Commission Regulation (EU) 2016/1447 of 26 August 2016 establishing a network code on requirements for grid connection of high voltage direct current systems and direct current-connected power park modules (Text with EEA relevance)

 Help about what version

Pa Fersiwn

 Help about advanced features

Nodweddion Uwch

 Help about UK-EU Regulation

Legislation originating from the EU

When the UK left the EU, legislation.gov.uk published EU legislation that had been published by the EU up to IP completion day (31 December 2020 11.00 p.m.). On legislation.gov.uk, these items of legislation are kept up-to-date with any amendments made by the UK since then.

Close

Mae hon yn eitem o ddeddfwriaeth sy’n deillio o’r UE

Mae unrhyw newidiadau sydd wedi cael eu gwneud yn barod gan y tîm yn ymddangos yn y cynnwys a chyfeirir atynt gydag anodiadau.Ar ôl y diwrnod ymadael bydd tair fersiwn o’r ddeddfwriaeth yma i’w gwirio at ddibenion gwahanol. Y fersiwn legislation.gov.uk yw’r fersiwn sy’n weithredol yn y Deyrnas Unedig. Y Fersiwn UE sydd ar EUR-lex ar hyn o bryd yw’r fersiwn sy’n weithredol yn yr UE h.y. efallai y bydd arnoch angen y fersiwn hon os byddwch yn gweithredu busnes yn yr UE. EUR-Lex Y fersiwn yn yr archif ar y we yw’r fersiwn swyddogol o’r ddeddfwriaeth fel yr oedd ar y diwrnod ymadael cyn cael ei chyhoeddi ar legislation.gov.uk ac unrhyw newidiadau ac effeithiau a weithredwyd yn y Deyrnas Unedig wedyn. Mae’r archif ar y we hefyd yn cynnwys cyfraith achos a ffurfiau mewn ieithoedd eraill o EUR-Lex. The EU Exit Web Archive legislation_originated_from_EU_p3

Changes to legislation:

There are currently no known outstanding effects for the Commission Regulation (EU) 2016/1447, CHAPTER 2 . Help about Changes to Legislation

Close

Changes to Legislation

Revised legislation carried on this site may not be fully up to date. At the current time any known changes or effects made by subsequent legislation have been applied to the text of the legislation you are viewing by the editorial team. Please see ‘Frequently Asked Questions’ for details regarding the timescales for which new effects are identified and recorded on this site.

CHAPTER 2 U.K. Compliance testing

Article 71U.K.Compliance testing for HVDC systems

1.Equipment certificates may be used instead of part of the tests below, on the condition that they are provided to the relevant system operator.

2.With regard to the reactive power capability test:

(a)the HVDC converter unit or the HVDC converter station shall demonstrate its technical capability to provide leading and lagging reactive power capability according to Article 20;

(b)the reactive power capability test shall be carried out at maximum reactive power, both leading and lagging, and concerning the verification of the following parameters:

(i)

Operation at minimum HVDC active power transmission capacity;

(ii)

Operation at maximum HVDC active power transmission capacity;

(iii)

Operation at active power setpoint between those minimum and maximum HVDC active power transmission capacity.

(c)the test shall be deemed passed, provided that the following conditions are cumulatively fulfilled:

(i)

the HVDC converter unit or the HVDC converter station has been operating no shorter than 1 hour at maximum reactive power, both leading and lagging, for each parameter as referred to in point (b);

(ii)

the HVDC converter unit or the HVDC converter station demonstrates its capability to change to any reactive power setpoint within the applicable reactive power range within the specified performance targets of the relevant reactive power control scheme; and

(iii)

no action of any protection within the operation limits specified by reactive power capacity diagram occurs.

3.With regard to the voltage control mode test:

(a)the HVDC converter unit or the HVDC converter station shall demonstrate its capability to operate in voltage control mode in the conditions set forth in Article 22(3);

(b)the voltage control mode test shall apply concerning the verification of the following parameters:

(i)

the implemented slope and deadband of the static characteristic;

(ii)

the accuracy of the regulation;

(iii)

the insensitivity of the regulation;

(iv)

the time of reactive power activation.

(c)the test shall be deemed passed, provided that the following conditions are cumulatively fulfilled:

(i)

the range of regulation and adjustable droop and deadband is compliant with agreed or decided characteristic parameters, according to Article 22(3);

(ii)

the insensitivity of voltage control is not higher than [F10.01] pu;

(iii)

following a step change in voltage, 90 % of the change in reactive power output has been achieved within the times and tolerances according to Article 22(3).

4.With regard to the reactive power control mode test:

(a)the HVDC converter unit or the HVDC converter station shall demonstrate its capability to operate in reactive power control mode, according to the conditions referred to in Article 22(4);

(b)the reactive power control mode test shall be complementary to the reactive power capability test;

(c)the reactive power control mode test shall apply concerning the verification of the following parameters:

(i)

the reactive power setpoint range and step;

(ii)

the accuracy of the regulation; and

(iii)

the time of reactive power activation.

(d)the test shall be deemed passed, provided that the following conditions are cumulatively fulfilled:

(i)

the reactive power setpoint range and step is ensured according to Article 22(4);

(ii)

the accuracy of the regulation is compliant with the conditions as referred to in Article 22(3).

5.With regard to the power factor control mode test:

(a)the HVDC converter unit or the HVDC converter station shall demonstrate its capability to operate in power factor control mode according to the conditions referred to in Article 22(5);

(b)the power factor control mode test shall apply concerning the verification of the following parameters:

(i)

the power factor setpoint range;

(ii)

the accuracy of the regulation;

(iii)

the response of reactive power due to step change of active power.

(c)the test shall be deemed passed, provided that the following conditions are cumulatively fulfilled:

(i)

the power factor setpoint range and step is ensured according to Article 22(5);

(ii)

the time of reactive power activation as result of step active power change does not exceed the requirements specified in accordance with Article 22(5);

(iii)

the accuracy of the regulation is compliant with the value, as referred to in Article 22(5).

6.With regard to the FSM response test:

(a)the HVDC system shall demonstrate its technical capability to continuously modulate active power over the full operating range between maximum HVDC active power transmission capacity and minimum HVDC active power transmission capacity to contribute to frequency control and shall verify the steady-state parameters of regulations, such as droop and deadband and dynamic parameters, including robustness during frequency step change response and large, fast frequency changes;

(b)the test shall be carried out by simulating frequency steps and ramps big enough to activate at least 10 % of the full active power frequency response range in each direction, taking into account the droop settings and the deadband. Simulated frequency deviation signals shall be injected into the controller of the HVDC converter unit or the HVDC converter station;

(c)the test shall be deemed to be passed, provided that the following conditions are all fulfilled:

(i)

activation time of full active power frequency response range as result of a step frequency change has been no longer than required by Annex II;

(ii)

undamped oscillations do not occur after the step change response;

(iii)

the initial delay time has been according to Annex II;

(iv)

the droop settings are available within the range provided for in Annex II and deadband (thresholds) is not more than the value in Annex II;

(v)

insensitivity of active power frequency response at any relevant operating point does not exceed the requirements set forth in Annex II.

7.With regard to the LFSM-O response test:

(a)the HVDC system shall demonstrate its technical capability to continuously modulate active power to contribute to frequency control in case of large increase of frequency in the system and shall verify the steady-state parameters of regulations, such as droop and deadband, and dynamic parameters, including frequency step change response;

(b)the test shall be carried out by simulating frequency steps and ramps big enough to activate at least 10 % of the full operating range for active power, taking into account the droop settings and the deadband. Simulated frequency deviation signals shall be injected into the controller of the HVDC converter unit or the HVDC converter station;

(c)the test shall be deemed passed, provided that the following conditions are both fulfilled:

(i)

the test results, for both dynamic and static parameters, are in line with the requirements as referred to in Annex II;

(ii)

undamped oscillations do not occur after the step change response.

8.With regard to the LFSM-U response test:

(a)the HVDC system shall demonstrate its technical capability to continuously modulate active power at operating points below maximum HVDC active power transmission capacity to contribute to frequency control in case of large drop of frequency in the system;

(b)the test shall be carried out by simulating at appropriate active power load points with low frequency steps and ramps big enough to activate at least 10 % of the full operating range for active power, taking into account the droop settings and the deadband. Simulated frequency deviation signals shall be injected into the controller of the HVDC converter unit or the HVDC converter station;

(c)the test shall be deemed passed, provided that the following conditions are both fulfilled:

(i)

the test results, for both dynamic and static parameters, are in line with the requirements as referred to in Annex II;

(ii)

undamped oscillations do not occur after the step change response.

9.With regard to the active power controllability test:

(a)the HVDC system shall demonstrate its technical capability to continuously modulate active power over the full operating range according to Article 13(1)(a) and (d);

(b)the test shall be carried out by sending manual and automatic instructions by the relevant TSO;

(c)the test shall be deemed passed, provided that the following conditions are cumulatively fulfilled:

(i)

the HVDC system has demonstrated stable operation;

(ii)

the time of adjustment of the active power is shorter than the delay specified pursuant to Article 13(1)(a);

(iii)

the dynamic response of the HVDC system when receiving instructions for the purposes of exchange or sharing of reserves, or for participating in imbalance netting processes, if capable of fulfilling the requirements for these products, as specified by the relevant TSO, has been demonstrated.

10.With regard to the ramping rate modification test:

(a)the HVDC system shall demonstrate its technical capability to adjust the ramping rate according to Article 13(2);

(b)the test shall be carried out by relevant TSO sending instructions of ramping modifications;

(c)the test shall be deemed passed, provided that the following conditions are cumulatively fulfilled:

(i)

ramping rate is adjustable;

(ii)

the HVDC system has demonstrated stable operation during ramping periods.

11.With regard to the black start test, if applicable:

(a)the HVDC system shall demonstrate its technical capability to energise the busbar of the remote AC substation to which it is connected, within a time frame specified by the relevant TSO, according to Article 37(2);

(b)the test shall be carried out while the HVDC system starts from shut down;

(c)the test shall be deemed passed, provided that the following conditions are cumulatively fulfilled:

(i)

the HVDC system has demonstrated being able to energise the busbar of the remote AC-substation to which it is connected;

(ii)

the HVDC system operates from a stable operating point at agreed capacity, according to the procedure of Article 37(3).

Article 72U.K.Compliance testing for DC-connected power park modules and remote-end HVDC converter units

1.Equipment certificates may be used instead of part of the tests below, on the condition that they are provided to the relevant system operator.

2.With regard to the reactive power capability test of DC-connected power park modules:

(a)the DC-connected power park module shall demonstrate its technical capability to provide leading and lagging reactive power capability according to Article 40(2);

(b)the reactive power capability test shall be carried out at maximum reactive power, both leading and lagging, and concerning the verification of the following parameters:

(i)

operation in excess of 60 % of maximum capacity for 30 minutes;

(ii)

operation within the range of 30-50 % of maximum capacity for 30 minutes; and

(iii)

operation within the range of 10-20 % of maximum capacity for 60 minutes.

(c)the test shall be deemed passed, provided that the following conditions are cumulatively fulfilled:

(i)

the DC-connected power park module has been operating no shorter than requested duration at maximum reactive power, both leading and lagging, in each parameter as referred to in point (b);

(ii)

the DC-connected power park module has demonstrated its capability to change to any reactive power setpoint within the agreed or decided reactive power range within the specified performance targets of the relevant reactive power control scheme; and

(iii)

no action of any protection within the operation limits specified by reactive power capacity diagram occurs.

3.With regard to the reactive power capability test of remote-end HVDC converter units:

(a)the HVDC converter unit or the HVDC converter station shall demonstrate its technical capability to provide leading and lagging reactive power capability according to Article 48(2);

(b)the test shall be deemed passed, provided that the following conditions are cumulatively fulfilled:

(i)

the HVDC converter unit or the HVDC converter station has been operating no shorter than 1 hour at maximum reactive power, both leading and lagging, at:

  • minimum HVDC active power transmission capacity;

  • maximum HVDC active power transmission capacity; and

  • an active power operating point between those maximum and minimum ranges.

(ii)

the HVDC converter unit or the HVDC converter station demonstrates its capability to change to any reactive power setpoint within the agreed or decided reactive power range within the specified performance targets of the relevant reactive power control scheme; and

(iii)

no action of any protection within the operation limits specified by reactive power capacity diagram occurs.

4.With regard to the voltage control mode test:

(a)the DC-connected power park module shall demonstrate its capability to operate in voltage control mode in the conditions set forth in Article 21 of Regulation (EU) 2016/631;

(b)the voltage control mode test shall apply concerning the verification of the following parameters:

(i)

the implemented slope and deadband of the static characteristic;

(ii)

the accuracy of the regulation;

(iii)

the insensitivity of the regulation;

(iv)

the time of reactive power activation.

(c)the test shall be deemed passed, provided that the following conditions are cumulatively fulfilled:

(i)

the range of regulation and adjustable the droop and deadband is compliant with agreed or decided characteristic parameters, according to Article 21(3)(d) of Regulation (EU) 2016/631;

(ii)

the insensitivity of voltage control is not higher than [F20.01] pu, according to Article 21(3)(d) of Regulation (EU) 2016/631;

(iii)

following a step change in voltage, 90 % of the change in reactive power output has been achieved within the times and tolerances according to Article 21(3)(d) of Regulation (EU) 2016/631.

5.With regard to the reactive power control mode test:

(a)the DC-connected power park module shall demonstrate its capability to operate in reactive power control mode, according to the conditions referred to in Article 21(3)(d)(iii) of Regulation (EU) 2016/631;

(b)the reactive power control mode test shall be complementary to the reactive power capability test;

(c)the reactive power control mode test shall apply concerning the verification of the following parameters:

(i)

the reactive power setpoint range and step;

(ii)

the accuracy of the regulation;

(iii)

the time of reactive power activation.

(d)the test shall be deemed passed, provided that the following conditions are cumulatively fulfilled:

(i)

the reactive power setpoint range and step is ensured according to Article 21(3)(d) of Regulation (EU) 2016/631;

(ii)

the accuracy of the regulation is compliant with the conditions as referred to in Article 21(3)(d) of Regulation (EU) 2016/631.

6.With regard to the power factor control mode test:

(a)the DC-connected power park module shall demonstrate its capability to operate in power factor control mode according to the conditions referred to in Article 21(3)(d)(iv) of Regulation (EU) 2016/631;

(b)the power factor control mode test shall apply concerning the verification of the following parameters:

(i)

the power factor setpoint range;

(ii)

the accuracy of the regulation;

(iii)

the response of reactive power due to step change of active power.

(c)the test shall be deemed passed, provided that the following conditions are cumulatively fulfilled:

(i)

the power factor setpoint range and step is ensured according to Article 21(3)(d) of Regulation (EU) 2016/631;

(ii)

the time of reactive power activation as result of step active power change does not exceed the requirement according to Article 21(3)(d) of Regulation (EU) 2016/631;

(iii)

the accuracy of the regulation is compliant with the value, as referred to in Article 21(3)(d) of Regulation (EU) 2016/631.

7.With regard to the tests identified in paragraphs 4, 5 and 6 the relevant TSO may select only two of the three control options for testing.

8.With regard to LFSM-O response of DC-connected power park module, the tests shall be carried out in accordance with Article 47(3) of Regulation (EU) 2016/631.

9.With regard to LFSM-U response of DC-connected power park module, the tests shall be carried out in accordance with Article 48(3) of Regulation (EU) 2016/631.

10.With regard to active power controllability of DC-connected power park module, the tests shall be carried out in accordance with 48(2) of Regulation (EU) 2016/631.

11.With regard to FSM response of DC-connected power park module, the tests shall be carried out in accordance with Article 48(4) of Regulation (EU) 2016/631.

12.With regard to frequency restoration control of DC-connected power park module, the tests shall be carried out in accordance with Article 45(5) of Regulation (EU) 2016/631.

13.With regard to fast signal response of DC-connected power park module, the test shall be deemed passed if the DC-connected power park module can demonstrate its response within the time specified in Article 39(1)(a).

14.With regard to tests for DC-connected power park modules where the AC collection network is not at nominal 50 Hz frequency, the relevant system operator, in coordination with the relevant TSO, shall agree with the DC-connected power park module owner the compliance tests required.

Yn ôl i’r brig

Options/Help

Print Options

Close

Mae deddfwriaeth ar gael mewn fersiynau gwahanol:

Y Diweddaraf sydd Ar Gael (diwygiedig):Y fersiwn ddiweddaraf sydd ar gael o’r ddeddfwriaeth yn cynnwys newidiadau a wnaed gan ddeddfwriaeth ddilynol ac wedi eu gweithredu gan ein tîm golygyddol. Gellir gweld y newidiadau nad ydym wedi eu gweithredu i’r testun eto yn yr ardal ‘Newidiadau i Ddeddfwriaeth’.

Gwreiddiol (Fel y’i mabwysiadwyd gan yr UE): Mae'r wreiddiol version of the legislation as it stood when it was first adopted in the EU. No changes have been applied to the text.

Close

Gweler y wybodaeth ychwanegol ochr yn ochr â’r cynnwys

Rhychwant ddaearyddol: Indicates the geographical area that this provision applies to. For further information see ‘Frequently Asked Questions’.

Dangos Llinell Amser Newidiadau: See how this legislation has or could change over time. Turning this feature on will show extra navigation options to go to these specific points in time. Return to the latest available version by using the controls above in the What Version box.

Close

Dewisiadau Agor

Dewisiadau gwahanol i agor deddfwriaeth er mwyn gweld rhagor o gynnwys ar y sgrin ar yr un pryd

Close

Rhagor o Adnoddau

Gallwch wneud defnydd o ddogfennau atodol hanfodol a gwybodaeth ar gyfer yr eitem ddeddfwriaeth o’r tab hwn. Yn ddibynnol ar yr eitem ddeddfwriaeth sydd i’w gweld, gallai hyn gynnwys:

  • y PDF print gwreiddiol y fel adopted version that was used for the EU Official Journal
  • rhestr o newidiadau a wnaed gan a/neu yn effeithio ar yr eitem hon o ddeddfwriaeth
  • pob fformat o’r holl ddogfennau cysylltiedig
  • slipiau cywiro
  • dolenni i ddeddfwriaeth gysylltiedig ac adnoddau gwybodaeth eraill
Close

Llinell Amser Newidiadau

Mae’r llinell amser yma yn dangos y fersiynau gwahanol a gymerwyd o EUR-Lex yn ogystal ag unrhyw fersiynau dilynol a grëwyd ar ôl y diwrnod ymadael o ganlyniad i newidiadau a wnaed gan ddeddfwriaeth y Deyrnas Unedig.

Cymerir dyddiadau fersiynau’r UE o ddyddiadau’r dogfennau ar EUR-Lex ac efallai na fyddant yn cyfateb â’r adeg pan ddaeth y newidiadau i rym ar gyfer y ddogfen.

Ar gyfer unrhyw fersiynau a grëwyd ar ôl y diwrnod ymadael o ganlyniad i newidiadau a wnaed gan ddeddfwriaeth y Deyrnas Unedig, bydd y dyddiad yn cyd-fynd â’r dyddiad cynharaf y daeth y newid (e.e. ychwanegiad, diddymiad neu gyfnewidiad) a weithredwyd i rym. Am ragor o wybodaeth gweler ein canllaw i ddeddfwriaeth ddiwygiedig ar Ddeall Deddfwriaeth.

Close

Rhagor o Adnoddau

Defnyddiwch y ddewislen hon i agor dogfennau hanfodol sy’n cyd-fynd â’r ddeddfwriaeth a gwybodaeth am yr eitem hon o ddeddfwriaeth. Gan ddibynnu ar yr eitem o ddeddfwriaeth sy’n cael ei gweld gall hyn gynnwys:

  • y PDF print gwreiddiol y fel adopted fersiwn a ddefnyddiwyd am y copi print
  • slipiau cywiro

liciwch ‘Gweld Mwy’ neu ddewis ‘Rhagor o Adnoddau’ am wybodaeth ychwanegol gan gynnwys

  • rhestr o newidiadau a wnaed gan a/neu yn effeithio ar yr eitem hon o ddeddfwriaeth
  • manylion rhoi grym a newid cyffredinol
  • pob fformat o’r holl ddogfennau cysylltiedig
  • dolenni i ddeddfwriaeth gysylltiedig ac adnoddau gwybodaeth eraill