Commission Delegated Regulation (EU) No 1254/2014 of 11 July 2014 supplementing Directive 2010/30/EU of the European Parliament and of the Council with regard to energy labelling of residential ventilation units (Text with EEA relevance)

 Help about what version

What Version

More Resources

 Help about UK-EU Regulation

Legislation originating from the EU

When the UK left the EU, legislation.gov.uk published EU legislation that had been published by the EU up to IP completion day (31 December 2020 11.00 p.m.). On legislation.gov.uk, these items of legislation are kept up-to-date with any amendments made by the UK since then.

Close

This item of legislation originated from the EU

Legislation.gov.uk publishes the UK version. EUR-Lex publishes the EU version. The EU Exit Web Archive holds a snapshot of EUR-Lex’s version from IP completion day (31 December 2020 11.00 p.m.).

Status:

This is the original version as it was originally adopted in the EU.
This legislation may since have been updated - see the latest available (revised) version

ANNEX VIIIMeasurements and calculations

1.The specific energy consumption (SEC) is calculated using the following equation:

where:

  • SEC is the specific energy consumption for ventilation per m2 heated floor area of a dwelling or building [kWh/m2.a];

  • ta is annual operating hours [h/a];

  • pef is the primary energy factor for electric power generation and distribution [-];

  • qnet is net ventilation rate demand per m2 heated floor area [m3/h.m2];

  • MISC is an aggregated general typology factor, incorporating factors for ventilation effectiveness, duct leakage and extra infiltration [-];

  • CTRL is the ventilation control factor [-];

  • x is an exponent that takes into account non-linearity between thermal energy and electricity saving, depending on motor and drive characteristics [-];

  • SPI is specific power input [kW/(m3/h)];

  • th is total hours heating season [h];

  • ΔΤh is the average difference in indoor (19 °C) and outdoor temperature over a heating season, minus 3 K correction for solar and internal gains [K];

  • ηh is the average space heating efficiency [-];

  • cair is the specific heat capacity of air at constant pressure and density [kWh/(m3 K)];

  • qref is the reference natural ventilation rate per m2 heated floor area [m3/h.m2];

  • ηt is the thermal efficiency of heat recovery [-];

  • Qdefr is the annual heating energy per m2 heated floor area [kWh/m2.a] for defrosting, based on a variable electric resistance heating.

    ,

    where:

    • tdefr is the duration of the defrosting period, i.e. when the outdoor temperature is below – 4 °C [h/a]; and

    • ΔΤdefr is the average difference in K between the outdoor temperature and – 4 °C during the defrosting period.

    Qdefr applies only to bidirectional units with recuperative heat exchanger; for unidirectional units or units with regenerative heat exchangers, Qdefr  = 0.

SPI and ηt are values derived from tests and calculation methods.

Other parameters and their defaults are given in Table 1. The SEC for label classification is based on the ‘average’ climate.

2.The annual electricity consumption per 100 m2 floor area (AEC) (in kWh/a electric per year); and the annual heating saved ((AHS), which means the annual saving in consumption of energy for heating (in kWh fuel gross calorific value per year) are calculated as follows, using the definitions in point 1, and the default values given in Table 1, for each type of climate (average, warm and cold):

;

.

Table 1

SEC calculation parameters

a

Defrosting applies only to bidirectional units with recuperative heat exchanger and is calculated as Qdefr = tdefr*Δtdefr*cair*qnet*pef. For unidirectional units or units with regenerative heat exchangers, Qdefr  = 0

general typology MISC
Ducted ventilation units 1,1
Non-ducted ventilation units 1,21
ventilation control CTRL
Manual control (no DCV) 1
Clock control (no DCV) 0,95
Central demand control 0,85
Local demand control 0,65
motor & drive x-value
on/off & single speed 1
2-speed 1,2
3-speed 1,5
variable speed 2
Climate th in h ΔΤh in K tdefr in h ΔΤdefr in K Qdefr ain kWh/a.m2
Cold 6 552 14,51 0035,2 5,82
Average 5 112 9,51682,4 0,45
Warm 4 392 5
Defaults value
specific heat capacity of air, cair in kWh/(m3K) 0,000344
net ventilation requirement per m2 heated floor area, qnet in m3/h.m2 1,3
reference natural ventilation rate per m2 heated floor area, qref in m3/h.m2 2,2
annual operating hours, ta in h 8 760
primary energy factor electric power generation & distribution, pef 2,5
space heating efficiency, ηh 75 %

Back to top

Options/Help

Print Options

Close

Legislation is available in different versions:

Latest Available (revised):The latest available updated version of the legislation incorporating changes made by subsequent legislation and applied by our editorial team. Changes we have not yet applied to the text, can be found in the ‘Changes to Legislation’ area.

Original (As adopted by EU): The original version of the legislation as it stood when it was first adopted in the EU. No changes have been applied to the text.

Close

Opening Options

Different options to open legislation in order to view more content on screen at once

Close

More Resources

Access essential accompanying documents and information for this legislation item from this tab. Dependent on the legislation item being viewed this may include:

  • the original print PDF of the as adopted version that was used for the EU Official Journal
  • lists of changes made by and/or affecting this legislation item
  • all formats of all associated documents
  • correction slips
  • links to related legislation and further information resources
Close

More Resources

Use this menu to access essential accompanying documents and information for this legislation item. Dependent on the legislation item being viewed this may include:

  • the original print PDF of the as adopted version that was used for the print copy
  • correction slips

Click 'View More' or select 'More Resources' tab for additional information including:

  • lists of changes made by and/or affecting this legislation item
  • confers power and blanket amendment details
  • all formats of all associated documents
  • links to related legislation and further information resources