SCHEDULE 3MONITORING

Regulations 2, 6, 8 and 9

Part 1Group A and Group B Parameters

Annotations:
Table 1Group A parameters and circumstances for monitoring

Item number (1)

Parameter (2)

Circumstances (3)

1

Aluminium

Where used as a water treatment chemical or where the water originates from, or is influenced by, surface waters

2

Ammonium

Where chloramination is practised

3

Coliform bacteria

In all circumstances

4

Colony counts 22 ° C

In all circumstances

5

Colour

In all circumstances

6

Conductivity1

In all circumstances

7

E. coli

In all circumstances

8

Hydrogen ion

In all circumstances

9

Iron

Where used as a water treatment chemical or where the water originates from, or is influenced by, surface waters

10

Manganese

Where the water originates from, or is influenced by, surface waters

11

Nitrate

Where chloramination is practised

12

Nitrite

Where chloramination is practised

13

Odour

In all circumstances

14

Residual disinfectant

In all circumstances

15

Taste

In all circumstances

16

Turbidity

In all circumstances

Note:

1 Sampling for this parameter in water supply zones may be substituted by sampling at supply points.

Table 2Group B1 parameters and circumstances for monitoring to be used for sampling in water supply zones (or supply points)

Item number

Parameter (2)

Circumstances

1

Aluminium

Where—

(i) not used as a water treatment chemical; or

(ii) the water neither originates from, nor is influenced by, surface waters.

2

Ammonium

Where chloramination is not practised

3

Antimony

In all circumstances

4

Arsenic

In all circumstances

5

Benzene 1

In all circumstances

6

Benzo(a)pyrene

In all circumstances

7

Boron 1

In all circumstances

8

Bromate 2

In all circumstances

9

Cadmium

In all circumstances

10

Chloride 1

In all circumstances

11

Chromium

In all circumstances

12

Clostridium perfringens (including spores)

In all circumstances

13

Copper

In all circumstances

14

Cyanide 1

In all circumstances

15

1, 2 dichloroethane 1

In all circumstances

16

Enterococci

In all circumstances

17

Fluoride 1

In all circumstances

18

Gross alpha 134

In all circumstances

19

Gross beta 134

In all circumstances

20

Iron

Where—

(i) not used as a flocculant; or

(ii) the water neither originates from, nor is influenced by, surface waters.

21

Lead

In all circumstances

22

Manganese

Where the water neither originates from, nor is influenced by, surface waters.

23

Mercury 1

In all circumstances

24

Nickel

In all circumstances

25

Nitrate

Where chloramination is not practised.

26

Nitrite

Where chloramination is not practised.

27

Pesticides and related products 1

In all circumstances

28

Polycyclic aromatic hydrocarbon

In all circumstances

29

Radon 14

In all circumstances

30

Selenium

In all circumstances

31

Sodium

In all circumstances

32

Sulphate 1

In all circumstances

33

Tetrachloroethene 1

In all circumstances

34

Tetrachloromethane 1

In all circumstances

Total organic carbon 1

35

Trichloroethene

In all circumstances

Trihalomethanes: Total

36

Tritium 14

In all circumstances

Notes:

1 Sampling for these parameters may be within water supply zones (Group B1) or at supply points (Group B2).

2 Monitoring of this parameter in water supply zones is required only where sodium hypochlorite is added after water has left the treatment works. In other circumstances, monitoring is required at supply points, see Group B2.

3 To monitor for indicative dose.

4 In the event that a single sample is taken in a year, a further sample must be taken if there is any change in relation to that supply that could affect the concentration of radionuclides in the water supply.

Table 3Group B2 parameters and circumstances for monitoring to be used for sampling at works or F1in water supply zones (or supply points)

Item number

Parameter 2

Circumstances

1

Benzene 1

In all circumstances

2

Boron 1

In all circumstances

3

Bromate 2

In all circumstances

4

Chloride 1

In all circumstances

5

F2Colstridium perfringens (including spores)(1)

In all circumstances

6

Cyanide 1

In all circumstances

7

1, 2 dichloroethane 1

In all circumstances

8

Fluoride 1

In all circumstances

9

Gross alpha 134

In all circumstances

10

Gross beta 134

In all circumstances

11

F3Indicative dose (1)

In all circumstances

12

Mercury 1

In all circumstances

13

Nitrite

When chloramination is not practised.

