Mae unrhyw newidiadau sydd wedi cael eu gwneud yn barod gan y tîm yn ymddangos yn y cynnwys a chyfeirir atynt gydag anodiadau.Ar ôl y diwrnod ymadael bydd tair fersiwn o’r ddeddfwriaeth yma i’w gwirio at ddibenion gwahanol. Y fersiwn legislation.gov.uk yw’r fersiwn sy’n weithredol yn y Deyrnas Unedig. Y Fersiwn UE sydd ar EUR-lex ar hyn o bryd yw’r fersiwn sy’n weithredol yn yr UE h.y. efallai y bydd arnoch angen y fersiwn hon os byddwch yn gweithredu busnes yn yr UE. EUR-Lex Y fersiwn yn yr archif ar y we yw’r fersiwn swyddogol o’r ddeddfwriaeth fel yr oedd ar y diwrnod ymadael cyn cael ei chyhoeddi ar legislation.gov.uk ac unrhyw newidiadau ac effeithiau a weithredwyd yn y Deyrnas Unedig wedyn. Mae’r archif ar y we hefyd yn cynnwys cyfraith achos a ffurfiau mewn ieithoedd eraill o EUR-Lex. The EU Exit Web Archive legislation_originated_from_EU_p3
EU_status_warning_original_version
This legislation may since have been updated - see the latest available (revised) version
Synchronous area | Frequency range | Time period for operation |
---|---|---|
Continental Europe | 47,5 Hz-48,5 Hz | To be specified by each TSO, but not less than 30 minutes |
48,5 Hz-49,0 Hz | To be specified by each TSO, but not less than the period for 47,5 Hz-48,5 Hz | |
49,0 Hz-51,0 Hz | Unlimited | |
51,0 Hz-51,5 Hz | 30 minutes | |
Nordic | 47,5 Hz-48,5 Hz | 30 minutes |
48,5 Hz-49,0 Hz | To be specified by each TSO, but not less than 30 minutes | |
49,0 Hz-51,0 Hz | Unlimited | |
51,0 Hz-51,5 Hz | 30 minutes | |
Great Britain | 47,0 Hz-47,5 Hz | 20 seconds |
47,5 Hz-48,5 Hz | 90 minutes | |
48,5 Hz-49,0 Hz | To be specified by each TSO, but not less than 90 minutes | |
49,0 Hz-51,0 Hz | Unlimited | |
51,0 Hz-51,5 Hz | 90 minutes | |
51,5 Hz-52,0 Hz | 15 minutes | |
Ireland and Northern Ireland | 47,5 Hz-48,5 Hz | 90 minutes |
48,5 Hz-49,0 Hz | To be specified by each TSO, but not less than 90 minutes | |
49,0 Hz-51,0 Hz | Unlimited | |
51,0 Hz-51,5 Hz | 90 minutes | |
Baltic | 47,5 Hz-48,5 Hz | To be specified by each TSO, but not less than 30 minutes |
48,5 Hz-49,0 Hz | To be specified by each TSO, but not less than the period for 47,5 Hz-48,5 Hz | |
49,0 Hz-51,0 Hz | Unlimited | |
51,0 Hz-51,5 Hz | To be specified by each TSO, but not less than 30 minutes |
The table shows the minimum time periods for which a transmission-connected demand facility, a transmission-connected distribution facility or a distribution system has to be capable of operating on different frequencies, deviating from a nominal value, without disconnecting from the network.
Synchronous area | Voltage range | Time period for operation |
---|---|---|
Continental Europe | 0,90 pu-1,118 pu | Unlimited |
1,118 pu-1,15 pu | To be specified by each TSO but not less than 20 minutes and not more than 60 minutes | |
Nordic | 0,90 pu-1,05 pu | Unlimited |
1,05 pu-1,10 pu | 60 minutes | |
Great Britain | 0,90 pu-1,10 pu | Unlimited |
Ireland and Northern Ireland | 0,90 pu-1,118 pu | Unlimited |
Baltic | 0,90 pu-1,118 pu | Unlimited |
1,118 pu-1,15 pu | 20 minutes |
The table shows the minimum time periods during which a transmission-connected demand facility, a transmission-connected distribution facility or a transmission-connected distribution system has to be capable of operating for voltages deviating from the reference 1 pu value at the connection point without disconnecting from the network where the voltage base for pu values is at or above 110 kV and up to (not including) 300 kV.
Synchronous area | Voltage range | Time period for operation |
---|---|---|
Continental Europe | 0,90 pu-1,05 pu | Unlimited |
1,05 pu-1,10 pu | To be specified by each TSO but not less than 20 minutes and not more than 60 minutes | |
Nordic | 0,90 pu-1,05 pu | Unlimited |
1,05 pu-1,10 pu | To be specified by each TSO but not more than 60 minutes | |
Great Britain | 0,90 pu-1,05 pu | Unlimited |
1,05 pu-1,10 pu | 15 minutes | |
Ireland and Northern Ireland | 0,90 pu-1,05 pu | Unlimited |
Baltic | 0,90 pu-1,097 pu | Unlimited |
1,097 pu-1,15 pu | 20 minutes |
The table shows the minimum time periods during which a transmission-connected demand facility, a transmission-connected distribution facility or a transmission-connected distribution system has to be capable of operating for voltages deviating from the reference 1 pu value at the connection point without disconnecting from the network, where the voltage base for pu values is from 300 kV to 400 kV (including).
Y Diweddaraf sydd Ar Gael (diwygiedig):Y fersiwn ddiweddaraf sydd ar gael o’r ddeddfwriaeth yn cynnwys newidiadau a wnaed gan ddeddfwriaeth ddilynol ac wedi eu gweithredu gan ein tîm golygyddol. Gellir gweld y newidiadau nad ydym wedi eu gweithredu i’r testun eto yn yr ardal ‘Newidiadau i Ddeddfwriaeth’.
Gwreiddiol (Fel y’i mabwysiadwyd gan yr UE): Mae'r wreiddiol version of the legislation as it stood when it was first adopted in the EU. No changes have been applied to the text.
Gallwch wneud defnydd o ddogfennau atodol hanfodol a gwybodaeth ar gyfer yr eitem ddeddfwriaeth o’r tab hwn. Yn ddibynnol ar yr eitem ddeddfwriaeth sydd i’w gweld, gallai hyn gynnwys:
Defnyddiwch y ddewislen hon i agor dogfennau hanfodol sy’n cyd-fynd â’r ddeddfwriaeth a gwybodaeth am yr eitem hon o ddeddfwriaeth. Gan ddibynnu ar yr eitem o ddeddfwriaeth sy’n cael ei gweld gall hyn gynnwys:
liciwch ‘Gweld Mwy’ neu ddewis ‘Rhagor o Adnoddau’ am wybodaeth ychwanegol gan gynnwys