Chwilio Deddfwriaeth

Commission Decision of 1 March 2013 establishing the guidelines for Member States on calculating renewable energy from heat pumps from different heat pump technologies pursuant to Article 5 of Directive 2009/28/EC of the European Parliament and of the Council (notified under document C(2013) 1082) (Text with EEA relevance) (2013/114/EU)

 Help about what version

Pa Fersiwn

 Help about advanced features

Nodweddion Uwch

 Help about UK-EU Regulation

Legislation originating from the EU

When the UK left the EU, legislation.gov.uk published EU legislation that had been published by the EU up to IP completion day (31 December 2020 11.00 p.m.). On legislation.gov.uk, these items of legislation are kept up-to-date with any amendments made by the UK since then.

Close

Mae hon yn eitem o ddeddfwriaeth sy’n deillio o’r UE

Mae unrhyw newidiadau sydd wedi cael eu gwneud yn barod gan y tîm yn ymddangos yn y cynnwys a chyfeirir atynt gydag anodiadau.Ar ôl y diwrnod ymadael bydd tair fersiwn o’r ddeddfwriaeth yma i’w gwirio at ddibenion gwahanol. Y fersiwn legislation.gov.uk yw’r fersiwn sy’n weithredol yn y Deyrnas Unedig. Y Fersiwn UE sydd ar EUR-lex ar hyn o bryd yw’r fersiwn sy’n weithredol yn yr UE h.y. efallai y bydd arnoch angen y fersiwn hon os byddwch yn gweithredu busnes yn yr UE. EUR-Lex Y fersiwn yn yr archif ar y we yw’r fersiwn swyddogol o’r ddeddfwriaeth fel yr oedd ar y diwrnod ymadael cyn cael ei chyhoeddi ar legislation.gov.uk ac unrhyw newidiadau ac effeithiau a weithredwyd yn y Deyrnas Unedig wedyn. Mae’r archif ar y we hefyd yn cynnwys cyfraith achos a ffurfiau mewn ieithoedd eraill o EUR-Lex. The EU Exit Web Archive legislation_originated_from_EU_p3

Changes over time for: Commission Decision of 1 March 2013 establishing the guidelines for Member States on calculating renewable energy from heat pumps from different heat pump technologies pursuant to Article 5 of Directive 2009/28/EC of the European Parliament and of the Council (notified under document C(2013) 1082) (Text with EEA relevance) (2013/114/EU) (Annexes only)

 Help about opening options

Changes to legislation:

This version of this Decision was derived from EUR-Lex on IP completion day (31 December 2020 11:00 p.m.). It has not been amended by the UK since then. Find out more about legislation originating from the EU as published on legislation.gov.uk. Help about Changes to Legislation

Close

Changes to Legislation

Revised legislation carried on this site may not be fully up to date. At the current time any known changes or effects made by subsequent legislation have been applied to the text of the legislation you are viewing by the editorial team. Please see ‘Frequently Asked Questions’ for details regarding the timescales for which new effects are identified and recorded on this site.

ANNEXU.K. Guidelines for Member States on calculating renewable energy from heat pumps from different heat pump technologies pursuant to Article 5 of Directive 2009/28/EC

1.INTRODUCTIONU.K.

Annex VII to the Renewable Energy Directive 2009/28/EC (the Directive) establishes the basic method for calculating renewable energy supplied by heat pumps. Annex VII sets out three parameters that are needed for the calculation of the renewable energy from heat pumps to be counted for the renewable energy targets;

(a)

the power system efficiency (η or eta);

(b)

the estimated amount of useful energy supplied from the heat pumps (Qusable);

(c)

the ‘seasonal performance factor’ (SPF).

The methodology for determining the power system efficiency (η) was agreed in the Renewable Energy Statistics Working Party of 23 October 2009(1). The data required for the calculation of the power system efficiency is covered by Regulation (EC) No 1099/2008 of the European Parliament and of the Council of 22 October 2008(2) on energy statistics. The power system efficiency (η) is set at 0,455 (or 45,5 %), based on the most recent data for 2010(3), which is the value to be used towards 2020.

These guidelines therefore set out how Member States should estimate the two remaining parameters of Qusable and the ‘seasonal performance factor’ (SPF), taking into consideration differences in climatic conditions, especially very cold climates. With these guidelines Member States are enabled to calculate the amount of renewable energy supplied by heat pump technologies.

2.DEFINITIONSU.K.

For the purpose of this Decision, the following definitions apply:

  • ‘Qusable’ means the estimated total usable heat delivered by heat pumps, calculated as the product of the rated capacity for heating (Prated) and the annual equivalent heat pump hours (HHP), expressed in GWh;

  • ‘annual equivalent heat pump hours’ (HHP) means the assumed annual number of hours a heat pump has to provide heat at rated capacity to deliver the total usable heat delivered by heat pumps, expressed in h;

  • ‘rated capacity’ (Prated) means the cooling or heating capacity of the vapour compression cycle or sorption cycle of the unit at standard rating conditions;

  • ‘SPF’ shall mean the estimated average seasonal performance factor, which refers to the ‘net seasonal coefficient of performance in active mode’ (SCOPnet) for electrically driven heat pumps or ‘net seasonal primary energy ratio in active mode’ (SPERnet) for thermally driven heat pumps.

3.ESTIMATING SPF AND QUSABLE U.K.

3.1. Methodology Principles U.K.

The methodology follows three main principles:

(a)

the methodology has to be technically sound;

(b)

the approach must be pragmatic, balancing accuracy and cost-effectiveness;

(c)

the default factors for establishing the contribution of renewable energy from heat pumps are set at a conservative level to lower the risk of overestimating the contribution of renewable energy from heat pumps.

Member States are encouraged to improve the conservative default values by adapting them to national/regional circumstances, including the development of more accurate methodologies. Such improvements should be reported to the Commission and made publicly available.

3.2. Outline of methodology U.K.

In accordance with Annex VII to the Directive, the amount of renewable energy supplied by heat pump technologies (ERES) shall be calculated with the following formula:

Where:

— Qusable

=

the estimated total usable heat delivered by heat pumps [GWh],

— HHP

=

equivalent full load hours of operation [h],

— Prated

=

capacity of heat pumps installed, taking into account the lifetime of different types of heat pumps [GW],

— SPF

=

the estimated average seasonal performance factor (SCOPnet or SPERnet).

Default values for HHP and conservative default SPF values are set out in Tables 1 and 2 in Section 3.6.

3.3. Minimum performance of heat pumps to be considered as renewable energy under the Directive U.K.

In accordance with Annex VII to the Directive, Member States shall ensure that only heat-pumps with a SPF above 1,15 * 1/η are taken into account.

With power system efficiency (η) set at 45,5 % (see Section 1 and footnote 3) it implies that the minimum SPF of electrically driven heat pumps (SCOPnet) to be considered as renewable energy under the Directive is 2,5.

For heat pumps that are driven by thermal energy (either directly, or through the combustion of fuels), the power system efficiency (η) is equal to 1. For such heat pumps the minimum SPF (SPERnet) is 1,15 for the purposes of being considered as renewable energy under the Directive.

Member States should consider, in particular for air sourced heat pumps, how large a fraction of their already installed capacity of heat pumps have a SPF above the minimum performance. In that assessment the Member States may rely on both test data and measurements, although lack of data may in many cases reduce the assessment to expert judgment by each Member State. Such expert judgments should be conservative, meaning that the estimates rather underestimate than overestimate the contribution of heat pumps(4). In the case of air-sourced water heaters it is normally only in exceptional cases that such heat pumps have an SPF above the minimum threshold.

3.4. System boundaries for measuring energy from heat pumps U.K.

The system boundaries for measurement include the refrigerant cycle, the refrigerant pump and, for ad/absorption, in addition the sorption cycle and solvent pump. The determination of the SPF should be according to the seasonal coefficient of performance (SCOPnet) according to EN 14825:2012 or seasonal primary energy ratio (SPERnet) according to EN 12309. That implies that electric energy or fuel consumption for operation of the heat pump and circulation of the refrigerant should be taken into account. The corresponding system boundary is shown in Figure 1 below as SPFH2, highlighted in red.

Figure 1

System boundaries for measurement of SPF and Qusable

Source:SEPEMO build.U.K.

The following abbreviations are used in Figure 1:

ES_fan/pump

Energy used to run fan and/or pump that circulates the refrigerant

EHW_hp

Energy used to run the heat pump itself

Ebt_pump

Energy used to run pump that circulates the medium that absorbs the ambient energy (not relevant for all heat pumps)

EHW_bu

Energy used to run supplementary heater (not relevant for all heat pumps)

EB_fan/pump

Energy used to run fan and/or pump that circulates the medium that supplies the final usable heat

QH_hp

Heat supplied from the heat source via the heat pump

QW_hp

Heat supplied from the mechanical energy used to drive the heat pump

QHW_hp

Heat supplied from the supplementary heater (not relevant for all heat pumps)

ERES

Renewable aerothermal, geothermal or hydrothermal energy (the heat source) captured by the heat pump

ERES
Qusable

It follows from the system boundaries set out above, that the calculation of renewable energy supplied by the heat pump depends on the heat pump alone and not the heating system the heat pump is a part of. Inefficient use of heat pump energy is therefore a matter of energy efficiency, and should therefore not influence the calculations of renewable energy supplied by heat pumps.

3.5. Climate conditions U.K.

The definition of average, colder and warmer climate conditions follows the method as proposed in the draft for Commission Delegated Regulation on energy labelling of boilers(5), where ‘average climate conditions’, ‘colder climate conditions’ and ‘warmer climate conditions’ mean the temperature conditions characteristic for the cities of Strasbourg, Helsinki and Athens, respectively. Suggested climate condition areas are set out in Figure 2 below.

Figure 2

Climate condition areas

In cases where several climate conditions are existing within the same Member State, the Member States should estimate the installed capacity of heat pumps in the respective climate condition area.

3.6. Default values for SPF and Qusable for heat pumps U.K.

The default values for HHP and SPF (SCOPnet) for electrically driven heat pumps are as set out in the table below:

Table 1

Default values for HHP and SPF (SCOPnet) for electrically driven heat pumps

Climate conditions
Warmer climateAverage climateColder climate
Heat Pump Energy source:Energy source and distribution mediumHHPSPF(SCOPnet)HHPSPF(SCOPnet)HHPSPF(SCOPnet)
Aerothermal energyAir-Air1 2002,71 7702,61 9702,5
Air-Water1 1702,71 6402,61 7102,5
Air-Air (reversible) [X1120]2,77102,61 9702,5
Air-Water (reversible) [X1120]2,76602,61 7102,5
Exhaust Air-Air7602,76602,66002,5
Exhaust Air-Water7602,76602,66002,5
Geothermal energyGround-Air1 3403,22 0703,22 4703,2
Ground-Water1 3403,52 0703,52 4703,5
Hydrothermal heatWater-Air1 3403,22 0703,22 4703,2
Water-Water1 3403,52 0703,52 4703,5

The default values for HHP and SPF (SPERnet) for heat pumps driven by thermal energy are as set out in the table below:

Table 2

Default values for HHP and SPF (SPERnet) for heat pumps driven by thermal energy

Climate conditions
Warmer climateAverage climateColder climate
Heat Pump Energy source:Energy source and distribution mediumHHPSPF(SPERnet)HHPSPF(SPERnet)HHPSPF(SPERnet)
Aerothermal energyAir-Air1 2001,21 7701,21 9701,15
Air-Water1 1701,21 6401,21 7101,15
Air-Air (reversible) [X1120]1,27101,21 9701,15
Air-Water (reversible) [X1120]1,26601,21 7101,15
Exhaust Air-Air7601,26601,26001,15
Exhaust Air-Water7601,26601,26001,15
Geothermal energyGround-Air1 3401,42 0701,42 4701,4
Ground-Water1 3401,62 0701,62 4701,6
Hydrothermal heatWater-Air1 3401,42 0701,42 4701,4
Water-Water1 3401,62 0701,62 4701,6

The default values set out in Tables 1 and 2 above are typical for the segment of heat pumps with a SPF above the minimum threshold, meaning that heat pumps with SPF below 2,5 have not been taken into consideration when the typical values have been established(6).