14

Pesticides and related products 1

In all circumstances

15

Radon 14

In all circumstances

16

Sulphate 1

In all circumstances

17

F4Tetrachloroethene/Trichloroethene(1)

In all circumstances

18

Tetrachloromethane 1

In all circumstances

19

Total organic carbon 1

20

F5. . .

F5. . .

21

Tritium 14

In all circumstances

Notes:

1 Sampling for these parameters may be within water supply zones (Group B1) or at supply points (Group B2).

2 Monitoring is required at supply points where sodium hypochlorite is not added after water has left the treatment works. In other circumstances, see Group B1.

3 To monitor for indicative dose.

4 In the event that a single sample is taken in a year, a further sample must be taken if there is any change in relation to that supply that could affect the concentration of radionuclides in the water supply.

Table 4Group A1 parameters

Item number

Parameter

1

Coliform bacteria

2

E. coli

3

Residual disinfectant

Table 5Group A2 parameters

Item number

Parameter

1

Coliform bacteria

2

Colony counts 22° C

3

E.coli

4

Nitrite

5

Residual disinfectant

6

Turbidity

Table 6Group A3 parameters

Item number

Parameter

1

Conductivity

Table 7Group A4 parameters

Item number

Parameter

1

Aluminium

2

Ammonium

3

Colony counts 22° C

4

Colour

5

Conductivity

6

Hydrogen ion

7

Iron

8

Manganese

9

Nitrate

10

Nitrite

11

Odour

12

Taste

13

Turbidity

PART 2Annual sampling frequencies: water supply zones

Table 8

Annual sampling frequencies for Group A4 parameters: water supply zones

Note:

This table and each table which follows it in this Part set out the annual sampling frequencies for all the substances and parameters comprising each of the groups to which they correspond, those groups having been outlined in Part 1 of this Schedule. These are determined for each water supply zone according to its estimated population (as specified in column one of each table in this Part). The number of samples to be taken is the standard number specified in column 2, unless a notice varying this number has been given under regulation 9.

Estimated population of water supply zone

Standard sampling frequency per year

<100

2

100-4,999

4

5,000—9,999

12

10,000-29,999

24

30,000-49,999

36

50,000-79,999

52

80,000-100,000

76

Table 9Annual sampling frequencies for Group B1 parameters: water supply zones

Estimated population of water supply zone

Standard sampling frequency per year

<100

1

100-4,999

4

5,000-100,000

8

Table 10Annual sampling frequencies for Group A1: water supply zones

Estimated population of water supply zone

Standard sampling frequency per year

<100

4

≥100

12 per 5,000 population

Note:

For the purposes of this Table, where the population is not an exact multiple of 5,000, the population figure must be rounded up to the nearest multiple of 5,000.

PART 3Annual sampling frequencies: treatment works and supply points

Table 11

Annual sampling frequencies for Group A2 parameters: treatment works or supply points

Note: This table and each table which follows it in this Part set out the annual sampling frequencies for all the substances and parameters comprising each of the groups to which they correspond at treatment works or supply points, those groups having been outlined in Part 1 of this Schedule. The frequencies are determined according to the volume of water supplied at each treatment works or supply point. The number of samples to be taken is the standard number specified in column 2, unless a notice varying this number has been issued under regulation 9.

Volume of water supplied m 3/day

Standard sampling frequency per year

<20

4

20-1,999

52

2,000-5,999

104

6,000-11,999

208

≥12,000

365

Table 12Annual sampling frequencies for Group A3 parameters: treatment works or supply points

Volume of water supplied m 3/day

Standard sampling frequency per year

<20

2

20-999

4

1,000-1999

12

2,000-5,999

24

6,000-9,999

36

10,000-15,999

52

16,000-32,999

104

33,000-49,999

156

50,000-67,999

208

68,000-84,999

260

85,000-101,999

312

102,000-119,999

365

120,000-241,999

730

242,000-484,999

1,460

485,000-728,999

2,190

Table 13Annual sampling frequencies for Group B2 parameters: treatment works or supply points

Volume of water supplied m 3/day

Standard sampling frequency per year

<20

1

20-999

4

1,000-49,999

8

50,000-89,999

12

90,000-299,999

24

300,000-649,999

36

≥650,000

48