SCHEDULE 1Concentrations or Values

PART 2Indicator Parameters

TABLE CPrescribed concentrations, values or states

Parameters

Maximum concentration or value or state (unless otherwise stated)

Units of measurement

Ammonium

0.50

mg/l

Chloride (i)

250

mg/l

Clostridium perfringens

0

Number/100ml

(including spores)

Coliform bacteria

0

Number/100ml (Number/250ml in the case of water put into bottles or containers)

Colony counts

No abnormal change

Number/ml at 22°C

No abnormal change

Number/ml at 37°C

Conductivity (i)

2500

μS/cm at 20°C

Hydrogen ion

9.5 (maximum)

pH value

6.5 (minimum) (in the case of still water put into bottles or containers the minimum is 4.5)

pH value

Sulphate (i)

250

mg/l

Total indicative dose (for radioactivity) (ii)

0.10

mSv/year

Total organic carbon (TOC)

No abnormal change

mgC/l

Tritium

(for radioactivity)

100

Bq/l

Turbidity(iii)

1

NTU

(i)

The water should not be aggressive.

(ii)

Excluding tritium, potassium-40, radon and radon decay products.

(iii)

Only in the case of surface water or groundwater that has been influenced by surface water.