |
Note 1: The limit of detection must be calculated according to the ISO standard 11929: Determination of the characteristic limits (decision threshold, detection limit, and limits of confidence interval) for measurements of ionising radiation – Fundamentals and application, with probabilities of errors of 1st and 2nd kind of 0,05 each M4.
Note 2: Measurement uncertainties must be calculated and reported as complete standard uncertainties, or as expanded uncertainties with an expansion factor of 1,96 according the ISO Guide for the Expression of Uncertainty in Measurement M5.
Note 3: The limit of detection for tritium and for radon is 10% of its parametric value of 100 Bq/1.
Note 4: The limit of detection for gross alpha activity and gross beta activities are 40% of the screening values of 0,1 and 1,0 Bq/1 respectively.
Note 5: This limit of detection applies only to initial screening for ID for a new water source; if initial checking indicates that it is not plausible that Ra-228 exceeds 20% of the derived concentration, the limit of detection may be increased to 0,08 Bq/1 for routine Ra-228 nuclide specific measurements, until a subsequent re-check is required.
Latest Available (revised):The latest available updated version of the legislation incorporating changes made by subsequent legislation and applied by our editorial team. Changes we have not yet applied to the text, can be found in the ‘Changes to Legislation’ area.
Original (As Enacted or Made): The original version of the legislation as it stood when it was enacted or made. No changes have been applied to the text.
Point in Time: This becomes available after navigating to view revised legislation as it stood at a certain point in time via Advanced Features > Show Timeline of Changes or via a point in time advanced search.
Geographical Extent: Indicates the geographical area that this provision applies to. For further information see ‘Frequently Asked Questions’.
Show Timeline of Changes: See how this legislation has or could change over time. Turning this feature on will show extra navigation options to go to these specific points in time. Return to the latest available version by using the controls above in the What Version box.
Explanatory Memorandum sets out a brief statement of the purpose of a Statutory Instrument and provides information about its policy objective and policy implications. They aim to make the Statutory Instrument accessible to readers who are not legally qualified and accompany any Statutory Instrument or Draft Statutory Instrument laid before Parliament from June 2004 onwards.
Access essential accompanying documents and information for this legislation item from this tab. Dependent on the legislation item being viewed this may include:
This timeline shows the different points in time where a change occurred. The dates will coincide with the earliest date on which the change (e.g an insertion, a repeal or a substitution) that was applied came into force. The first date in the timeline will usually be the earliest date when the provision came into force. In some cases the first date is 01/02/1991 (or for Northern Ireland legislation 01/01/2006). This date is our basedate. No versions before this date are available. For further information see the Editorial Practice Guide and Glossary under Help.
Use this menu to access essential accompanying documents and information for this legislation item. Dependent on the legislation item being viewed this may include:
Click 'View More' or select 'More Resources' tab for additional information including: