xmlns:atom="http://www.w3.org/2005/Atom" xmlns:atom="http://www.w3.org/2005/Atom"
Regulation 6(c)
1. The name and address of the testing laboratory by which tests have been carried out.E+W+S
2. The name and signature of the person authorised by the testing laboratory to issue the certificate.E+W+S
3. The date of issue of the certificate together with a certificate reference number.E+W+S
4. Where the testing laboratory is accredited to BS EN ISO/IEC 17025:2005M1[F1, 17025:2017 or a subsequent version of that standard]—E+W+S
(a)the date of that accreditation; and
(b)the accreditation number.
Textual Amendments
F1Words in Sch. 1 para. 4 inserted (1.4.2022) by The Domestic Renewable Heat Incentive Scheme and Renewable Heat Incentive Scheme (Amendment) Regulations 2022 (S.I. 2022/159), regs. 1(3), 45(a)
Marginal Citations
M1The ISBN for the English language version of this standard is ISBN 0 580 46330 3. This standard was published by the British Standards Institution on 29th June 2005 and copies, including hard copies, can be obtained at www.bsigroup.com.
5. The name, model, manufacturer and installation capacity of the plant tested.E+W+S
6. The date of the testing.E+W+S
7. Confirmation that emissions of NOₓ and PM have been tested on the same occasion in accordance with the requirements specified in paragraph 8 or 9.E+W+S
8. The requirements of this paragraph are that testing is carried out in accordance with the provisions relevant to emissions of PM and NOₓ in [F2BS EN 303-5:2012 or a subsequent version of that standard, whichever version] is current at the time of testing.E+W+S
Textual Amendments
F2Words in Sch. 1 para. 8 substituted (1.4.2022) by The Domestic Renewable Heat Incentive Scheme and Renewable Heat Incentive Scheme (Amendment) Regulations 2022 (S.I. 2022/159), regs. 1(3), 45(b)
9. The requirements of this paragraph are that—E+W+S
(a)testing is carried out in accordance with—
(i)BS [F314792:2017 or a subsequent version of that standard] in respect of NOₓ emissions; and
(ii)[F4BS EN 13284-1:2017 or BS ISO 9096:2017 or a subsequent version of one of those standards] in respect of PM emissions;
(b)the emissions of PM represent the average of at least three measurements of emissions of PM, each of at least 30 minutes duration; and
(c)the value for NOₓ emissions is derived from the average of measurements made throughout the PM emission tests.
Textual Amendments
10. Confirmation that the test was carried out at no less than 85% of the installation capacity of the plant.E+W+S
11. Confirmation that when tested as specified in paragraphs 7 to 10—E+W+S
(a)emissions of PM from the plant did not exceed 30 grams of PM per gigajoule net heat input; and
(b)emissions of NOₓ did not exceed 150 grams of NOₓ per gigajoule net heat input.
12. The actual emissions of PM and NOₓ measured when the plant was tested as specified in paragraphs 7 to 10.E+W+S
13. A list of—E+W+S
(a)the types of fuel used during the testing; and
(b)the types of fuel which can be used so as to ensure that the emission limits referred to in paragraph 11 are not exceeded.
14. The moisture content of the fuel used during testing and the maximum moisture content which can be used so as to ensure that the emission limits referred to in paragraph 11 are not exceeded.E+W+S
15. A statement indicating whether or not the plant tested was a manually stoked natural draught plant.E+W+S
16. A list of plants, other than the plant tested, in the type-testing range of plants to which the certificate applies, if any.E+W+S