3.—(1) IE is set out in Tables 21 to 26, for different values of the motor rated output power PN at 50 Hz or 60 Hz.
(2) IE classes are determined at rated output power (PN), rated voltage (UN), and based on 25 °C ambient reference temperature.
(3) For 50/60 Hz motors, the requirements in Tables 21 to 26 must be met at both 50Hz and 60 Hz at the rated output power specified for 50 Hz.
(4) For 50Hz motors the requirements in Tables 21 to 23 must be met at 50 Hz at the rated output power specified for 50 Hz.
(5) For 60Hz motors the requirements in Tables 24 to 26 must be met at 60 Hz at the rated output power specified for 60 Hz.
(6) Losses must be determined in accordance with Schedule 17.
Rated output power PN [kW] | 2 poles | 4 poles | 6 poles | 8 poles |
---|---|---|---|---|
0.12 | 53.6 | 59.1 | 50.6 | 39.8 |
0.18 | 60.4 | 64.7 | 56.6 | 45.9 |
0.20 | 61.9 | 65.9 | 58.2 | 47.4 |
0.25 | 64.8 | 68.5 | 61.6 | 50.6 |
0.37 | 69.5 | 72.7 | 67.6 | 56.1 |
0.40 | 70.4 | 73.5 | 68.8 | 57.2 |
0.55 | 74.1 | 77.1 | 73.1 | 61.7 |
0.75 | 77.4 | 79.6 | 75.9 | 66.2 |
1.1 | 79.6 | 81.4 | 78.1 | 70.8 |
1.5 | 81.3 | 82.8 | 79.8 | 74.1 |
2.2 | 83.2 | 84.3 | 81.8 | 77.6 |
3 | 84.6 | 85.5 | 83.3 | 80.0 |
4 | 85.8 | 86.6 | 84.6 | 81.9 |
5.5 | 87.0 | 87.7 | 86.0 | 83.8 |
7.5 | 88.1 | 88.7 | 87.2 | 85.3 |
11 | 89.4 | 89.8 | 88.7 | 86.9 |
15 | 90.3 | 90.6 | 89.7 | 88.0 |
18.5 | 90.9 | 91.2 | 90.4 | 88.6 |
22 | 91.3 | 91.6 | 90.9 | 89.1 |
30 | 92.0 | 92.3 | 91.7 | 89.8 |
37 | 92.5 | 92.7 | 92.2 | 90.3 |
45 | 92.9 | 93.1 | 92.7 | 90.7 |
55 | 93.2 | 93.5 | 93.1 | 91.0 |
75 | 93.8 | 94.0 | 93.7 | 91.6 |
90 | 94.1 | 94.2 | 94.0 | 91.9 |
110 | 94.3 | 94.5 | 94.3 | 92.3 |
132 | 94.6 | 94.7 | 94.6 | 92.6 |
160 | 94.8 | 94.9 | 94.8 | 93.0 |
200 up to 1,000 | 95.0 | 95.1 | 95.0 | 93.5 |
Rated output power PN [kW] | 2 poles | 4 poles | 6 poles | 8 poles |
---|---|---|---|---|
0.12 | 60.8 | 64.8 | 57.7 | 50.7 |
0.18 | 65.9 | 69.9 | 63.9 | 58.7 |
0.20 | 67.2 | 71.1 | 65.4 | 60.6 |
0.25 | 69.7 | 73.5 | 68.6 | 64.1 |
0.37 | 73.8 | 77.3 | 73.5 | 69.3 |
0.40 | 74.6 | 78.0 | 74.4 | 70.1 |
0.55 | 77.8 | 80.8 | 77.2 | 73.0 |
0.75 | 80.7 | 82.5 | 78.9 | 75.0 |
1.1 | 82.7 | 84.1 | 81.0 | 77.7 |
1.5 | 84.2 | 85.3 | 82.5 | 79.7 |
2.2 | 85.9 | 86.7 | 84.3 | 81.9 |
3 | 87.1 | 87.7 | 85.6 | 83.5 |
4 | 88.1 | 88.6 | 86.8 | 84.8 |
5.5 | 89.2 | 89.6 | 88.0 | 86.2 |
7.5 | 90.1 | 90.4 | 89.1 | 87.3 |
11 | 91.2 | 91.4 | 90.3 | 88.6 |
15 | 91.9 | 92.1 | 91.2 | 89.6 |
18.5 | 92.4 | 92.6 | 91.7 | 90.1 |
22 | 92.7 | 93.0 | 92.2 | 90.6 |
30 | 93.3 | 93.6 | 92.9 | 91.3 |
37 | 93.7 | 93.9 | 93.3 | 91.8 |
45 | 94.0 | 94.2 | 93.7 | 92.2 |
55 | 94.3 | 94.6 | 94.1 | 92.5 |
75 | 94.7 | 95.0 | 94.6 | 93.1 |
90 | 95.0 | 95.2 | 94.9 | 93.4 |
110 | 95.2 | 95.4 | 95.1 | 93.7 |
132 | 95.4 | 95.6 | 95.4 | 94.0 |
160 | 95.6 | 95.8 | 95.6 | 94.3 |
200 up to 1,000 | 95.8 | 96.0 | 95.8 | 94.6 |
Rated output power PN [kW] | 2 poles | 4 poles | 6 poles | 8 poles |
---|---|---|---|---|
0.12 | 66.5 | 69.8 | 64.9 | 62.3 |
0.18 | 70.8 | 74.7 | 70.1 | 67.2 |
0.20 | 71.9 | 75.8 | 71.4 | 68.4 |
0.25 | 74.3 | 77.9 | 74.1 | 70.8 |
0.37 | 74.3 | 77.9 | 74.1 | 70.8 |
0.40 | 78.9 | 81.7 | 78.7 | 74.9 |
0.55 | 81.5 | 83.9 | 80.9 | 77.0 |
0.75 | 83.5 | 85.7 | 82.7 | 78.4 |
1.1 | 85.2 | 87.2 | 84.5 | 80.8 |
1.5 | 86.5 | 88.2 | 85.9 | 82.6 |
2.2 | 88.0 | 89.5 | 87.4 | 84.5 |
3 | 89.1 | 90.4 | 88.6 | 85.9 |
4 | 90.0 | 91.1 | 89.5 | 87.1 |
5.5 | 90.9 | 91.9 | 90.5 | 88.3 |
7.5 | 91.7 | 92.6 | 91.3 | 89.3 |
11 | 92.6 | 93.3 | 92.3 | 90.4 |
15 | 93.3 | 93.9 | 92.9 | 91.2 |
18.5 | 93.7 | 94.2 | 93.4 | 91.7 |
22 | 94.0 | 94.5 | 93.7 | 92.1 |
30 | 94.5 | 94.9 | 94.2 | 92.7 |
37 | 94.8 | 95.2 | 94.5 | 93.1 |
45 | 95.0 | 95.4 | 94.8 | 93.4 |
55 | 95.3 | 95.7 | 95.1 | 93.7 |
75 | 95.6 | 96.0 | 95.4 | 94.2 |
90 | 95.8 | 96.1 | 95.6 | 94.4 |
110 | 96.0 | 96.3 | 95.8 | 94.7 |
132 | 96.2 | 96.4 | 96.0 | 94.9 |
160 | 96.3 | 96.6 | 96.2 | 95.1 |
200 up to 249 | 96.5 | 96.7 | 96.3 | 95.4 |
250 up to 314 | 96.5 | 96.7 | 96.5 | 95.4 |
315 up to 1,000 | 96.5 | 96.7 | 96.6 | 95.4 |
Rated output power PN [kW] | 2 poles | 4 poles | 6 poles | 8 poles |
---|---|---|---|---|
2 | 4 | 6 | 8 | |
0.12 | 59.5 | 64.0 | 50.5 | 40.0 |
0.18 | 64.0 | 68.0 | 55.0 | 46.0 |
0.25 | 68.0 | 70.0 | 59.5 | 52.0 |
0.37 | 72.0 | 72.0 | 64.0 | 58.0 |
0.55 | 74.0 | 75.5 | 68.0 | 62.0 |
0.75 | 75.5 | 78.0 | 73.0 | 66.0 |
1.1 | 82.5 | 84.0 | 85.5 | 75.5 |
1.5 | 84.0 | 84.0 | 86.5 | 82.5 |
2.2 | 85.5 | 87.5 | 87.5 | 84.0 |
3.7 | 87.5 | 87.5 | 87.5 | 85.5 |
5.5 | 88.5 | 89.5 | 89.5 | 85.5 |
7.5 | 89.5 | 89.5 | 89.5 | 88.5 |
11 | 90.2 | 91.0 | 90.2 | 88.5 |
15 | 90.2 | 91.0 | 90.2 | 89.5 |
18.5 | 91.0 | 92.4 | 91.7 | 89.5 |
22 | 91.0 | 92.4 | 91.7 | 91.0 |
30 | 91.7 | 93.0 | 93.0 | 91.0 |
37 | 92.4 | 93.0 | 93.0 | 91.7 |
45 | 93.0 | 93.6 | 93.6 | 91.7 |
55 | 93.0 | 94.1 | 93.6 | 93.0 |
75 | 93.6 | 94.5 | 94.1 | 93.0 |
90 | 94.5 | 94.5 | 94.1 | 93.6 |
110 | 94.5 | 95.0 | 95.0 | 93.6 |
150 | 95.0 | 95.0 | 95.0 | 93.6 |
185 | 95.4 | 95.4 | 95.0 | 93.6 |
220 | 95.4 | 95.4 | 95.0 | 93.6 |
250 | 95.4 | 95.4 | 95.0 | 93.6 |
300 | 95.4 | 95.4 | 95.0 | 93.6 |
335 | 95.4 | 95.4 | 95.0 | 93.6 |
375 up to 1000 | 95.4 | 95.8 | 95.0 | 94.1 |
Rated output power PN [kW] | 2 poles | 4 poles | 6 poles | 8 poles |
---|---|---|---|---|
2 | 4 | 6 | 8 | |
0.12 | 62.0 | 66.0 | 64.0 | 59.5 |
0.18 | 65.6 | 69.5 | 67.5 | 64.0 |
0.25 | 69.5 | 73.4 | 71.4 | 68.0 |
0.37 | 73.4 | 78.2 | 75.3 | 72.0 |
0.55 | 76.8 | 81.1 | 81.7 | 74.0 |
0.75 | 77.0 | 83.5 | 82.5 | 75.5 |
1.1 | 84.0 | 86.5 | 87.5 | 78.5 |
1.5 | 85.5 | 86.5 | 88.5 | 84.0 |
2.2 | 86.5 | 89.5 | 89.5 | 85.5 |
3.7 | 88.5 | 89.5 | 89.5 | 86.5 |
5.5 | 89.5 | 91.7 | 91.0 | 86.5 |
7.5 | 90.2 | 91.7 | 91.0 | 89.5 |
11 | 91.0 | 92.4 | 91.7 | 89.5 |
15 | 91.0 | 93.0 | 91.7 | 90.2 |
18.5 | 91.7 | 93.6 | 93.0 | 90.2 |
22 | 91.7 | 93.6 | 93.0 | 91.7 |
30 | 92.4 | 94.1 | 94.1 | 91.7 |
37 | 93.0 | 94.5 | 94.1 | 92.4 |
45 | 93.6 | 95.0 | 94.5 | 92.4 |
55 | 93.6 | 95.4 | 94.5 | 93.6 |
75 | 94.1 | 95.4 | 95.0 | 93.6 |
90 | 95.0 | 95.4 | 95.0 | 94.1 |
110 | 95.0 | 95.8 | 95.8 | 94.1 |
150 | 95.4 | 96.2 | 95.8 | 94.5 |
185 | 95.8 | 96.2 | 95.8 | 95.0 |
220 | 95.8 | 96.2 | 95.8 | 95.0 |
250 | 95.8 | 96.2 | 95.8 | 95.0 |
300 | 95.8 | 96.2 | 95.8 | 95.0 |
335 | 95.8 | 96.2 | 95.8 | 95.0 |
375 up to 1000 | 95.8 | 96.2 | 95.8 | 95.0 |
Rated output power PN [kW] | 2 poles | 4 poles | 6 poles | 8 poles |
---|---|---|---|---|
2 | 4 | 6 | 8 | |
0.12 | 66.0 | 70.0 | 68.0 | 64.0 |
0.18 | 70.0 | 74.0 | 72.0 | 68.0 |
0.25 | 74.0 | 77.0 | 75.5 | 72.0 |
0.37 | 77.0 | 81.5 | 78.5 | 75.5 |
0.55 | 80.0 | 84.0 | 82.5 | 77.0 |
0.75 | 82.5 | 85.5 | 84.0 | 78.5 |
1.1 | 85.5 | 87.5 | 88.5 | 81.5 |
1.5 | 86.5 | 88.5 | 89.5 | 85.5 |
2.2 | 88.5 | 91.0 | 90.2 | 87.5 |
3.7 | 89.5 | 91.0 | 90.2 | 88.5 |
5.5 | 90.2 | 92.4 | 91.7 | 88.5 |
7.5 | 91.7 | 92.4 | 92.4 | 91.0 |
11 | 92.4 | 93.6 | 93.0 | 91.0 |
15 | 92.4 | 94.1 | 93.0 | 91.7 |
18.5 | 93.0 | 94.5 | 94.1 | 91.7 |
22 | 93.0 | 94.5 | 94.1 | 93.0 |
30 | 93.6 | 95.0 | 95.0 | 93.0 |
37 | 94.1 | 95.4 | 95.0 | 93.6 |
45 | 94.5 | 95.4 | 95.4 | 93.6 |
55 | 94.5 | 95.8 | 95.4 | 94.5 |
75 | 95.0 | 96.2 | 95.8 | 94.5 |
90 | 95.4 | 96.2 | 95.8 | 95.0 |
110 | 95.4 | 96.2 | 96.2 | 95.0 |
150 | 95.8 | 96.5 | 96.2 | 95.4 |
185 | 96.2 | 96.5 | 96.2 | 95.4 |
220 | 96.2 | 96.8 | 96.5 | 95.4 |
250 | 96.2 | 96.8 | 96.5 | 95.8 |
300 | 96.2 | 96.8 | 96.5 | 95.8 |
335 | 96.2 | 96.8 | 96.5 | 95.8 |
375 up to 1000 | 96.2 | 96.8 | 96.5 | 95.8 |
The Whole Instrument you have selected contains over 200 provisions and might take some time to download. You may also experience some issues with your browser, such as an alert box that a script is taking a long time to run.
Would you like to continue?
The Whole Instrument you have selected contains over 200 provisions and might take some time to download.
Would you like to continue?
The Whole Instrument you have selected contains over 200 provisions and might take some time to download. You may also experience some issues with your browser, such as an alert box that a script is taking a long time to run.
Would you like to continue?
The Schedules you have selected contains over 200 provisions and might take some time to download. You may also experience some issues with your browser, such as an alert box that a script is taking a long time to run.
Would you like to continue?
Latest Available (revised):The latest available updated version of the legislation incorporating changes made by subsequent legislation and applied by our editorial team. Changes we have not yet applied to the text, can be found in the ‘Changes to Legislation’ area.
Original (As Enacted or Made): The original version of the legislation as it stood when it was enacted or made. No changes have been applied to the text.
Explanatory Memorandum sets out a brief statement of the purpose of a Statutory Instrument and provides information about its policy objective and policy implications. They aim to make the Statutory Instrument accessible to readers who are not legally qualified and accompany any Statutory Instrument or Draft Statutory Instrument laid before Parliament from June 2004 onwards.
Access essential accompanying documents and information for this legislation item from this tab. Dependent on the legislation item being viewed this may include:
Impact Assessments generally accompany all UK Government interventions of a regulatory nature that affect the private sector, civil society organisations and public services. They apply regardless of whether the regulation originates from a domestic or international source and can accompany primary (Acts etc) and secondary legislation (SIs). An Impact Assessment allows those with an interest in the policy area to understand:
Use this menu to access essential accompanying documents and information for this legislation item. Dependent on the legislation item being viewed this may include:
Click 'View More' or select 'More Resources' tab for additional information including: