Commission Regulation (EU) 2016/1447Dangos y teitl llawn

Commission Regulation (EU) 2016/1447 of 26 August 2016 establishing a network code on requirements for grid connection of high voltage direct current systems and direct current-connected power park modules (Text with EEA relevance)

Frequency rangeTime period for operation
[F147.0] Hz-[F247.5] Hz20 seconds
[F247.5] Hz-[F349.0] Hz90 minutes
[F349.0] Hz-[F451.0] HzUnlimited
[F451.0] Hz-[F551.5] Hz90 minutes
[F551.5] Hz-[F652.0] Hz15 minutes

Table 8: Minimum time periods for the 50 Hz nominal system for which a PPM shall be capable of operating for different frequencies deviating from a nominal value without disconnecting from the network.