Commission Delegated Regulation (EU) No 1254/2014 of 11 July 2014 supplementing Directive 2010/30/EU of the European Parliament and of the Council with regard to energy labelling of residential ventilation units (Text with EEA relevance)
When the UK left the EU, legislation.gov.uk published EU legislation that had been published by the EU up to IP completion day (31 December 2020 11.00 p.m.). On legislation.gov.uk, these items of legislation are kept up-to-date with any amendments made by the UK since then.
Mae unrhyw newidiadau sydd wedi cael eu gwneud yn barod gan y tîm yn ymddangos yn y cynnwys a chyfeirir atynt gydag anodiadau.Ar ôl y diwrnod ymadael bydd tair fersiwn o’r ddeddfwriaeth yma i’w gwirio at ddibenion gwahanol. Y fersiwn legislation.gov.uk yw’r fersiwn sy’n weithredol yn y Deyrnas Unedig. Y Fersiwn UE sydd ar EUR-lex ar hyn o bryd yw’r fersiwn sy’n weithredol yn yr UE h.y. efallai y bydd arnoch angen y fersiwn hon os byddwch yn gweithredu busnes yn yr UE. EUR-Lex Y fersiwn yn yr archif ar y we yw’r fersiwn swyddogol o’r ddeddfwriaeth fel yr oedd ar y diwrnod ymadael cyn cael ei chyhoeddi ar legislation.gov.uk ac unrhyw newidiadau ac effeithiau a weithredwyd yn y Deyrnas Unedig wedyn. Mae’r archif ar y we hefyd yn cynnwys cyfraith achos a ffurfiau mewn ieithoedd eraill o EUR-Lex. The EU Exit Web Archive legislation_originated_from_EU_p3
EU_status_warning_original_version
This legislation may since have been updated - see the latest available (revised) version
where:
SEC is the specific energy consumption for ventilation per m2 heated floor area of a dwelling or building [kWh/m2.a];
ta is annual operating hours [h/a];
pef is the primary energy factor for electric power generation and distribution [-];
qnet is net ventilation rate demand per m2 heated floor area [m3/h.m2];
MISC is an aggregated general typology factor, incorporating factors for ventilation effectiveness, duct leakage and extra infiltration [-];
CTRL is the ventilation control factor [-];
x is an exponent that takes into account non-linearity between thermal energy and electricity saving, depending on motor and drive characteristics [-];
SPI is specific power input [kW/(m3/h)];
th is total hours heating season [h];
ΔΤh is the average difference in indoor (19 °C) and outdoor temperature over a heating season, minus 3 K correction for solar and internal gains [K];
ηh is the average space heating efficiency [-];
cair is the specific heat capacity of air at constant pressure and density [kWh/(m3 K)];
qref is the reference natural ventilation rate per m2 heated floor area [m3/h.m2];
ηt is the thermal efficiency of heat recovery [-];
Qdefr is the annual heating energy per m2 heated floor area [kWh/m2.a] for defrosting, based on a variable electric resistance heating.
where:
tdefr is the duration of the defrosting period, i.e. when the outdoor temperature is below – 4 °C [h/a]; and
ΔΤdefr is the average difference in K between the outdoor temperature and – 4 °C during the defrosting period.
Qdefr applies only to bidirectional units with recuperative heat exchanger; for unidirectional units or units with regenerative heat exchangers, Qdefr = 0.
SPI and ηt are values derived from tests and calculation methods.
Other parameters and their defaults are given in Table 1. The SEC for label classification is based on the ‘average’ climate.
SEC calculation parameters
a Defrosting applies only to bidirectional units with recuperative heat exchanger and is calculated as Qdefr = tdefr*Δtdefr*cair*qnet*pef. For unidirectional units or units with regenerative heat exchangers, Qdefr = 0 | |||||
general typology | MISC | ||||
---|---|---|---|---|---|
Ducted ventilation units | 1,1 | ||||
Non-ducted ventilation units | 1,21 | ||||
ventilation control | CTRL | ||||
Manual control (no DCV) | 1 | ||||
Clock control (no DCV) | 0,95 | ||||
Central demand control | 0,85 | ||||
Local demand control | 0,65 | ||||
motor & drive | x-value | ||||
on/off & single speed | 1 | ||||
2-speed | 1,2 | ||||
3-speed | 1,5 | ||||
variable speed | 2 | ||||
Climate | th in h | ΔΤh in K | tdefr in h | ΔΤdefr in K | Qdefr ain kWh/a.m2 |
Cold | 6 552 | 14,5 | 1 003 | 5,2 | 5,82 |
Average | 5 112 | 9,5 | 168 | 2,4 | 0,45 |
Warm | 4 392 | 5 | — | — | — |
Defaults | value | ||||
specific heat capacity of air, cair in kWh/(m3K) | 0,000344 | ||||
net ventilation requirement per m2 heated floor area, qnet in m3/h.m2 | 1,3 | ||||
reference natural ventilation rate per m2 heated floor area, qref in m3/h.m2 | 2,2 | ||||
annual operating hours, ta in h | 8 760 | ||||
primary energy factor electric power generation & distribution, pef | 2,5 | ||||
space heating efficiency, ηh | 75 % |
Y Diweddaraf sydd Ar Gael (diwygiedig):Y fersiwn ddiweddaraf sydd ar gael o’r ddeddfwriaeth yn cynnwys newidiadau a wnaed gan ddeddfwriaeth ddilynol ac wedi eu gweithredu gan ein tîm golygyddol. Gellir gweld y newidiadau nad ydym wedi eu gweithredu i’r testun eto yn yr ardal ‘Newidiadau i Ddeddfwriaeth’.
Gwreiddiol (Fel y’i mabwysiadwyd gan yr UE): Mae'r wreiddiol version of the legislation as it stood when it was first adopted in the EU. No changes have been applied to the text.
Gallwch wneud defnydd o ddogfennau atodol hanfodol a gwybodaeth ar gyfer yr eitem ddeddfwriaeth o’r tab hwn. Yn ddibynnol ar yr eitem ddeddfwriaeth sydd i’w gweld, gallai hyn gynnwys:
Defnyddiwch y ddewislen hon i agor dogfennau hanfodol sy’n cyd-fynd â’r ddeddfwriaeth a gwybodaeth am yr eitem hon o ddeddfwriaeth. Gan ddibynnu ar yr eitem o ddeddfwriaeth sy’n cael ei gweld gall hyn gynnwys:
liciwch ‘Gweld Mwy’ neu ddewis ‘Rhagor o Adnoddau’ am wybodaeth ychwanegol gan gynnwys