3.7. Remarks related to non-electrically driven heat pumps U.K.

The heat pumps that do not use electricity, either use liquid or gaseous fuel to drive the compressor, or use an ad/absorption process (driven by combustion of liquid or gaseous fuel or by use of geothermal/solarthermal energy or waste heat) are delivering renewable energy as long as the ‘net seasonal primary energy ratio in active mode’ (SPERnet) is 115 % or larger than that value(7).

3.8. Remarks related to heat pumps using exhaust air as energy source U.K.

Heat pumps using exhaust air as energy source use ambient energy, and such heat pumps therefore supply renewable energy. But simultaneously such heat pumps recover the energy in the exhaust air, which is not aerothermal energy according to the Directive(8). It is therefore only the aerothermal energy that is counted as renewable energy. This is adjusted for by correcting the HHP values for such heat pumps as set out in Section 3.6.

3.9. Remarks to air sourced heat pumps U.K.

The HHP values shown in Tables 1 and 2 above are based on HHE values which includes not only the hours the heat pump is used, but also the hours that the supplementary heater is used. As the supplementary heater is outside of the system boundaries described in Section 3.4, the HHE values for all air source heat pumps are appropriately adjusted to only account for the useful heat delivered by the heat pump itself. The adjusted HHP figures are shown in Tables 1 and 2 above.

In the case of air sourced heat pumps with capacity reported for design conditions (and not for standard testing conditions), the HHE values should be used(9).

Only ambient air, i.e. outdoor air, can be the source of energy for an air-sourced heat pump.

3.10. Remarks related to reversible heat pumps U.K.

Firstly, reversible heat pumps in warm and to some extent average climates are often installed with the purpose of cooling the indoor environment, although they are also used to provide heating during the winter. As the cooling demand in the summer is higher than the heating demand in the winter, the rated capacity reflects the cooling demand rather than the need for heating. As the installed capacity is used as an indicator of heating demand, it implies that the statistics of installed capacity will not reflect the capacity installed for heating purposes. Moreover, reversible heat pumps are often installed in parallel to existing heating systems, implying that these heat pumps are not always used for heating purposes.

Both elements need appropriate adjustment. A conservative reduction(10) to 10 % for warm climate and 40 % for average climate is assumed in Tables 1 and 2 above. However, the real reduction is strongly dependent on national practices for providing heating systems, and national figures shall therefore be used where possible. The use of alternative figures should be submitted to the Commission, together with a report describing the method and data used. The Commission will, if necessary, translate the documents and publish them on its transparency platform.

3.11. Renewable energy contribution from hybrid heat pump systems U.K.

For hybrid heat pump systems, where the heat pump works in cooperation with other renewable energy technologies (e.g. solar thermal collectors used as pre-heaters), the accounting of renewable energy is at risk of inaccuracy. Member States shall therefore ensure that the accounting of renewable energy from hybrid heat pump systems is correct, and in particular ensure that no renewable energy is accounted more than once.

3.12. Guidance on the development of more accurate methodologies U.K.

It is envisaged and encouraged that Member States do their own estimations for both SPF and HHP. If improved estimations can be made, such national/regional approaches should be based on accurate assumptions, representative samples of sufficient size, resulting in a significantly improved estimate of renewable energy from heat pumps compared to the estimate obtained through the use of the method set out in this Decision. Such improved methodologies may be based on detailed calculation based on technical data taking into account, among other factors, year of installation, quality of installation, compressor type, operation mode, heat distribution system, bivalence point and the regional climate.

If measurements are only available at other system boundaries than the system boundary set out in Section 3.4, appropriate adjustments should be made.

Only those heat pumps with energy efficiency above the minimum threshold, as set out in Annex VII to the Directive, shall be included for the calculation of renewable energy for the purpose of the Directive.

Member States are invited, when alternative methodologies and/or values are used, to submit them to the Commission together with a report describing the method and data used. The Commission will, if necessary, translate the documents and publish them on its transparency platform.

4.CALCULATION EXAMPLEU.K.

The table below show an example for a hypothetical Member State located in average climate conditions, which has 3 different heat pump technologies installed.

a

The Member State in this hypothetical example did a survey of installed reversible air to air heat pumps and concluded that the equivalent of 48 % of the installed reversible heat pump capacity were used fully for heating, instead of the 40 % assumed in these guidelines. The HHP value is therefore adjusted up from 710 hours, which assumes 40 % and set out in Table 1, to 852 hours, which is representative for the estimated 48 %.

Air to air(reversible)Water to waterExhaust Air to water
Calculation Description Variable Unit
Capacity of heat pumps installedPratedGW25574215
of which the SPF is above the minimum thresholdPratedGW15070120
Equivalent full load hours of operationHHPh852a [X12 070]660
Estimated total usable heat delivered by heat pumpsQusableGWh127 800144 90079 200
the estimated average seasonal performance factorSPF2,63,52,6
Amount of renewable energy supplied per heat pump technologyERESGWh78 646103 50048 738
Total amount of renewable energy supplied by heat pumpsERESGWh230 885
(1)

See point 4.5 of minutes of 23 October 2009, available here: https://circabc.europa.eu/w/browse/be80a323-0f89-4ab7-b8f7-888e3ff351ed

(3)

The value for η in 2010 is 45,5 % (developing from 44,0 % in 2007, 44,7 % 2008 and 45,1 % in 2009), leading to a minimum SPF of 2,5 in 2010. This is a conservative estimate, as the power system efficiency is expected to increase towards 2020. However, as the basis of estimating the power system efficiency (η) changes due to updates in the underlying statistics, it is more predictable to set the η at a fixed level in order to avoid confusion regarding the minimum SPF requirements (create legal certainty) and also to facilitate methodology development by Member States (see Section 3.10). If necessary, η can be revised as per Article 2 (revision of guidelines if necessary by 31 December 2016).

(4)

Particular attention is required regarding reversible air sourced heat pumps, as a number of potential sources of overestimation exist, notably: (a) not all reversible heat pumps are used for heating, or only to a limited extent, and (b) older (and new less efficient) units may have an efficiency (SPF) below the required minimum threshold of 2,5.

(5)

This draft has not been adopted yet by the Commission (January 2013). The draft can be found in the WTO’s database: http://members.wto.org/crnattachments/2012/tbt/EEC/12_2119_00_e.pdf

(6)

This implies that Member States can consider the values set out in Tables 1 and 2 as average values of the electrically driven heat pumps that have SPF above the minimum 2,5.

(7)

See Section 3.3.

(8)

See Article 5(4), and definition of ‘aerothermal energy’ in Article 2(b) of the Directive.

(9)

These values are 1 336, 2 066 and 3 465 for warm, average and cold climate respectively.

(10)

An Italian study (referred to on page 48 of ‘Outlook 2011 — European Heat Pump Statistics’) finds that in less than 10 % of the cases, heat pumps were the only installed heat generator. As reversible air-air heat pumps is the single most installed heat pump technology type (60 % of all installed units — mostly installed in Italy, Spain and France, as well as Sweden and Finland), it is important to adjust the figures appropriately. The Impact Assessment of Commission Regulation (EU) No 206/2012 of 6 March 2012 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for air conditioners and comfort fans (OJ L 72, 10.3.2012, p. 7) assumes that EU wide, 33 % of reversible heat pumps are not used for heating. In addition one can assume that a large number of the 67 % of reversible heat pumps are only used partly for heating, as the heat pump is installed in parallel to another heating system. The proposed values are therefore appropriate to reduce the risk of over-estimation.

Yn ôl i’r brig

Options/Help

Print Options

Close

Mae deddfwriaeth ar gael mewn fersiynau gwahanol:

Y Diweddaraf sydd Ar Gael (diwygiedig):Y fersiwn ddiweddaraf sydd ar gael o’r ddeddfwriaeth yn cynnwys newidiadau a wnaed gan ddeddfwriaeth ddilynol ac wedi eu gweithredu gan ein tîm golygyddol. Gellir gweld y newidiadau nad ydym wedi eu gweithredu i’r testun eto yn yr ardal ‘Newidiadau i Ddeddfwriaeth’.

Gwreiddiol (Fel y’i mabwysiadwyd gan yr UE): Mae'r wreiddiol version of the legislation as it stood when it was first adopted in the EU. No changes have been applied to the text.

Close

Gweler y wybodaeth ychwanegol ochr yn ochr â’r cynnwys

Rhychwant ddaearyddol: Indicates the geographical area that this provision applies to. For further information see ‘Frequently Asked Questions’.

Dangos Llinell Amser Newidiadau: See how this legislation has or could change over time. Turning this feature on will show extra navigation options to go to these specific points in time. Return to the latest available version by using the controls above in the What Version box.

Close

Dewisiadau Agor

Dewisiadau gwahanol i agor deddfwriaeth er mwyn gweld rhagor o gynnwys ar y sgrin ar yr un pryd

Close

Rhagor o Adnoddau

Gallwch wneud defnydd o ddogfennau atodol hanfodol a gwybodaeth ar gyfer yr eitem ddeddfwriaeth o’r tab hwn. Yn ddibynnol ar yr eitem ddeddfwriaeth sydd i’w gweld, gallai hyn gynnwys:

  • y PDF print gwreiddiol y fel adopted version that was used for the EU Official Journal
  • rhestr o newidiadau a wnaed gan a/neu yn effeithio ar yr eitem hon o ddeddfwriaeth
  • pob fformat o’r holl ddogfennau cysylltiedig
  • slipiau cywiro
  • dolenni i ddeddfwriaeth gysylltiedig ac adnoddau gwybodaeth eraill
Close

Llinell Amser Newidiadau

Mae’r llinell amser yma yn dangos y fersiynau gwahanol a gymerwyd o EUR-Lex yn ogystal ag unrhyw fersiynau dilynol a grëwyd ar ôl y diwrnod ymadael o ganlyniad i newidiadau a wnaed gan ddeddfwriaeth y Deyrnas Unedig.

Cymerir dyddiadau fersiynau’r UE o ddyddiadau’r dogfennau ar EUR-Lex ac efallai na fyddant yn cyfateb â’r adeg pan ddaeth y newidiadau i rym ar gyfer y ddogfen.

Ar gyfer unrhyw fersiynau a grëwyd ar ôl y diwrnod ymadael o ganlyniad i newidiadau a wnaed gan ddeddfwriaeth y Deyrnas Unedig, bydd y dyddiad yn cyd-fynd â’r dyddiad cynharaf y daeth y newid (e.e. ychwanegiad, diddymiad neu gyfnewidiad) a weithredwyd i rym. Am ragor o wybodaeth gweler ein canllaw i ddeddfwriaeth ddiwygiedig ar Ddeall Deddfwriaeth.

Close

Rhagor o Adnoddau

Defnyddiwch y ddewislen hon i agor dogfennau hanfodol sy’n cyd-fynd â’r ddeddfwriaeth a gwybodaeth am yr eitem hon o ddeddfwriaeth. Gan ddibynnu ar yr eitem o ddeddfwriaeth sy’n cael ei gweld gall hyn gynnwys:

  • y PDF print gwreiddiol y fel adopted fersiwn a ddefnyddiwyd am y copi print
  • slipiau cywiro

liciwch ‘Gweld Mwy’ neu ddewis ‘Rhagor o Adnoddau’ am wybodaeth ychwanegol gan gynnwys

  • rhestr o newidiadau a wnaed gan a/neu yn effeithio ar yr eitem hon o ddeddfwriaeth
  • manylion rhoi grym a newid cyffredinol
  • pob fformat o’r holl ddogfennau cysylltiedig
  • dolenni i ddeddfwriaeth gysylltiedig ac adnoddau gwybodaeth eraill