SCHEDULE 6Requirements for slurry storage systems
10.
(1)
Subject to sub-paragraph (3), if the slurry storage tank or any effluent tank or reception pit is fitted with a drainage pipe there must be two valves in series on the pipe with each valve separated from the other by a minimum distance of 1 metre.
(2)
Each valve must be capable of shutting off the flow of slurry through the pipe and must be kept shut and locked in that position when not in use.
(3)
Sub-paragraph (1) does not apply in relation to a slurry storage tank that drains through the pipe into another slurry storage tank if the other tank is of equal or greater capacity or if the tops of the tanks are at the same level.